Crestron WPR-48 Waterproof Wireless Handheld Remote

Select Firmware File
6. If the transfer is successful, the Viewport screen displays a message similar
to CNWPR [v0.3]. If the transfer is unsuccessful, the screen will again
display the bootloader message CNWPR Bootloader (v8.3).
Problem Solving

Troubleshooting

The following table provides corrective action for possible trouble situations. If
further assistance is required, please contact a Crestron customer service
representative.
WPR-48 Troubleshooting
TROUBLE PROBABLE
CAUSE(S)
CORRECTIVE ACTION
LEDs do not
illuminate.
Battery is discharged. Place unit in docking station to
recharge battery.
Battery charge is low. Place unit in docking station to
recharge battery.
Intermittent
response
during RF
transmission. RF gateway is near
large metal structure.
Verify that large amount of metal is
not blocking transmission.
Net ID of gateway is
incorrectly set.
Verify that the Net ID for the gateway
and the Net ID set in the SIMPL
program match.
RF ID is incorrectly set. Verify that the RF ID for the gateway
and the RF ID set in the SIMPL
program match.
Program does not
match hardware.
Verify correct program is loaded in
system.
Gateway is unplugged
(no power).
Verify power to the gateway.
Wrong WPR-48 in use. If multiple transmitters are accessible,
verify proper unit is used.
No response
from Cresnet
system.
WPR-48 not properly
configured.
Run Viewport and verify WPR-48
attributes.
Operations Guide – DOC. 6254A Waterproof Wireless Handheld Remote: WPR-48 21