50 Watt Cresnet Power Supply Crestron GLA-PWS50 Physical Description

This section provides information on the connections,

controls and indicators available on the GLA-PWS50.

GLA-PWS50 Overall Dimensions
5.55 in
(14.09 cm)
4.00 in
(10.16 cm)
5.03 in
(12.77 cm)
2.15 in
(5.45 cm) 0.12 in
(0.31 cm)
GLA-PWS50
12
3
4
Connectors, Controls & Indicators
# CONNECTORS,
CONTROLS &
INDICATORS
DESCRIPTION
1 LINE POWER (3) 6” flying leads, 18 AWG, line
power input
Hot (black), neutral (white), and
ground (green/yellow)
connections
2 OUTPUT (2) 6” flying leads, 18 AWG,
Cresnet power output
+24 VDC (red), G (black/white)
connections
Connects to “24” and “G”
connections of the Cresnet
control network, or directly to a
24 Volt DC powered Crestron
device
3 FUSE DC output fuse, T3.15AH
(5x20mm, 250V, 3.15A, time-
lag, ceramic cartridge).
4 24VDC LED (1) green LED, indicates 24
Volts DC output, extinguishes
when fuse is blown
Setup

Important Notes

Read before installation.

Permits: An electrical permit shall be obtained

prior to each installation.

Codes: Install in accordance with all local and

national electrical codes.

Wiring: Use 75°C copper wire only.

Not suitable for Hazardous/Classified areas.

Supplied Hardware

The hardware supplied with the GLA-PWS50 is listed in

the following table.

Supplied Hardware for the GLA-PWS50
DESCRIPTION PART NUMBER QUANTITY
Partition 2022663 1
Plastic Rivet 2005423 3
Twist-On Wire Connector 2005432 5
4 Wall Mount 50 Watt Cresnet Power Supply: GLA-PWS50 Installation Guide – DOC. 6734A