LX1325G / LX1500G

User’s Manual

K01-0000294-01

IMPORTANT SAFETY WARNINGS

(SAVE THESE INSTRUCTIONS)

This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate your UPS.

CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of conductive contaminants. (Please see specifications for acceptable temperature and humidity range).

CAUTION! To reduce the risk of electric shock, do not remove the cover except to service the battery. Turn off and unplug the unit before servicing the batteries. There are no user serviceable parts inside except for the battery.

CAUTION! Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected.

CAUTION! The UPS must be connected to an AC power outlet with fuse or circuit breaker protection. Do not plug into an outlet that is not grounded. If you need to de-energize this equipment, turn off and unplug the unit.

CAUTION! To avoid electric shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a computer

component.

CAUTION! Not for use in a computer room as defined in the Standard for the Protection of Electronic Computer/Data Processing Equipment, ANSI/NFPA 75.

CAUTION! To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit over current protection in accordance with the National Electric Code, ANSI/NFPA 70.

DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPower Systems does not sell products for life support or medical applications. DO NOT use in any circumstance that would affect the operation and safety of life support equipment, medical applications, or

patient care.

DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire or electric shock, do not use with or near an aquarium. Condensation from the aquarium can cause the unit to short out.

DO NOT USE THE UPS ON ANY TRANSPORTATION! To reduce the risk of fire or electric shock, do not use the unit on any transportation such as airplanes or ships. The effect of shock or vibration caused during transit and the damp environment can cause the unit to short out.

INSTALLING YOUR UPS SYSTEM

UNPACKING

Inspect the UPS upon receipt. The box should contain the following:

(a) UPS unit (b) User’s manual (c) USB A+B type cable

*PowerPanel® Personal Edition software is available on our website. Please visit www.cpsww.com and go to the Software Section for free download.

OVERVIEW

The LX1325G/LX1500G provides complete power protection from utility power that is not always consistent. The LX1325G/LX1500G features 1500 Joules of surge protection. Both units provide long lasting battery backup during power outages with maintenance free batteries. The LX1325G/LX1500G ensures consistent power to your electronic equipment and includes software that will automatically save your open files and shutdown your electronic equipment during a utility power loss.

AUTOMATIC VOLTAGE REGULATOR

The LX1325G/LX1500G stabilizes inconsistent utility power voltage to nominal levels that are safe for equipment. Inconsistent incoming utility power may be damaging to important data files and hardware, but with Automatic Voltage Regulation (AVR), damaging voltage levels are corrected to safe levels. AVR automatically increases low utility power and decreases high utility power to a consistent and safe 110/120 volts.

HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT

1.Ensure that the equipment plugged into the UPS does not exceed the UPS unit’s rated capacity (1325VA/810W for LX1325G; 1500VA/900W for LX1500G). If the rated capacities of the unit are exceeded, an overload condition may occur and cause the UPS unit to shut down or the circuit breaker to trip.

2.There are many factors that can affect the amount of power that your electronic equipment will require. It is suggested that the load placed on the battery outlets not exceed 80% of the unit’s capacity.

HARDWARE INSTALLATION GUIDE

1.Your new UPS may be used immediately upon receipt. However, after receiving a new UPS, to ensure the battery’s maximum charge capacity, it is recommended that you charge the battery for at least 8 hours. Your UPS is equipped with an auto-charge feature. When the UPS is plugged into an AC outlet, the battery will automatically charge whether the UPS is turned on or off.

2.With the UPS unit turned off and unplugged, connect your computer, monitor, and any other peripherals requiring battery backup into the battery power supplied outlets. DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum cleaner, sump pump or other large electrical devices into the “Battery and Surge Protected Outlets”. The power demands of these devices may overload and damage the unit.

3.To protect a fax, phone or modem line, connect a telephone cable or network cable from the wall jack outlet to the IN jack of the UPS. Connect a telephone cable or network cable from the OUT jack of the UPS to a fax machine, telephone, modem, or network devices.

4.Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air conditioner, copier, etc…). The warranty prohibits the use of extension cords, outlet strips, and surge strips in conjunction with the UPS unit.

5.Press the power switch to turn the unit on. The Power On indicator light will illuminate and the unit will “beep”.

6.If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug at least one piece of equipment from the battery power supplied outlets. Make sure the circuit breaker is depressed and then turn the UPS on.

7.To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.

8.To store the UPS for an extended period of time, cover it and store with the battery fully charged. While in storage, recharge the battery every three months to ensure battery life.

9.Ensure the wall outlet and UPS are located near the equipment being attached for proper accessibility.

BASIC OPERATION

DESCRIPTION

1Power Switch

Used as the master ON/OFF switch for equipment connected to the battery power supplied outlets.

2Power On Indicator

This LED is illuminated when the utility power is normal and the UPS outlets are providing power, free of surges and spikes.

3LCD module display

High resolution and intelligent LCD display shows all the UPS information using icons and messages. For more information please review

the “Definitions for Illuminated LCD Indicators” section below.

4LCD Display Toggle/Selected Switch

The switch can be used to select the LCD display contents including Input Voltage, Output Voltage, and Estimated Run Time.

The toggle frequency is set to one time per second. Holding the switch for more than two seconds while running on battery will silence the

buzzer.

5Battery and Surge Protected Outlets

The unit has four battery powered/surge suppression outlets for connected equipment to ensure temporary uninterrupted operation of your equipment during a power failure. (DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum cleaner, sump pump

or other large electrical devices into the “Battery and Surge Protected Outlets”. The power demands of these devices may overload and damage the unit.)

6Full-Time Surge Protection Outlets

The unit has four surge suppression outlets.

7Wiring Fault Indicator

This LED indicator will illuminate to warn the user that a wiring problem exists, such as bad ground, missing ground or reversed wiring. If this is illuminated, disconnect all electrical equipment from the outlet and have an electrician verify the outlet is properly wired. The unit will

not provide surge protection without being plugged into a grounded and properly wired wall outlet.

8Communication Protection Ports

Communication protection ports will protect any standard modem, fax, telephone line, network or Ethernet connection (RJ11/RJ45).

9Circuit Breaker

Located on the back of the UPS, the circuit breaker serves to provide overload and fault protection.

10Serial/USB Ports to PC

The ports allow connection and communication between the USB/DB-9 port on the computer and the UPS unit. Note: Only one of these two ports can be used to communicate with your computer at one time.

11Coax/Cable/DSS Surge Protection

The Coax/Cable/DSS protection ports will protect any cable modem, CATV converter, or DSS receiver.

12Outlet Designed for AC Adapters

The unit has one outlet spaced to allow AC power adapter blocks to be plugged into the UPS without overlapping or blocking adjacent outlets.

REPLACING THE BATTERY

CAUTION! Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery. Service the battery under the supervision of personnel knowledgeable of batteries and their precautions.

CAUTION! Use only the specified type of battery. See your dealer for replacement batteries.

CAUTION! The battery may present a risk of electrical shock. Do not dispose of battery in a fire as it may explode. Follow all local ordinances regarding proper disposal of batteries. Almost any retailer that sells lead-acid batteries collects used batteries for recycling, as required by most state laws.

CAUTION! Do not open or mutilate the batteries. Released electrolyte is harmful to skin and eyes and may be toxic.

CAUTION! A battery can present a high risk of short circuit current and electrical shock. Take the following precautions before replacing the

battery:

1.Remove all watches, rings or other metal objects.

2.Only use tools with insulated handles.

3.Do not lay tools or metal parts on top of battery or any terminals.

4.Wear rubber gloves and boots.

5.Determine if the battery is inadvertently grounded. If grounded, remove the source of ground. CONTACT WITH GROUNDED BATTERY

CAN RESULT IN ELECTRICAL SHOCK!

BATTERY REPLACEMENT PROCEDURE:

1.Turn off and unplug all connected equipment.

2.Turn the UPS off and unplug it from the AC power source.

3.Turn the UPS upside down.

4.Remove the retaining screw.

5.Slide the battery compartment cover (front panel) completely off of the unit.

6.Remove the batteries from the compartment.

7.Disconnect the battery wires from the batteries.

8.Install the replacement batteries by connecting the red wire (+) and black wire (-) to the same color connectors from the battery pack.

9.Put the batteries back into the compartment.

10.Slide back the battery compartment cover and tighten the retaining screws.

11.Recharge the UPS for 8-16 hours to fully charge the battery.

REMINDER: Batteries are considered HAZARDOUS WASTE and must be disposed of properly. Most retailers that sell lead-acid batteries collect used batteries for recycling, as required by local regulations.

DEFINITIONS FOR ILLUMINATED LED INDICATORS

 

 

 

CONDITION

Power ON

Wiring Fault

Alarm

 

 

 

 

 

On

Off

Off

Normal

 

 

 

 

On

Off

Beep twice

Utility Failure- The UPS is providing power to battery power-supplied

every 30 seconds

 

 

 

outlets from its battery.

 

 

 

 

On

Off

Rapid Beeping

Utility Failure- The UPS is providing battery power. Rapid beeping

every 1/2 second

indicates the unit will run out of power shortly.

 

 

 

 

 

 

 

 

 

Battery Overload - Occurs when connected equipment exceeds the

Off

Off

Constant tone

listed capacity of the UPS. Turn the UPS off, unplug at least one

piece of equipment from battery outlets, wait 10 seconds, reset the

 

 

 

 

 

 

circuit breaker and turn the unit on.

 

 

 

 

 

 

 

Electrical Wiring Fault - This indicates a wiring problem with the

On/Off

On

None

AC outlet such as bad ground, missing ground, or reversed wiring.

Disconnect all electrical equipment from the outlet and have an

 

 

 

 

 

 

electrician check the outlet to insure proper wiring.

 

 

 

 

DEFINITIONS FOR ILLUMINATED LCD INDICATORS

1.INPUT voltage meter:

This meter measures the AC voltage that the UPS system is receiving from the utility wall outlet. The UPS is designed to continuously supply connected equipment with stable output voltage In the event of a complete power loss, severe brownout, or over-voltage, the UPS relies on its internal battery to supply consistent 110/120 output voltage. The INPUT voltage meter can be used as a diagnostic tool to identify poor-quality input power.

2.OUTPUT voltage meter:

This meter measures, in real time, the AC voltage that the UPS system is providing to the computer, such as normal line mode, AVR mode, and battery backup mode. (Note: The OUTPUT voltage meter shows the status of the battery backup outlets.)

3.ESTIMATED RUN TIME:

This displays the run time estimate of the UPS with current battery capacity and load.

4.NORMAL icon:

This icon appears when the UPS is working under normal conditions.

5.BATTERY icon:

During a severe brownout or blackout, this icon appears and an alarm sounds (two short beeps followed by a pause) to indicate the UPS is

Page 1
Image 1
CyberPower Systems K01-0000294-01 user manual Important Safety Warnings, Installing Your UPS System, Basic Operation

K01-0000294-01 specifications

The CyberPower Systems K01-0000294-01 is a versatile and reliable power management solution designed for both home and commercial use. This uninterruptible power supply (UPS) provides essential protection against power interruptions, surges, and outages, ensuring that your critical devices remain operational. One of the standout features of the K01-0000294-01 is its high-capacity battery, which delivers ample runtime during outages, allowing users to save their work and safely shut down equipment.

The UPS is equipped with advanced Line Interactive technology, which not only offers superior voltage regulation but also ensures a smooth and consistent power supply. This technology allows the K01-0000294-01 to adjust voltage levels automatically, maintaining optimal power quality. The unit also includes a wide input voltage range, which helps protect connected devices from fluctuations and spikes in the electrical supply.

Another key characteristic of this UPS is its robust outlet configuration. The K01-0000294-01 features several outlets, providing users with the flexibility to connect multiple devices simultaneously. Some of these outlets are specifically designed for battery backup, while others offer surge protection, making it suitable for computers, networking equipment, and even gaming consoles.

In addition to its power management capabilities, the CyberPower K01-0000294-01 incorporates smart management features. The built-in LCD display provides real-time status updates, giving users critical information at a glance, such as remaining battery life and estimated runtime. Furthermore, the UPS can be integrated with proprietary monitoring software, allowing for advanced control and management of power resources.

The design of the K01-0000294-01 is both compact and aesthetic, enabling it to fit into a variety of environments without taking up excessive space. Its energy-efficient operation helps reduce electricity costs while adhering to strict environmental standards.

Overall, the CyberPower Systems K01-0000294-01 stands out in the UPS market due to its combination of reliability, advanced features, and user-friendly design, making it a solid choice for anyone seeking to protect their electronic devices from potential power issues. Whether used in a home office or a larger corporate setting, this UPS delivers the performance and peace of mind that users require.