Climate Control Unit - CCU
Technical Specifications
General
Safety | EN 60 950 class I |
| UL 60 950 |
| CE |
EMI, radiated | EN 55022, class B |
Compliant with | EN 300 |
| FCC part 15 |
| Telcordia |
Cooling | Convection cooled |
Protection | IP20 |
Input |
|
Voltage range | 18 … 59 VDC |
Current maximum | 0.4 ADC maximum |
EMI, conducted | EN 55022, class B |
Input protection | Internal fuse |
Input switch | None |
Features |
|
Cooling control | Up to 2 ports |
Heater control | 1 port |
Lighting control | 1 port |
Temperature | 2 ports |
Intrusion | 1 port |
Display | LED |
Local monitoring | |
Remote monitoring | None |
Remote alarming | Dry contacts |
Function
Outdoor cabinet environment control
Versatile cooling devices control
Heater control
Lighting control
Local parameter setting function w/o additional tool
AC or DC type cooler, heater and lighting compatible
PWM fan speed control
User definable alarm
oC / oF convertible display
User Interfaces
Status indications
Dry Contact
Alarm
LED
Mechanics
Height, body
Height, overall
Width, overall
Depth, body
Depth, overall
Weight
Environment
Operating temperature
Relative humidity
LED 《Cooling 1》
LED 《Cooling 2》
LED 《Heater》
LED 《CCU Fail》
LED 《Alarm》
Environment temperature,
parameter setting, error
messages
1.Major
2.Minor
3.Alarm
4.
5.System Major Alarm
6.System Minor Alarm
CCU Fail Alarm Cooling 1 fail Cooling 2 fail Heater fail High temperature Low temperature Temperature sensor fail Intrusion alarm
High water Smoke / Fire High humidity
95 mm / 3.7 in
115 mm / 4.4 in
120 mm / 4.7 in
55.8mm / 2.2 in
60.1mm / 2.4 in
0.24kg / 0.5 lb
95 %, non condensing
All specifications are subject to change without notice according to engineering progress.
DELTA ELECTRONICS, INC. |
|
3, Tung Yuan Road, Chungli Industral Park, |
|
Taoyuan Hsien 320 Taiwan, R.O.C. | www.deltaww.com |
Phone: +886 3 |