4
ABBLCCLDEGKH P M
G18S P 275 90 200 365 475 340 255 115 230 125 121÷134 M8
Fig. 1
PART I: INSTALLATION MANUAL
TECHNICAL DATA
BURNER MODEL IDENTIFICATION
Burners are identified by burner type and model. Burner type identification is described as follow:
Type: G18 Model: G-. SP. S. *. A.
(1) (2) (3) (4) (5) (6)
(1) BURNER TYPE G18 SP - PG25 SP - PG30 TN
(2) FUEL G = Light oil (Viscosity at 20°C 5 cSt)
(3) ADJUSTMENT SP = Soft Start
TN = Single Stage
(4) BLAST TUBE LENGHT (See overall dimensions)
S = Standard
L = Long
(5) DESTINATION COUNTRY * see data plate
(6) SPECIAL VERSIONS A = Standard
OVERALL DIMENSIONS
INSTALLATION
BURNER TYPE G18 SP PG25 SP PG30 TN
Input min kcal/h 90.300 140.200 140.200
max kcal/h 180.000 250.200 300.000
min kW 105 163 163
max kW 209 291 349
Oil firing rate kg/h min . 9 14 14
kg/h max. 18 25 30
Fuel light oil light oil light oil
Electrical supply 230V 230V 230V
Frequency 50 Hz 50 Hz 50 Hz
Motor 2800 g/1' kW 0.25 0.37 0.37
A absorbed A 1.5 2.2 2.2
Total power absorption kW 0.55 0.87 0.87
Operation Soft start Soft start Single
stage