The Static Switch Product Line

SSW 230V-6kVA

SSW 230 V – 20 kVA →

Description:

The static switch product line is a micro-controller driven state-of-the-art switch between the AC mains and the inverter to provide uninterruptible AC power. After an extremely quick detection of a mains fault, the static switch transfers the load almost without cut off to the redundant AC line. A communication and synchronization bus is responsible for the system performance and the Delta inverters are synchronized to the public AC mains. Modular UPS configurations in ON LINE or OFF LINE mode can be realized in combination with Delta inverters and DC power systems with battery backup.

Features

Two static switch models 6 kVA and 20 kVA

230 Vrms / 50 Hz single phase

ON LINE or OFF LINE mode selection

High performance AC line quality monitoring

Quick detection of AC faults

Configurable switching criteria

Load transfer of up to 6 kVA or 20 kVA

Synchronization of the Delta inverter group

Convection cooled

Compact and light

Power connectors on the rear

Specification

General

 

 

 

Product name

SSW 230 V – 6 kVA

 

SSW 230 V – 20 kVA

Safety

EN 60 950, class I

 

EMI, radiated compliant with

EN 55 022, class B

 

EN 300 386-2

 

 

Cooling

Convection cooled

 

Public AC Input

 

 

 

Voltage range

184 ... 276 Vrms

 

 

Frequency range

45 - 55 Hz

 

 

EMI, conducted compliant with EN 55022, class B

 

Inverter AC Input

 

 

 

Voltage range

230 Vrms ± 1%

 

 

Frequency

50 Hz

 

 

EMI, conducted compliant with EN 55022, class B

 

AC Output

 

 

 

Voltage, nominal

230 Vrms

 

 

Frequency, nominal

50 Hz

 

 

Maximum power

6 kVA / 20 kVA

 

 

cosφ, range

0 .. 1 ind. and cap.

 

EMI, conducted compliant with EN 55022, class B

 

Mechanics

6kVA

;

20kVA

Width, overall

2.8” / 70 mm

; 5.3” / 135 mm

Depth, overall

13.8” / 350 mm ; 13.8” / 350 mm

Height, overall

12.2” / 311 mm ; 12.2” / 7U / 311 mm

Weight

7.7 lb / 3.5 kg

;

18.0 lb / 8.6 kg

Switching Criteria

 

 

 

According to

ETS 300 132-1

 

 

Static rms deviation

± 10 %

 

 

Dynamic rms deviation

± 15 % for max. 500 ms

Static freq. deviation

± 2Hz

 

 

Dynamic freq. deviation

± 2Hz for 5 s maximum

Environment

 

 

 

Operating temperature

0 ... + 50 °C

 

 

Relative humidity

95 % max, non condensing