OWNER’S MANUAL

TROUBLESHOOTING

Note: For additional help, visit DESA International’s Technical Service web site at www.desatech.com.

Note: All troubleshooting items are listed in order of operation.

WARNING: Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.

CAUTION: Never use a wire, needle, or similar object to clean pilot. This can damage pilot unit.

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

When ignitor button is pressed, there is no spark at pilot

1.Ignitor electrode not connected to igni- tor cable

2.Ignitor cable pinched or wet

3.Piezo ignitor nut is loose

4.Broken ignitor cable

5.Bad piezo ignitor

6.Ignitor electrode broken

7.Ignitor electrode positioned wrong

1.Reconnect ignitor cable

2.Free ignitor cable if pinched by any metal or tubing. Keep ignitor cable dry

3.Tighten nut holding piezo ignitor. Nut is located behind the mounting bracket.

4.Replace ignitor cable

5.Replace piezo ignitor

6.Replace pilot assembly

7.Replace pilot assembly

When ignitor button is pressed, there is spark at pilot but no ignition

1.Gas supply turned off or manual shutoff valve closed

2.Control knob not in PILOT position

3.Control knob not pressed in while in PILOT position

4.Air in gas lines when installed

5.Depleted gas supply (propane models only)

6.Pilot is clogged

7.Gas regulator setting is not correct

1.Turn on gas supply or open manual shutoff valve

2.Turn control knob to PILOT position

3.Press in control knob while in PILOT position

4.Continue holding down control knob. Repeat igniting operation until air is removed

5.Contact local propane gas company

6.Clean pilot (see Cleaning and Maintenance, page 26) or replace pilot assembly

7.Replace gas control

Pilot lights but flame goes out when control knob is released

1.Control knob not fully pressed in

2.Control knob not pressed in long enough

3.Manual shutoff valve not fully open

4.Pilot flame not touching thermocouple, which allows thermocouple to cool, causing pilot flame to go out. This prob- lem could be caused by one or both of the following:

A)Low gas pressure

B)Dirty or partially clogged pilot

5.Thermocouple connection loose at con- trol valve

6.Thermocouple damaged

7.Control valve damaged

1.Press in control knob fully

2.After pilot lights, keep control knob pressed in 30 seconds

3.Fully open manual shutoff valve

4.A) Contact local gas company

B)Clean pilot (see Cleaning and Maintenance, page 26) or replace pilot assembly

5.Hand tighten until snug, then tighten 1/4 turn more

6.Replace thermocouple

7.Replace control valve

www.desatech.com

Continued

105453

27

Page 27
Image 27
Desa BDV34N(A) installation manual Troubleshooting, Observed Problem Possible Cause