VAX 7000 Model 810
Specifications
Physical Characteristics | Operating |
| Shipping | |
Height | 170.0 cm (67.0 in.) |
| 195.0 cm (76.7 in.) | |
Width | 80.0 cm (31.5 in.) |
| 109.5 cm (43.1 in.) | |
Depth | 87.5 cm (34.4 in.) |
| 121.0 cm (47.5 in.) | |
Weight, full configuration |
|
|
|
|
Without batteries | 408 kg (900 lb) |
| 448 kg (1000 lb) | |
With batteries | 545 kg (1200 lb) |
| 585 kg (1300 lb) | |
Clearances | Operating |
| Service |
|
|
|
|
| |
Front | 1.0 m (40 in.) |
| 1.5 m (59 in.) | |
Rear | 1.0 m (40 in.) |
| 1.0 m (40 in.) | |
Environmental | Operating |
| Nonoperating | |
Temperature | 15° to 28° C (59° to 82°F) | |||
Humidity | 20% to 80% |
| 10% to 95% | |
Altitude |
| 9,100 m (30,000 ft) | ||
Vibration | ||||
Heat dissipation1 | Fully Configured System | Fully Configured System | ||
| (System Cabinet) |
| (System Cabinet with Two | |
| 17,700 Btu/hr, 5,200 W | I/O Expansion Cabinets) | ||
| Minimally Configured System2 | 47,000 Btu/hr, 13,800 W | ||
| (System Cabinet) |
|
|
|
| 3,400 Btu/hr, 1,000 W |
|
| |
Power requirements3 | U.S./Canada | Europe/APA | Japan | |
Nominal voltage | 120/208 V | 202 V | ||
Frequency range |
| |||
Phases | ||||
| ||||
|
|
|
| |
Maximum input | 24 A rms | 12.8 A rms | 24 A rms | |
current/phase |
|
|
|
|
Surge current | 50 A peak | 50 A peak | 50 A peak | |
Rating | 30 A | 16 A |
| 30 A |
Power cap (system) | DEC | DEC | ||
Receptacle (site) | DEC | See footnote 4 | DEC | |
Receptacle | NEMA | IEC309 |
| NEMA |
PCS/PDS/PDU/UPS cable | BC24W | BN29X |
| BC24W |
1.Power system provides unity power factor which allows full use of input line current (watts=VA). Approximate Btu's for a given system configuration can be calculated by multiplying the “EPU” value per cabinet by 85.4.
2.Minimally configured system contains one regulator, one CPU module, one memory module, one IOP module, and one Ethernet controller.
3.Power cord is required for system cabinet and each I/O expansion cabinet.
4.Receptacle type is Hubbell 516R6 or equivalent.
VAX Systems 4.39