Power Switching CRESTRON GREEN LIGHT™
Feed Wiring (Section A)

Feed Wiring for MLO (left) and MCB (right) Applications

Refer to the following table for information on wiring the feed to the panel.

Feed Wire Information

120 Volt Models 277 Volt Models

TERMINAL CONNECTOR MAX

WIRE RANGE TORQUE Max

Current CONNECTOR MAX

WIRE RANGE TORQUE Max

Current

Neutral and
Main Lugs 10-2/0 AWG (CU) or
6-2/0 AWG (AL)
6 - 300 kcmil (CU or AL)
15 lb-ft
(20.3 Nm)
21 lb-ft
(28.5 Nm)
6-350 kcmil (CU or AL)
1/0-750 kcmil (CU or AL) 275-300 lb-in
(31.1-33.9 Nm)
Neutral Bus 14-10 AWG(CU) or
12-10 AWG (AL)
8 AWG (CU or AL)
6-4 AWG (CU or AL)
20 lb-in
(2.3 Nm)
25 lb-in
(2.8 Nm)
35 lb-in
(4.0 Nm)
225
Amps 14-6 AWG (CU or AL)
14-2/0 AWG (CU or AL)
24-35 lb-in
(2.7-4.0 Nm)
40-50 lb-in
(4.5-5.6 Nm)
250
Amps
Use copper or aluminum conductors only – rated 75°C.
WARNING: Failure to properly tighten lugs may result in poor electrical connection and overheating of the terminals.

6 CRESTRON GREEN LIGHT Power Switching Installation Guide – DOC. 6672B