BATTERY REPLACEMENT PROCEDURE:

1. Remove the 2 retaining screws then push the battery cover backward and remove the cover.

2. Lean the UPS to one side and pull out the battery partially from the compartment. Disconnect the battery wires from the battery, and then remove the battery from the compartment.

3. Install the replacement battery by connecting the red wire to the positive (+) terminal of the battery and connecting the black wire to the negative (-) terminal of the battery.

4. Slide the battery back into the compartment. Turn the UPS upside down to help the batteries entirely slide into the compartment. Replace the cover and the retaining screws.

REMINDER: Recharge the unit for 4 – 8 hours to ensure the UPS performs expected runtime

STORAGE

First turn off your UPS and disconnect its power cord from the wall outlet. Disconnect all cables connected the UPS to avoid battery drain. To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months to insure battery life. If the battery remains uncharged for an extended period of time, it may suffer permanent loss of capacity.

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS

 

Model

UP425UIT

 

UP550UI

 

UP750UI

 

Capacity (VA)

425VA

 

550VA

 

750VA

 

Capacity (Watts)

255W

 

330W

 

450W

 

Input

 

 

 

 

 

 

Input Voltage Range

160Vac - 278Vac (User Configuration)

 

Frequency Range

 

 

50 / 60 Hz

 

 

Output

 

 

 

 

 

 

On Battery Output Voltage

Simulated Sine Wave at 230Vac +/- 5%

 

On Battery Output Frequency

 

 

50/60 Hz +/- 1%

 

 

Overload Protection

On Utility: Fuse, On Battery: Internal Current Limiting

 

Surge Protection and Filtering

 

 

 

 

 

 

Lightning / Surge Protection

 

 

Yes

 

 

Network Protection

RJ11/RJ45 (One In/One Out)

 

Physical

 

 

 

 

 

 

Total # of UPS Receptacles

2 (UPS) + 1 (Surge)

 

3 (UPS) + 1 (Surge)

 

Maximum Dimensions (cm)

23.8 x 8.0 x 13.7

 

28.3 x 9.1 x 16.4

 

Weight (Kg)

5

 

6.8

 

7.5

 

Battery

 

 

 

 

 

 

Sealed Maintenance Free

12V / 4.5 AH x1

 

12V / 8 AH x1

 

12V / 9 AH x1

 

 

 

 

Lead Acid Battery

 

 

 

 

 

 

 

 

 

User Replaceable

No

 

Yes, Hot Swappable Battery Pack

 

Typical Recharge Time

 

 

8 Hours

 

 

Warning Diagnostics

 

 

 

 

 

 

Indicators

Power on, Using Battery, Overload, Replace Battery

 

Audible Alarms

On Battery, Low Battery, Overload

 

Environmental

 

 

 

 

 

 

Operating Temperature

32 F to 95 F ( 0 C to 35 C )

 

 

Operating Relative Humidity

0 to 95% Non-Condensing

 

 

Communication

 

 

 

 

 

 

PowerPanel Personal

Windows 98/ME/2000/NT/XP/Server 2003/Vista

 

Edition Software

 

 

 

 

 

 

 

Management

 

 

 

 

 

 

Self-Test

 

 

Yes

 

 

USB

 

 

Yes

 

 

Auto-Charger

 

 

Yes

 

 

Auto-Restart

 

 

Yes

 

All specifications are subject to change without notice.

 

TROUBLETROUB

SHOOTINGO TING

 

 

 

 

Problem

Possible Cause

 

Solutions

The UPS does not

Batteries are not fully

 

Recharge the battery by leaving the UPS

perform expected

charged.

 

plugged in.

runtime.

 

 

 

Battery is slightly worn out.

 

Contact CyberPower Systems at

 

 

 

 

 

service@cyberpower-eu.com.

 

 

 

 

The UPS will not

The on/off switch is

 

Turn the UPS off. Wait 10 seconds and then

turn on.

designed to prevent

 

turn the UPS on.

 

damage by rapidly turning it

 

 

 

off and on.

 

 

 

 

 

 

 

The unit is not connected to

 

The unit must be connected to a 220-240V

 

an AC outlet.

 

50/60Hz outlet.

 

The battery is worn out.

 

Contact CyberPower Systems at

 

 

 

service@cyberpower-eu.com

 

Mechanical problem.

 

Contact CyberPower Systems at

 

 

 

service@cyberpower-eu.com

Outlets do not

Fuse is blown due to

 

Turn the UPS off and unplug at least one piece

provide power to

overload.

 

of equipment. Unplug the power cord of the

equipment

 

 

UPS then remove the fuse compartment

 

 

 

beneath the power inlet of the UPS and

 

 

 

replace the blown fuse with a spare one. Lock

 

 

 

the compartment back to the UPS. Connect

 

 

 

power cord then turn the UPS on. Make sure

 

 

 

that your spare fuse meets the specification :

 

 

 

6.3A, 250V, 5x10mm.

 

 

 

 

 

Batteries are discharged.

 

Allow the unit to recharge for at least 4 hours.

 

 

 

 

 

Unit has been damaged by

 

Contact CyberPower Systems at

 

a surge or spike.

 

service@cyberpower-eu.com.

PowerPanel

The USB cable is not

 

Connect the USB cable to the UPS unit and an

Personal Edition is

connected.

 

open USB port on the back of the computer.

inactive (all icons

 

 

You must use the cable that came with the

are gray).

 

 

unit.

 

The USB cable is

 

Try another USB port of your computer.

 

connected to the wrong

 

 

 

port.

 

 

 

The unit is not providing

 

Shut down your computer and turn the UPS

 

battery power.

 

off. Wait 10 seconds and turn the UPS back

 

 

 

on. This should reset the unit.

 

The USB cable is not the

 

You must use the cable included with the unit

 

cable that was provided

 

for the software.

 

with the unit.

 

 

For more information, please contact:

CyberPower Systems ( USA ), Inc. 4241 12th Avenue East Suite 400 Shakopee, MN 55379 CyberPower Systems B. V. ( Europe ) Flight Forum 3545,5657DW Eindhoven,The Netherlands

DEFINITIONS FOR ILLUMINATED LED INDICATORS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

Using

Replace

Overload

Fuse

Alarm

Condition

On

Battery

Battery

 

 

 

 

 

 

 

 

On

 

 

Off

 

 

Off

Off

Normal

Off

Normal

Off

 

 

On

 

 

Off

Off

Normal

Two Beeps

Utility Failure- The UPS is providing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

battery power to battery-power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

supplied outlets.

Off

 

 

On

 

 

Off

Off

Normal

Rapid

Utility Failure- The UPS is providing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Beeps

battery power. Rapid beeps indicate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the unit will run out of power shortly.

On

 

 

Off

 

 

Off

On

Blown

Long Beeps

System Overload- Occurs in the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

full-time surge protection outlet. Turn

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the UPS off, unplug at least one piece

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of equipment from UPS. Replace the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fuse with the spare one then turn the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS on.

Off

 

 

On

 

 

Off

On

Normal

Long Beeps

Battery Overload- Occurs when

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connected equipment exceeds the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rating of battery outlets of the unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn the UPS off, unplug at least one

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

piece of equipment from battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

outlets. Check the fuse and do the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

replacement if necessary. Turn the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS on.

On

 

 

Off

 

 

On

Off

Normal

Beep

Replace Battery- UPS battery is no

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

longer useful and must be replaced.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Please see manual “Battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

replacement procedure”.

CyberPower warrants to you, the original purchaser, that CyberPower UPS will be free from defects in design, assembly, materials and workmanship for two years ( battery is only one year) from the date of original purchase. Any warranty services, please contact your local dealers or distributors.

Phone: (952)403-9500

Fax: (952)403-0009

www.cyberpowersystems.com

Phone: 31 (0)40 2348170

Fax: 31 (0)40 2340314

eu.cyberpowersystems.com

Entire contents copyright ©2005 CyberPower Systems B.V., All rights reserved. Reproduction in whole or in part without permission is prohibited. PowerPanel and PowerPanel Plus are trademarks of CyberPower Systems (USA) Inc.

Page 2
Image 2
CyberPower Systems UP550UI Technical Specifications, Shootingo Ting, Definitions for Illuminated LED Indicators, Storage

UP425UIT, UP550UI, UP750UI specifications

CyberPower Systems, a leading provider of power protection solutions, offers an impressive range of uninterruptible power supplies (UPS) tailor-made for both home and office environments. Among their notable models are the UP750UI, UP550UI, and UP425UIT. Each model carries unique features and technologies to ensure that electronics remain powered during outages or fluctuations.

The CyberPower UP750UI is a robust UPS designed to deliver reliable backup power and surge protection for equipment such as computers, networking devices, and gaming consoles. With a capacity of 750VA/450W, this model offers ample power to sustain multiple devices. One of its key features is the Automatic Voltage Regulation (AVR), which stabilizes voltage fluctuations and shields connected devices from damage. The UP750UI also includes an LCD display that provides real-time information about battery status, load, and estimated runtime. Additionally, it is equipped with a variety of outlets, including USB and surge-protected ports, ensuring compatibility with various devices.

Next in line is the UP550UI, which is a slightly smaller model with a capacity of 550VA/330W. Despite its lower power rating, this UPS maintains a remarkable balance of performance and efficiency. The UP550UI similarly incorporates AVR technology and an LCD display for monitoring. Its compact design makes it an excellent option for home offices or small workspaces where space is a premium. The unit is also fitted with multiple outlets, allowing users to connect essential devices without concern.

Lastly, the UP425UIT is the most compact option at 425VA/255W. This model is ideal for smaller setups, such as single PC systems, routers, or home entertainment systems. It features a simple and user-friendly design, making it accessible even for those who may not be tech-savvy. The UP425UIT provides seamless power backup and surge protection without compromising on performance. Its lightweight nature enhances portability, facilitating usage in different environments.

All three UPS models boast advanced battery management technologies to extend battery life and optimize performance. With features like the GreenPower UPS technology, these units aim to minimize energy consumption, promoting an eco-friendly operation. CyberPower UPS systems are designed with user safety in mind, offering various protections against overloads, short circuits, and thermal events. In summary, the UP750UI, UP550UI, and UP425UIT from CyberPower Systems are excellent choices for anyone seeking dependable power protection, each catering to different needs while ensuring optimal performance and longevity.