http://www.delta.com.tw/industrialautomation/ |
|
|
|
|
|
| |||||||||||||||||||||||
DVP Peripheral Series | Frequency Measurement Card | ||||||||||||||||||||||||||||
|
| Instruction Sheet | |||||||||||||||||||||||||||
1 |
|
| |||||||||||||||||||||||||||
| WARNING |
This frequency measurement card is a specific function card for
Frequency measurement card is an OPEN TYPE without any mechnical shield. When installing this card, user is supposed to power off the MPU and take precaution against static
Do NOT connect the AC power line to any of the input/output terminals, or it will damage the PLC. Make sure all the wiring is correct before power on.
To enhance the
Frequency measurement card is only workable for the
3.2 Operation mode:
There are 3 types of operation mode for the frequency measurement card. User can decide the operation mode by setting CR1. Detail information as follows:
Mode 1: Pulse Interval Length Measurement (CR1=K1) Measurement method of pulse interval:
Interval of
Interval of
Inputs of pulse interval measurement: F0, F1.
Time unit of pulse interval measurement: 50ns, 100ns.
Interrupt function: I180 will be executed after frequency measurement card detects rising edge or falling edge in F0 and F1. And bit 0 of CR9 will inform interrupt trigger by F0 while bit1 of CR9 by F1. For more information, please see section 6.1.
Input frequency range: 1Hz~1kHz.
Accuracy: ±0.01% (max.)
Mode 2:
There are 3 types for mode 2 the
Pulse/Direction: F0 is pulse input point. F1 is the signal to control the
| Value |
| F0 |
| Value |
| F1 | ||||
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
F1 |
| High |
| F0 |
| High |
| ||||
|
| Low |
|
|
| Low |
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
Mode 3: Pulse Number Capture (CR1=K3)
Input point: F0 is pulse input point. F1 is the signal to capture pulse number.
Following diagram show the count method of pulse number:
F0
F1
Pulse Captured Period
The calculation of the pulse numbers for F0 is based on the interval between two rising edge or falling edge of F1.
Interrupt function: when PLC set M1019 (flag of operation mode setting for frequency measurement card) and D1034 (flag of operation mode setting for frequency measurement card) to set up operation mode, I180 will be triggered based on the
Accuracy: ±1 pulse.
4 |
| CONTROL REGISTER |
2 |
| INTRODUCTION |
Thank you for choosing Delta DVP series product. The frequency measurement card
There are 255
Nameplate Explanation:
|
| Model: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Mode Number |
|
|
|
| ||||||||||||||||||||||
|
|
| ||||||||||||||||||||||||
Serial Number & Barcode |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| DVPF2FR0T5280001 | |||||||||||||||||||||||
|
|
| ||||||||||||||||||||||||
Version |
|
|
| |||||||||||||||||||||||
| VX.XX |
|
|
|
|
|
|
|
| MADE IN XXXXXX | ||||||||||||||||
|
|
|
|
|
|
|
|
|
Serial Number Explanation:
Production number
Production week
Production year 2005
Production factory (Taoyuan plant)
Version type
Production model
F0
F1
Count up |
|
| Count down |
|
|
|
|
|
|
|
|
Count value
F0
F1
Count up |
|
|
|
| Count down | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Count value
Control Register Explanation Table:
| CR NO. |
|
|
|
|
|
| Latched |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| Attribute |
| Factory |
|
| Mode |
|
|
| Function explanation |
|
| |||||
| HW | LW |
|
|
| setting |
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| #0 |
|
| R |
| H2A0 | ° |
|
|
|
| System default, read only, number=H’2A0 |
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Frequency measurement card execution mode |
| ||||||
| #1 |
|
| R/W* |
| K0 | ° |
|
|
|
| K1 (mode 1) |
|
| K2 (mode 2) |
| K3 (mode 3) |
| |||
|
|
|
|
|
|
|
| Pulse interval |
|
|
| Pulse number |
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| measurement |
|
|
| capture |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| #2 |
|
| R/W |
| K0 | ° | 1,2,3 |
|
| Frequency | measurement card Run | of Stop |
| |||||||
|
|
|
|
|
| K0 |
|
|
|
|
| K1 |
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Stop |
|
|
|
|
| Run |
|
| #3 |
|
| R/W* |
| K0 | ° | 1,3 |
|
|
| F0 record item | (range 0~40) |
|
| ||||||
| #4 |
|
| R/W* |
| K0 | ° | 1,3 |
|
|
| F1 record item (range 0~40) |
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Trigger by rising edge or falling edge |
| ||||||
| #5 |
|
| R/W* |
| K0 | ° | 1,3 |
|
| rising edge=0, |
|
| ||||||||
|
|
|
|
|
| CR5 Low byte |
| CR5 High byte |
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| F0 |
|
|
|
|
| F1 |
|
| #6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Reserved |
|
| |||
| #7 |
|
| R/W* |
| K2 | ° | 1 |
|
| F0 measure time unit |
|
| 50ns measure unit K1 |
| ||||||
| #8 |
|
| R/W* |
| K2 | ° | 1 |
|
| F1 measure time unit |
| 100ns measure unit K2 |
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Mode | 1: interrupt trigger flag |
|
| |||
| #9 |
|
| R |
| K0 |
|
| 1 |
|
| When F0 trigger I180, bit0 of CR9 will be ON. |
| ||||||||
|
|
|
| ° |
|
| When F1 trigger I180, bit1 of CR9 will be ON. |
|
Product Outline:
Vertical view
Screw hole
Terminal
Dismounting Holder (for dismounting from PLC)
F0
F1
Value |
|
| F0 (A phase) | ||
|
|
|
| ||
|
| ||||
|
|
|
| ||
F1 |
| High |
| ||
(B phase) |
| Low |
|
|
|
|
|
|
| When PLC read CR10~CR11, bit0 of CR9 will be OFF. | |
|
|
|
|
|
| When PLC read CR12~CR13, bit1 of CR9 will be OFF. | |
#11 | #10 | R | K0 | ° | 1 | F0 pulse interval measurement | |
#13 | #12 | R | K0 | ° | 1 | F1 pulse interval measurement | |
#15 | #14 | R | K0 | ° | 1 | F0 value of frequency floating point | |
#17 | #16 | R | K0 | ° | 1 | F1 value of frequency floating point | |
#19 | #18 | R | K0 | ° | 1 | F0, F1 | |
|
|
|
|
|
|
| |
#21 | #20 | R/W | K0 | ° | 2 | be cleared when frequency | |
|
|
|
|
|
|
| measurement card stop |
Terminal |
| RUN/STOP indicator |
|
|
|
| Power indicator | F0 |
|
|
|
|
| |
3 |
| SPECIFICATION | F1 |
|
3.1 Basic Specification: |
|
|
|
|
|
|
| Count up | Count down |
|
| Terminals [A+] & |
| |
| Electric Level |
|
| |
| SINK or SOURCE |
|
| |
|
|
|
|
t1 | Count value |
t 1 |
Input Signal |
| t 2 | t1: rising/falling time ≦0.8us |
| Pulse Type | t2 | t2: ON/OFF pulse bandwidth ≧2.5us |
|
| t 3 | t3: phase difference of A, B phase ≧1us |
|
| t 3 |
|
Storage and | Storage | ||
Environment | Operation | Operation: 0oC~55oC (Temperature), 50~95% (Humidity), Pollution degree: 2 |
|
|
|
|
|
|
| |||||
#22 | R/W* | K0 | ° | 2 | K0 | K1 |
|
| K2 | ||
| A/B phase two |
| A/B four times | ||||||||
|
|
|
|
|
| Pulse/Direction | times frequency |
| |||
|
|
|
|
|
|
| frequency count | ||||
|
|
|
|
|
|
| count |
|
| ||
|
|
|
|
|
|
|
|
|
| ||
#23 | R | K0 | ° | 2 | Indication | flag of count up or count down | |||||
K0 |
|
|
|
| K1 | ||||||
|
|
|
|
|
| Count up |
|
|
| Count down | |
#24 | R/W | K0 |
| 2 | Flag of | of | |||||
° | K0 |
|
|
|
| K1 | |||||
|
|
|
|
|
| Stop counting |
|
| Start counting | ||
#26 #25 | R/W | K0 | ° | 3 | Number of captured pulse |
| |||||
#27 | R/W* | K0 | ° | 3 | Method of pulse count |
| |||||
K0 |
|
|
|
| K1 | ||||||
|
|
|
|
|
| Pulse number |
| Pulse number accumulated | |||
#28 | R/W | K0 | ° | 1 | F0 | (K0~K32767) | |||||
#29 | R/W | K0 | ° | 1 | F1 | ||||||
|
| #30~#32 |
|
|
| Reserved |
| ||||
|
|
|
|
|
| Return to factory setting |
| ||||
| #33 | W* | K0 | ° |
| When writing “1” into CR33, all the CR of frequency measurement | |||||
|
|
|
|
|
| card will return to factory setting and modify former “1” as “0”. | |||||
| #34 | R | K0 | ° |
| Version explanation: high byte is the value in the left side of decimal | |||||
|
| and low byte is the value in the right side of decimal. e.g. H1000 is | |||||||||
|
|
|
|
|
|