2007-07-09

5011659301-SBT1

CME-USB01USB Interface for VFD-E Series Instruction Sheet

Please thoroughly read this instruction sheet before installing option cards and putting them into use.

The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the most updated version at http://www.delta.com.tw/industrialautomation/.

XLayout

USB Card (CME-USB01)

ZSpecification

Environmental

YInstallation

Operating Temperature

Storage Temperature

Ambient

Humidity

Installation Altitude

Vibration

-10oC to 50oC (non-condensing and not frozen)

-20oC to + 60oC

Less than 90%RH (non-condensing)

Below 1000m

Less than 20Hz: Maximum 9.81 m/s2 (1G);

20 ~ 50Hz:

Maximum 5.88 m/s2 (0.6G)

Make sure that the AC Motor Drive is powered off before operation. DO NOT insert or remove the card when the AC Motor Drive is powered on.

Please mount the extension card as shown and fix it with the screw packed with the card.

Screw torque:

Maximum 2kgf-cm

USB Cable

USB Type B to CME-USB01

USB Type A to PC

NOTE

Refer to Chapter 5: Parameters 9 (Group 9) in the user manual for further details.

NOTE

Always use this product in a clean indoor location free from dust, corrosive gas and liquid.

Inputs/Outputs

 

Baud Rate

Supports 4800, 9600, 19200,

 

38400, 57600 bps.

 

 

 

USB

USB v1.1

 

Specification

[Notes

Please use shielded wires to avoid interferences and connect the shield to ground.

To avoid interference, route the extension card wires separately and as far away (at least 15cm) as possible from other control wires, motor wires and power wires, etc. Where these wires must cross each other, please make sure they are at a 90o angle.

Always use and operate this product within the limit of its specifications.