Sequence of Operation - Steam Boiler
1)When the boiler is energized, 24 volts is immediately applied to terminals “1” (blue) and “4” (yellow) on the vent damp- er. Assuming that there is no call for heat, and that the damper switch is in the “automatic” position, the damper will close. On boilers equipped with Hydrolevel CG400A probe type low water
2)Assuming that water is above the
3)Assuming that steam pressure is below the pressure limit setting, power will appear on one side of relay contact 1R1 (Gray lead). Relay 1R is the R8225 mounted under the junction box.
4)A call for heat from the thermostat energizes relay coil 1R causing contacts 1R1 to make. Current then flows through con- tacts 1R1 to pin terminal “2” (orange) at the vent damper (if used) and the damper opens.
5)Once the vent damper is fully open, an end switch inside the damper will make, energizing pin “3” (red) at the damper.
If a vent damper is not present, current flows through the red jumper indicated by Note 2 in Figure A directly to the blocked vent switch.
6)Current passes from terminal “3” on the vent damper through the blocked vent switch. Under normal conditions, this switch is made and voltage will therefore immediately appear across terminals “24V” and “24V (GND)” on the ignition module.
7)Upon application of voltage across the “24V” and “24V (GND)” terminals, the ignition module will start an ignition spark at the pilot and apply 24 volts across the pilot valve (terminals “PV” and “MV/PV”).
8)Once the pilot is established, the pilot flame will act as a diode, converting the AC current at the electrode to a half wave DC current at the pilot’s ground strap. This DC current flows through the boiler to the “GND (BURNER)” connection on the ignition module. For the ignition module to recognize that a pilot flame is present, the DC current flowing into this ter- minal must be in excess of approximately 1.0 uA.
9)Once the ignition module detects the presence of a pilot flame, voltage is applied across the main valve (terminals “MV” and “MV/PV”), opening the valve and establishing main flame.
10)The way in which the ignition module handles failure to establish pilot or the loss of an already established pilot depends upon the exact ignition module supplied with the boiler. For more information on module operation, consult the ignition module instructions supplied with the boiler or the local Crown representative.
Safety Control Operation - Steam Boilers
Hydrolevel CG400A Low Water
The CG400 is also equipped with a feature which will shut down the burners after they have been firing for 20 minutes, regardless of the water level status. The CG400 then keeps the burners off for 90 seconds, allowing the water level and any foam which is present to settle. During this 90 second interval, the green LED on the CG400 will glow. If the water level is still above the
The vent damper will close when the low water
Pressure Limit Control - Interrupts burner operation when the pressure in the boiler exceeds the
Blocked Vent Switch - Automatically interrupts burner operation in the event of a blocked vent condition. This switch is
5