Delta DVP04TC-H2 instruction sheet Introduction, Specifications, Control Register, Functions

Models: DVP04TC-H2

1 2
Download 2 pages 53.74 Kb
Page 1
Image 1
Temperature Measurement Module

2007-01-09

http://www.delta.com.tw/industrialautomation/

5011652100-T2E0

Temperature Measurement Module

Instruction Sheet

Warning

9Please read this instruction sheet carefully before use.

9Switch off the power before wiring.

9DVP04TC-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or specific tools are required to open the enclosure) in case danger and damages on the device may occur.

9DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all the wiring again before switching on the power.

9DO NOT touch any terminal when the power is switched on.

9Make sure the ground termnial Instruction Sheet is correctly grounded in order to prevent electromagnetic interference.

9Keep the wire as short as possible between RTD and PLC and the power wire as far away as possible from I/O wire to prevent interference.

Introduction

1.1 Model Explanation & Peripherals

™Thank you for choosing Delta’s DVP series. DVP04TC-H2 is able to receive 4 points of external thermocouple temperature sensors (J-type, K-type, R-type, S-type, T-type) and convert them into 14-bit digital signals. Besides, through FROM/TO instructions in DVP-EH2 MPU program, DVP04TC-H2 is able to read and write the data in the module. There are 49 16-bit control registers (CR) in DVP04TC-H2.

™The power unit and module of DVP04TC-H2 are separate, compact in size and easy to install.

™DVP04TC-H2 displays temperatures in Celsius (resolution: 0.1°C) and Fahrenheit (resolution: 0.18°F).

™Nameplate Explanation

Delta PLC model name

MOD EL:

 

Power input specification

POWER INPUT: 24Vdc 2.5W

Analog I/O module specification

THERMOCOUPLESE: TYPE J, K, R, S, T

RESOLUTION: 14 BITS

Barcode, serial No., Version

VX.XXXX

04 TC -H2 0T6 500 001

 

MADE IN XXXXX X

™Model/Serial No. Explanation

DVP series

H: For EH series MPU

Production No.

 

Production week

Points (input + output)

H2: For EH2 series MPU

 

 

Production year (2006)

Model type

 

Production plant (Taoyuan)

AD: Analog input

 

Version No.

 

Model name

DA: Analog output

XA: Mixed analog I/O

PT: Temperature measurement (PT-100) HC: High-speed counter input

 

TC: Temperature measurement

PU: Single-axis position control

 

(thermocouple)

 

 

1.2 Product Profile (Indicators, Terminal Block, I/O Terminals)

 

24V

RS-

0V D

485

D -

 

+

CH1

SLD L + L

 

-

CH2

SLD L + L

 

-

CH3

SLD L + L

 

-

8

L

 

1.3

External Wiring

 

 

 

 

 

 

DVP04TC-H2

 

 

Description

 

 

 

 

 

 

 

Thermocouple

 

 

 

CR

RS-485

 

 

Register content

 

 

 

 

 

 

 

 

 

 

 

 

 

Shielding

 

 

#

Parameter Latched

b15 b14 b13 b12

b11 b10 b9

b8

b7

b6

b5

b4

b3

b2

b1

b0

 

 

cable *1

CH1

10 k

 

address

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

 

L+

MUX

#0

H’4096

R

Model name

Set up by the system. DVP04TC-H2 model code = H’6403

 

 

 

 

 

-

 

L -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLD

 

 

 

 

 

 

 

Reserved

CH4

 

CH3

 

 

CH2

 

 

CH1

 

 

Thermocouple Shielding

 

 

 

 

 

 

 

Take the setting of CH1 for example:

 

 

 

 

 

 

 

 

 

 

cable *1

CH4

 

#1

H’4097

○ R/W

Thermocouple type

1.

When (b2, b1, b0) is set as (0,0,0), choose J-type

 

 

 

 

 

 

+

 

L+

 

2. When (b2, b1, b0) is set as (0,0,1), choose K-type

 

 

 

 

 

 

-

 

L -

 

 

 

 

 

 

3.

When (b2, b1, b0) is set as (0,1,0), choose R-type

 

 

 

 

 

 

 

 

SLD

 

 

 

 

 

 

4.

When (b2, b1, b0) is set as (0,1,1), choose S-type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.

When (b2, b1, b0) is set as (1,0,0), choose T-type

 

 

 

 

 

*2

Cold-Junction

5V

#2 H’4098 ○ R/W CH1 average time

Compensation

 

Terminal of

 

 

 

 

AG

#3

H’4099

○ R/W

CH2 average time

Range of settings in CH1 ~ CH4: K1 ~ K20

 

 

 

 

 

#4

H’409A

○ R/W

CH3 average time

Default = K10

 

 

 

 

 

 

 

power module

 

*3 System

24+

 

+15V

#5

H’409B

○ R/W

CH4 average time

 

 

 

 

DC/ DC

 

 

 

 

grounding

0V

Converter

AG

#6

H’409C

R

Average °C temp. measured

 

 

 

 

Earth

 

 

-15V

at CH1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(100

or less)

 

 

 

#7

H’409D

R

Average °C temp. measured

 

 

 

 

 

 

 

 

at CH2

Average Celsius temperature measured at CH1 ~ CH4.

 

 

 

 

 

 

 

 

 

 

 

*1: The wiring used for analog input should adopts the connection cable or shielding cable of thermocouple temperature

#8

H’409E

R

Average °C temp. measured

Unit: 0.1°C

at CH3

 

sensor J-type or K-type and should be separated from other power cable or wirings that may cause interference. The

 

 

 

 

 

#9

H’409F

R

Average °C temp. measured

 

screw torque of the terminal should be 1.95 kg-cm (1.7 in-lbs).

 

 

at CH4

 

*2: Terminal SLD is the ground location for noise suppression.

 

 

 

#10

H’40A0

R

Average °F temp. measured

 

*3: Please connect the

terminal on both the power module and DVP04TC-H2 to the system earth point and ground the

at CH1

 

 

 

 

 

 

#11

H’40A1

 

R

Average °F temp. measured

 

system contact or connect it to the cover of power distribution cabinet.

 

 

 

 

 

at CH2

Average Fahrenheit temperature measured at CH1 ~ CH4

Note: DO NOT wire empty terminal

.

 

 

 

 

#12

H’40A2

R

Average °F temp. measured

Unit: 0.1°F

Note: Use 60/75°C copper conductor only.

 

 

 

 

at CH3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#13

 

H’40A3

 

 

R

Average °F temp. measured

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Specifications

 

 

 

 

at CH4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#14

 

H’40A4

 

 

R

Present °C temp. measured

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

at CH1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.1. Functions

 

 

 

 

 

#15

 

H’40A5

 

 

 

R

 

Present °C temp. measured

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

at CH2

Present Celsius temperature measured at CH1 ~ CH4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#16

 

H’40A6

 

 

 

 

R

 

Present °C temp. measured

Unit: 0.1°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature measurement

 

Celsius (°C)

 

Fahrenheit (°F)

 

 

 

 

 

 

at CH3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(04TC) module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#17

 

H’40A7

 

 

 

R

 

Present °C temp. measured

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply voltage

 

24 VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)

 

 

 

 

 

 

at CH4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#18

 

 

 

 

 

 

 

 

 

 

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog output channel

 

4 channels/module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#19

 

H’40A9

 

 

 

R

 

Present °F temp. measured

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Applicable sensor

 

 

 

 

 

 

 

 

 

 

at CH1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J-type, K-type, R-type, S-type, T-type thermocouple

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

types

 

 

#20

 

H’40AA

 

 

 

R

 

Present °F temp. measured

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

at CH2

Present Fahrenheit temperature measured at CH1 ~ CH4

 

 

 

 

 

 

 

 

J type: -100°C ~ 700°C

J type: -148°F ~ 1,292°F

 

#21

 

H’40AB

 

 

 

R

 

Present °F temp. measured

 

Unit: 0.1°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K type: -100°C ~ 1,000°C

K type: -148°F ~ 1,832°F

 

 

 

 

 

 

at CH3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Range of input

 

 

#22

 

H’40AC

 

 

 

R

 

Present °F temp. measured

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature

 

R type: -10°C ~ 1,700°C

R type: -14°F ~ 3,092°F

 

 

 

 

 

 

 

 

 

 

at CH4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S type: -10°C ~ 1,700°C

S type: -14°F ~ 3,092°F

 

#23

 

 

 

 

 

 

 

 

 

 

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#24

 

H’40AE

 

 

 

R/W

 

OFFSET value of CH1

 

Adjustable OFFSET settings at CH1 ~ CH4.

 

 

 

 

 

 

 

 

 

 

 

T type: -100°C ~ 350°C

T type: -148°F ~ 662°F

 

#25

 

H’40AF

 

 

 

R/W

 

OFFSET value of CH2

 

Range: -1,000 ~ +1,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#26

 

H’40B0

 

 

 

R/W

 

OFFSET value of CH3

 

Default = K0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J type: K-1,000 ~ K7,000

J type: K-1,480 ~ K12,920

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit: 0.1°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#27

 

H’40B1

 

 

 

R/W

 

OFFSET value of CH4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K type: K-1,000 ~ K10,000

K type: K-1,480 ~ K18,320

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Range of digital

 

 

#28 ~ #29

 

 

 

 

 

 

 

 

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R type: K-100 ~ K17,000

R type: K-140 ~ K30,920

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

conversion

 

 

#30

 

H’40B4

 

 

 

R

 

Error status

 

Register for storing all error status. See the table of error status for more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S type: K-100 ~ K17,000

S type: K-140 ~ K30,920

 

 

 

 

 

 

 

information.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T type: K-1,000 ~ K3,500

T type: K-1,480 ~ K6,620

#31

 

H’40B5

 

 

R/W

Communication address

For setting RS-485 communication address. Range: 01 ~ 255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setting

Default = K1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Resolution

 

14 bits (0.1)

14 bits (0.18)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For setting up communication speed:

 

 

 

 

 

 

 

 

 

 

Overall accuracy

 

±0.5% when in full scale (25°C, 77°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

4,800/9,600/19,200/38,400/57,600/115,200 bps

 

 

 

 

 

 

 

 

 

±1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F

 

 

 

 

 

 

 

 

 

 

 

 

ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1) Default: H’0002

 

 

 

 

Response time

 

200 ms × the number of channels

 

 

#32

 

H’40B6

 

 

 

R/W

 

Communication speed (baud

 

b0: 4,800 bps

 

b1: 9,600 bps (default)

 

 

 

 

 

 

 

 

 

Isolation

 

Isolation between digital area and analog area. No isolation among channels.

 

 

 

 

 

 

 

 

 

 

rate) setting

 

b2: 19,200 bps

b3: 38,400 bps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b4: 57,600 bps

b5: 115,200 bps

 

 

 

 

 

 

 

 

 

 

 

Digital data format

 

13 significant bits out of 16 bits are available; in 2’s complement

 

 

 

 

 

 

 

 

 

 

 

 

b6 ~ b13: reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b14: High/low bit exchange of CRC checksum (only valid in RTU mode)

 

 

 

Average function

 

Yes; available for setting up in CR#2 ~ CR#5; range: K1 ~ K20

 

 

 

 

 

 

 

 

 

 

 

 

b15: Switch between ASCII/RTU modes; 0 = ASCII mode (default)

 

 

 

 

Self-diagnosis

 

Upper and lower bound detection/channel

 

 

 

 

 

 

 

 

 

 

 

 

 

b15

b14

b13

 

b12

b11

b10

b9

b8

b7

b6

b5

b4

b3

b2

b1

b0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ERR

LED

 

 

 

 

CH4

 

 

CH3

 

 

CH2

 

 

CH1

 

 

 

 

 

The voltage output is protected by short circuit. Please also be aware that being

 

 

 

 

 

 

 

 

 

 

 

 

Take the setting of CH1 for example:

 

 

 

 

 

 

 

 

 

 

Protection

 

short circuit for too long period of time may cause damage on internal circuit. The

 

 

 

 

 

 

 

 

 

 

 

 

1.

b0 is reserved.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.

b1 is reserved.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

current output can be open circuit.

 

 

 

 

 

 

 

 

 

 

 

 

 

3. When b2 is set as 1, all the settings will return to default settings.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ERR LED definition: default of b12 ~ b15 = 1111

 

 

 

 

 

 

 

 

 

 

ASCII/RTU mode.

 

#33

 

H’40B7

 

 

 

R/W

Returning to default setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. b12 corresponds to CH1. When b12 = 1 or the scale exceeds the range,

 

 

 

 

Communication speed: 4,800/9,600/19,200/38,400/57,600 /115,200 bps

 

 

 

 

 

 

 

 

 

 

 

 

 

ERR LED will flash.

 

 

 

 

 

 

 

 

 

 

 

 

 

Communication mode

 

 

 

 

 

 

 

 

 

 

 

 

 

2. b13 corresponds to CH2. When b13 = 1 or the scale exceeds the range,

 

 

 

ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ERR LED will flash.

 

 

 

 

 

 

 

 

 

 

 

 

 

(RS-485)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1)

 

 

 

 

 

 

 

 

 

 

 

 

3. b14 corresponds to CH3. When b14 = 1 or the scale exceeds the range,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ERR LED will flash.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS-485 cannot be used when connected to PLC MPU.

 

 

 

 

 

 

 

 

 

 

 

 

4. b15 corresponds to CH4. When b15 = 1 or the scale exceeds the range,

 

 

When connected to

 

The modules are numbered from 0 to 7 automatically by their distance from MPU.

 

 

 

 

 

 

 

 

 

 

 

 

 

ERR LED will flash.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#34

 

H’40B8

 

 

 

R

 

Firmware version

 

Displaying the current firmware version in hex; e.g. version 1.0A is indicated

 

 

DVP-PLC MPU in

 

No. 0 is the closest to MPU and No. 7 is the furthest. Maximum 8 modules are

 

 

 

 

 

 

 

as H’010A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

series

 

allowed to connect to MPU and will not occupy any digital I/O points.

#35 ~ #48

 

 

 

 

 

 

 

 

For system use

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit: mm

CH4

SLD +

 

 

 

L -

1

DIN rail (35mm)

6

Terminals

2

Connection port for extension unit/module

7

Mounting hole

3

Model name

8

I/O terminals

4

POWER, ERROR, A/D indicator

9

Mounting port for extension unit/module

5DIN rail clip

2.2. Others

 

 

Power Supply

 

Max. rated power

24 VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%), 2.5W supplied by external power.

 

consumption

 

 

 

 

Environment

 

Environment spec.

Same as that of DVP-PLC MPU

Control Register

Symbols

○: latched (when written in through RS-485 communication)

: non-latched

R:Able to read data by FROM instruction or RS-485 communication

W:Able to write data by TO instruction or RS-485 communication

Explanations:

1.CR#0: Model name. The user can read the model name from the program and see if the extension module exists.

Page 1
Image 1
Delta DVP04TC-H2 instruction sheet Introduction, Specifications, Control Register, Model Explanation & Peripherals, Others