Crestron DIN-8SW8 DIN Rail High-Voltage Switch
Hardware Hookup
Make the necessary connections as called out in the illustration that
follows this paragraph. Refer to “Network Wiring” on page 10 before
attaching the 4-position terminal block connector. Apply power after all
connections have been made.
WARNING: Prior to connecting the device, turn off power at the circuit
breaker. Failure to do so may result in serious personal injury or damage
to the device. Restore power after all connections have been made.
CAUTION: Connecting this device to the wrong type of load or
short-circuiting the load can cause severe product damage. Each load
should be tested to identify a short circuit condition prior to wiring the
load to the module.
NOTE: Install in accordance with all local and national electric codes.
NOTE: High-voltage connections accept 2.5 mm2 (12 AWG) wire. Wire
should be stripped to 8 mm (1/3 inch). Tighten terminal blocks to 0.5 Nm
(5 in-lbs).
NOTE: Use copper wire only. For high-voltage connections, use wire
rated for at least 75º C (167º F).
NOTE: Each switch leg of the DIN-8SW8 may be fed from a separate
circuit breaker.
When making network connections to the DIN-8SW8, use a Crestron
power supply.
Operations & Installation Guide – DOC. 6666A DIN Rail High-Voltage Switch: DIN-8SW8 13