Unit Number: P 7 - M 4 2 T- E 7 T _
P 7 - M 3 2 T- E 7 T _
P H O T O M E T R I C S
Test No. H35091
C a n d e l a s
Vertical | CD |
Distribution L u m i n a n c e
Degree cd/m2
Cone of Light
Distance to | Initial Nadir | Beam |
Lamp: | 42W PLT |
Lumens: | 3200 |
Cutoff: | 50° |
Spacing: | 1.0 |
Efficiency: | 44.8% |
Unit LPW: | 27.0 |
Angle |
|
90 | 0 |
85 | 0 |
75 | 0 |
65 | 0 |
55 | 1 |
45 | 142 |
35 | 594 |
25 | 947 |
15 | 1313 |
5 | 1397 |
0 | 1279 |
0° |
85˚0
75˚0
65˚0
55˚76
45˚ 8768
Illuminated Plane | Footcandles | Diameter |
4'6" | 63 | 4'6" |
5'6" | 42 | 5'6" |
6'6" | 30 | 6'6" |
8'0" | 20 | 8'0" |
10'0" | 13 | 10'0" |
12'0" | 9 | 12'0" |
Zonal Lumen Summary |
|
| Coefficient of Utilization |
|
|
|
|
|
|
|
| ||||||
Zone | Lumens | %Lamp | %Luminaire | Ceiling Reflectance |
|
| 80% |
|
| 70% |
| 50% |
| 30% | 0% | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
933 | 29.2 | 65.1 |
| Wall Reflectance | 70 | 50 | 30 | 10 | 50 | 10 | 50 | 10 | 50 | 10 | 0 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1299 | 40.6 | 90.6 |
| Room Cavity Ratio |
|
|
|
|
|
|
|
|
|
|
| ||
1433 | 44.8 | 100.0 |
| 0 |
| 53 | 53 | 53 | 53 | 52 | 52 | 50 | 50 | 48 | 48 | 45 | |
1433 | 44.8 | 100.0 |
| 1 |
| 50 | 48 | 47 | 45 | 47 | 44 | 45 | 43 | 43 | 42 | 40 | |
0 | 0.0 | 0.0 |
| 2 |
| 47 | 45 | 43 | 41 | 44 | 40 | 42 | 39 | 41 | 39 | 37 | |
1433 | 44.8 | 100.0 |
| 3 |
| 45 | 42 | 39 | 37 | 41 | 37 | 40 | 36 | 39 | 36 | 35 | |
|
|
|
|
| 4 |
| 43 | 39 | 36 | 34 | 38 | 34 | 37 | 34 | 37 | 33 | 32 |
|
|
|
|
| 5 |
| 40 | 36 | 34 | 32 | 36 | 31 | 35 | 31 | 34 | 31 | 30] |
|
|
|
|
| 6 |
| 38 | 34 | 31 | 29 | 34 | 29 | 33 | 29 | 32 | 29 | 28 |
|
|
|
|
| 7 |
| 36 | 32 | 29 | 27 | 32 | 27 | 31 | 27 | 31 | 27 | 26 |
|
|
|
|
| 8 |
| 34 | 30 | 27 | 25 | 30 | 25 | 29 | 25 | 29 | 25 | 24 |
|
|
|
|
| 9 |
| 33 | 28 | 25 | 24 | 28 | 23 | 27 | 23 | 27 | 23 | 23 |
|
|
|
|
| 10 | 31 | 26 | 24 | 22 | 26 | 22 | 26 | 22 | 26 | 22 | 21 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Test No. H35094
Lamp: | 32W PLT |
Lumens: | 2400 |
Cutoff: | 50° |
Spacing: | 0.9 |
Efficiency: | 43.4% |
Unit LPW: | 28.9 |
Candelas
Vertical | CD |
Angle |
|
90 | 0 |
85 | 0 |
75 | 0 |
65 | 0 |
55 | 1 |
45 | 75 |
35 | 371 |
25 | 701 |
15 | 1083 |
5 | 1159 |
0 | 1083 |
Distribution |
0° |
Luminance
Degree cd/m2
85˚0
75˚0
65˚0
55˚76
45˚ 4631
Cone of Light
Distance to | Initial Nadir | Beam |
Illuminated Plane | Footcandles | Diameter |
4'6" | 54 | 4'0" |
5'6" | 36 | 5'0" |
6'6" | 26 | 6'0" |
8'0" | 17 | 7'6" |
10'0" | 11 | 9'0" |
12'0" | 8 | 11'0" |
Zonal Lumen Summary |
|
| Coefficient of Utilization |
|
|
|
|
|
|
|
| ||||||
Zone | Lumens | %Lamp | %Luminaire | Ceiling Reflectance |
|
| 80% |
|
| 70% |
| 50% |
| 30% | 0% | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
733 | 30.5 | 70.4 |
| Wall Reflectance | 70 | 50 | 30 | 10 | 50 | 10 | 50 | 10 | 50 | 10 | 0 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
964 | 40.2 | 92.6 |
| Room Cavity Ratio |
|
|
|
|
|
|
|
|
|
|
| ||
1041 | 43.4 | 100.0 |
| 0 |
| 52 | 52 | 52 | 52 | 50 | 50 | 48 | 48 | 46 | 46 | 43 | |
1041 | 43.4 | 100.0 |
| 1 |
| 48 | 46 | 45 | 43 | 45 | 43 | 44 | 41 | 42 | 40 | 38 | |
0 | 0.0 | 0.0 |
| 2 |
| 46 | 43 | 41 | 39 | 42 | 39 | 41 | 38 | 40 | 37 | 36 | |
1041 | 43.4 | 100.0 |
| 3 |
| 44 | 40 | 38 | 36 | 40 | 36 | 39 | 35 | 38 | 35 | 33 | |
|
|
|
|
| 4 |
| 41 | 38 | 35 | 33 | 37 | 33 | 36 | 33 | 36 | 32 | 31 |
|
|
|
|
| 5 |
| 39 | 35 | 33 | 31 | 35 | 31 | 34 | 30 | 34 | 30 | 29 |
|
|
|
|
| 6 |
| 37 | 33 | 31 | 29 | 33 | 29 | 32 | 28 | 32 | 28 | 27 |
|
|
|
|
| 7 |
| 35 | 31 | 29 | 27 | 31 | 27 | 30 | 26 | 30 | 26 | 26 |
|
|
|
|
| 8 |
| 34 | 29 | 27 | 25 | 29 | 25 | 29 | 25 | 28 | 25 | 24 |
|
|
|
|
| 9 |
| 32 | 28 | 25 | 23 | 27 | 23 | 27 | 23 | 27 | 23 | 22 |
|
|
|
|
| 10 | 30 | 26 | 24 | 22 | 26 | 22 | 26 | 22 | 25 | 22 | 21 | |
Notes and Formulas: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Luminance: To convert cd/m2 to footlamberts, multiply by 0.2919
Cone of Light:
•Beam diameter is to 50% of maximum footcandles, rounded to the nearest
•Footcandle values are initial. Apply appropriate light loss factors where necessary. See page
CU Notes/Formulas:
•maintained illuminance=lamp lumens x CU x light loss factors room area
•total number of luminaires=total room area x maintained illuminance lamp lumens x CU x light loss factors
•CU data based on 20% effective floor cavity reflectance.
Note: Specifications and Dimensions subject to change without notice.
Visit our web site at www.cooperlighting.com
Customer First Center 1121 Highway 74 South Peachtree City, GA 30269 770.486.4800 FAX 770 486.4801 ADI030703 Cooper Lighting 5925 McLaughlin Rd. Mississauga, Ontario, Canada L5R 1B8 905.507.4000 FAX 905.568.7049