Appendix A Technical Specifications
Router Specifications
A-4
Cisco 12016, Cisco 12416, and Cisco 12816 Router Installation and Configuration Guide
OL-11495-01
Input current rating 60A maximum @ 40.5 VDC
Source DC service requirement Sufficient to supply the rated input current. Local codes apply.
1. For each PEM.
Caution To ensure that the chassis configuration complies with the required power
budgets, use the on-line power calculator. Failure to properly verify the
configuration may result in an unpredictable state if one of the power units fails.
Contact your local sales representative for assistance.
Tab l e A-4 Environmental Specifications
Description Value
Tempe ratu re Operating: 32° to 104°F (0° to 40°C)
Nonoperating: –4° to 149°F (–20° to 65°C)
Humidity Operating: 10 to 90% noncondensing
Nonoperating: 5 to 95% noncondensing
Altitude Operating: 0 to 10,000 ft (0 to 3,000 m)
Nonoperating: 0 to 15,000 ft (0 to 4,570 m)
Heat dissipation 11,602 BTU/hr maximum (original series)
16,378 BTU/hr maximum (enhanced series)
Acoustic noise 70 dBa maximum
Shock Operating (halfsine): 21 in./sec (0.53 m/sec)
Nonoperating (trapezoidal pulse): 20G1, 52 in./sec (1.32 m/sec)
1. G is a value of acceleration, where 1G equals 32.17 ft/sec2 (9.81 m/sec2).
Vibrat ion Operating: 0.35 Grms2 from 3 to 500 Hz
Nonoperating: 1.0 Grms from 3 to 500 Hz
2. Grms is the root mean square value of acceleration.
Table A-3 DC Electrical Specifications
Description Value