91961OPR
INSTALLATION

LOCATION

Install the Chiller indoors in a well ventilated area where ambient temperatures will never fall below 40F or rise
above 110F. To obtain optimum cooling capacity, the ambient temperature should be 80F or below.
Standard CH Chiller have air-cooled condensers. On air-cooled units it is important that the air intake and dis-
charge are not obstructed. Avoid hot air discharge from other equipment or enclosed areas where heat build-up
could cause a significant rise in ambient temperatures. A minimum of two feet of space on all four sides of the
Chiller will be sufficient to prevent obstruction. Water-cooled units should be located near a water source and
drain.
CONTROL PANEL
(SEE DETAIL)
TANK LEVEL GAUGE
CH 5000 AND 7500
ON REAR FOR
CH1500, 2000 AND 3000
AIR OUTLET
(AIR INLET ON
OPPOSITE END) WATER OUTLET
3/4–INCH OR 1–INCH
FPT S.S.
WATER INLET
3/4–INCH OR 1–INCH
FPT S.S.
ELECTRICAL JUNCTION BOX
TANK FILL, 1–INCH FPT
CH1500, 2000, 3000
TANK FILL 1–INCH FPT
S.S. (CH5000, 7500)
FIGURE 1. INSTALLATION DETAILS
TANK DRAIN