HALO®
Installation Instructions for LV211 End Feed
701934Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • 770.486.4800 • FAX 770.486.4801

WARNING

Avoid Fire or Electric Shock
Follow installation instructions carefully.
If unsure about electrical installation
consult a qualified electrician.
1

Safety Information

Read carefully for your protection and save all instructions.
Turn off the power at fuse or circuit breaker box before installation and
maintenance
Wear rubber-soled shoes and work on a sturdy wooden ladder
NOTE:Power supplies should be used on a 120-Volt or 277-Volt fused
circuit. (Check labeling)
This Lighting System must be installed according to National Electric
Code and local building codes.
Ground power supply to avoid potential electric shock.
To avoid a hazard to children, account for all parts and destroy all
packing materials.
WARNING: Risk of fire. Most dwellings built before 1985 have supply
wire rated 60°C. Consult a qualified electrician before installing.
If you are unsure about wiring, consult a qualified electrician.
Do not install any lampholder closer than 6" from any curtain or
similar combustible material.
Wireway Channel is intended to be connected only to 12 volt or
24-volt secondary of an isolated type transformer supply.
Do not exceed nominal supply voltage.
CAUTION:To reduce risk of fire and electrical shock, use only fixtures
and fittings intended for use with Linea LV 100 series channel, or
Linea LV-114 and LV-214 Wire Way channel.
CAUTION:Do not exceed 25-amp capacity of Wireway channel
(600 watts at 24 volts).
Layout Planning
Carefully plan your layout and determine location and type of feed point
and connectors required. For most installations it is recommended that
the feed point be attached to the channel prior to mounting the channel
to the mounting surface.
NOTE: The maximum recommended length of Wireway channel feed by
a single feed point is 20' when used with electronic power supplies and
40' when used with magnetic power supplies.