BATTERY REPLACEMENT AND STORAGE
CAUTION! Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery.
Service the battery under the supervision of personnel knowledgeable of batteries and their precautions. Keep unauthorized personnel away from batteries. If you have questions, contact your dealer or call the number in this manual for information on battery replacement.
CAUTION! Use only the specified type of battery. See your dealer for replacement batteries. CAUTION! The battery may present the risk of electrical shock. Do not dispose of batteries in a fire, as it may explode. Follow all local ordinances regarding proper disposal of batteries. CAUTION! Do not open or mutilate the batteries. Release electrolyte is harmful to the skin and eyes and may be toxic.
CAUTION! A battery can present a high risk of short circuit current and electrical shock. Take the following precautions before replacing the battery:
1.Remove all watches, rings or other metal objects.
2.Only use tools with insulated handles.
3.DO NOT lay tools or other metal parts on top of battery or any battery terminals.
4.Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of ground. CONTACT WITH A GROUNDED BATTERY CAN RESULT IN ELECTRICAL SHOCK! The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance (applicable to a UPS and a remote battery supply not having a grounded circuit).
5.Batteries are consider HAZARDOUS WASTE and must be disposed of properly. Contact your local government for more information about proper disposal and recycling of batteries.
6.Turn off and unplug all connected equipment.
7.Turn the UPS off and unplug it from the AC power source.
BATTERY REPLACEMENT PROCEDURE:
1. Remove the right side front panel.
2. Remove the two retaining screws of the cable protection cover then remove the cover.
3. Disconnect the black and red cable.
4. Remove the four retaining screws.
5. Pull the battery pack out from the unit.
6. Slide a new battery pack into the unit. Assemble the screws, cover, cable and front panel in the reverse sequence of above steps.
REMINDER: Recharge the unit for 4 – 8 hours to ensure the UPS performs expected runtime.
STORAGE
First turn off your UPS and disconnect its power cord from the wall outlet. Disconnect all cables connected to the UPS to avoid battery drain. To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months to insure battery life. If the battery remains uncharged for an extended period of time, it may suffer permanent loss of
TROUBLE SHOOTING
| Problem |
| Possible Cause |
| Solution |
|
| The UPS does not |
| Batteries are not fully charged. |
| Recharge the battery by leaving the UPS plugged |
|
|
|
| in. |
| ||
| perform expected |
|
|
|
| |
|
|
|
| Contact Cyber Power Systems at |
| |
| runtime. |
| Battery is slightly worn out. |
|
| |
|
|
|
| |||
|
|
|
|
|
| |
|
|
| The on/off switch is designed to |
| Turn the UPS off. Wait 10 seconds and then turn |
|
|
|
| prevent damage by rapidly |
|
| |
|
|
|
| the UPS on. |
| |
|
|
| turning it off and on. |
|
| |
|
|
|
|
|
| |
| The UPS will not |
| The unit is not connected to an |
| The unit must be connected to a |
|
| turn on. |
| AC outlet. |
| 50/60Hz outlet. |
|
|
|
| The battery is worn out. |
| Contact Cyber Power Systems at |
|
|
|
|
|
| ||
|
|
|
|
|
| |
|
|
| Mechanical problem. |
| Contact Cyber Power Systems at |
|
|
|
|
|
| ||
|
|
|
|
|
| |
|
|
| Circuit breaker is tripped due to |
| Turn the UPS off and unplug at least one piece of |
|
|
|
|
| equipment. Wait 10 seconds, reset the circuit |
| |
| Outlets do not |
| overload. |
|
| |
|
|
| breaker and then turn the UPS on. |
| ||
|
|
|
|
| ||
| provide power to |
|
|
|
|
|
|
| Batteries are discharged |
| Allow the unit to recharge for at least 4 hours. |
| |
| equipment |
|
|
| ||
|
|
|
|
|
| |
|
|
| Unit has been damaged by a |
| Contact Cyber Power Systems at |
|
|
|
| surge or spike. |
|
| |
|
|
| The serial/USB cable is not |
| Connect the serial/USB cable to the UPS unit and |
|
|
|
|
| an open serial port on the back of the computer. |
| |
|
|
| connected. |
|
| |
|
|
|
| You must use the cable that came with the unit. |
| |
|
|
|
|
|
| |
| PowerPanel |
| The serial/USB cable is |
| Try another serial/USB port of your computer. |
|
| Business Edition |
| connected to the wrong port. |
|
| |
|
|
|
|
| ||
| or PowerPanel is |
| The unit is not providing battery |
| Shut down your computer and turn the UPS off. |
|
| inactive (all icons |
|
| Wait 10 seconds and turn the UPS back on. This |
| |
| are gray). |
| power. |
| should reset the unit. |
|
|
|
| The serial cable is not the cable |
| You must use the cable included with the unit for |
|
|
|
| that was provided with the unit. |
| the software. |
|
TECHNICAL SPECIFICATIONS
| Model | PR1500E |
| PR2200E |
Capacity | (VA) | 1500VA |
| 2200VA |
Capacity | (Watts) | 1000W |
| 1600W |
Input |
|
|
|
|
Input Voltage Range |
| |||
Frequency Range | 50/60 Hz |
| ||
Output |
|
|
|
|
On Battery Output Voltage | Pure Sine Wave at 230Vac +/- 7% | |||
On Battery Output Frequency | 50/60 Hz |
| ||
Overload Protection | On Utility: Circuit Breaker, On Battery: internal current limiting | |||
Surge Protection and Filtering |
|
|
| |
Lightning / Surge Protection | Yes |
| ||
Network Protection | RJ45 (One In/One Out) |
| ||
Physical |
|
|
|
|
Total # of UPS Receptacles | 6 |
|
| |
Maximum Dimensions | 43.3cm*8.8cm*38.8cm |
| ||
Weight (Kg) | 26.4 |
| 32.1 | |
Battery |
|
|
|
|
Sealed Maintenance Free Lead Acid | 12V / 7AHx4 |
| 12V / 9AHx4 | |
Battery |
|
| ||
|
|
|
| |
User Replaceable | Yes, Hot Swappable Battery Pack | |||
Typical Recharge Time | 8 Hours |
| ||
Warning Diagnostics |
|
|
| |
Indicators |
| Power On, Using Battery, AVR, Load Level, Battery Level | ||
Audible Alarms | On Battery, Low Battery, Overload, | |||
Environmental |
|
|
| |
Operating Temperature | +32°F to 95°F ( 0°C to 35°C ) | |||
Operating Relative Humidity | 0 to 95% | |||
Communication |
|
|
| |
PowerPanel Business edition | Windows 98/ME/2000/NT/XP, Server 2003 | |||
Software |
| |||
|
|
|
| |
Management |
|
|
| |
Yes |
| |||
Yes |
| |||
USB |
| Yes |
| |
SNMP/HTTP network function | Optional |
|
DEFINITIONS FOR ILLUMINATED LED INDICATORS
|
|
| Using | Circuit |
| Condition | |
Power | AVR | Alarm | |||||
| On | Battery Breaker |
| ||||
| On | Off | Off | Set | Off | Normal | |
| On | Slow | Off | Set | Off | AVR- Max. boost 13% of input voltage for output | |
| regulation while input voltage is from 8% to 15% under | ||||||
| flash | ||||||
|
|
|
|
| nominal. | ||
|
|
|
|
|
| ||
| On | Rapid | Off | Set | Off | AVR- Max. boost 26% of input voltage for output | |
| regulation while input voltage is from 15% to 26% under | ||||||
| flash | ||||||
|
|
|
|
| nominal. | ||
|
|
|
|
|
| ||
| ON | On | Off | Set | Off | AVR- Max. buck 11% of input voltage for output regulation | |
| while input voltage is from 8% to 26% over nominal. | ||||||
|
|
|
|
|
| ||
| Off | Off | On | Set | Two | Utility Failure- The UPS is providing battery power to the | |
| Beeps | outlets. | |||||
|
|
|
|
| |||
| Off | Off | On | Set | Rapid | Utility Failure- The UPS is providing battery power. | |
| Rapid beeps indicate the battery will run out of charge | ||||||
| Beeps | ||||||
|
|
|
|
| within a few minutes. | ||
|
|
|
|
|
| ||
On/Off | On/ Off | On/Off | Set | Long | Overload- Please turn the UPS off and unplug at least one | ||
piece of equipment from the UPS. Wait 5 seconds, reset | |||||||
/Flash | Beep |
capacity.
Input
AVR Switch
Battery
Charger
Block Diagram
Transformer Output
Battery |
| Inverter |
| (DC/AC) | |
|
| |
|
|
|
|
|
|
|
| the circuit breaker and restart the UPS. | |
Off | Off | On | Up | Long | Overload- Please turn the UPS off and unplug at least one | |
piece of equipment from the UPS. Wait 5 seconds, reset | ||||||
Beep | ||||||
|
|
|
| the circuit breaker and restart the UPS. | ||
|
|
|
|
| ||
Off | Off | Off | Set | Off | Surge Protection Malfunction- Power surge has | |
damaged the unit. Please contact CyberPower Systems. | ||||||
|
|
|
|
|
For more information, visit eu.cyberpowersystems.com or contact
CyberPower Systems B.V. Flight Forum 3545,5657DW Eindhoven,The Netherlands Tel: + 31(0)40 2348170, Fax : + 31(0)40 2340314,
Tel: +1 952 4039500, Fax: +1 952 4030009,
Entire contents copyright ©2004 CyberPower Systems B.V., All rights reserved. Reproduction in whole or in part without permission is prohibited.
PowerPanel and PowerPanel Plus are trademarks of CyberPower Systems (USA) Inc.
CyberPower warrants to you, the original purchaser, that CyberPower UPS will be free from defects in design, assembly, materials and workmanship for two years ( battery is only one year) from the date of original purchase. Any warranty services, please contact your local dealers or distributors.