VENTING INSTALLATION INSTRUCTIONS

Installation Planning (Cont.)

VENTING INSTALLATION

INSTRUCTIONS

Continued

GROUND FLOOR INSTALLATION

Recommended Applications:

Minimum Pipe

Overlap 11/4"

Direct Vent

Pipe

Wall

Firestop

Maintain 1"

Minimum Air

Space Around

Outer Pipe When

Penetrating a Wall

10" x 10" Framed Opening

Siding Standoff

Screws

High Wind

Termination

Apply Mastic to

Outside Edge of

Standoff

Exterior Wall with Vinyl Siding

Installation using cabinet surrounds

Through the wall using round or square termination (up to 12" horizontal pipe)

NOT FOR CORNER INSTALLATION

Adjustable

45° Elbow

 

 

 

 

Pipe 12" Max.

 

 

 

Horizontal High

 

 

 

Wind Square

 

 

 

Termination

 

 

 

Wall Firestop

 

 

 

 

Square Termination

 

 

Vertical (V)

Horizontal (H)

T32 Series

29" min.

17" max.

T36 Series

32" min.

17" max.

45° Elbow

 

Exterior Portion of Wall

 

 

Wall

Firestop (Round

 

 

Termination Only)

Figure 13 - Typical Horizontal Termination Cap Mounting with Additional Siding Standoff Installed

Horizontal Termination Configurations

Figures 14 through 18 show different configurations and alternatives for venting with horizontal termination. Each figure includes a chart with critical minimum and maximum dimensions which MUST be met. IMPORTANT: Remember that a horizontal run of venting must have a 1/4" rise for every 12" of run toward the termination.

WARNING: Never run vent downward as this may cause excessive temperatures which could cause a fire. Operation of improperly installed and main- tained venting system could result in serious injury, property damage or loss of life.

Firestop

Slide Ring

Round

Termination

Over Elbow to

Cap

Complete

 

Connection

 

Round Termination

(Kit HTK Shown)

Figure 14 - Horizontal Termination Configuration for Square and Round Terminations

For..com

108860-01C

Page 10
Image 10
Desa (V)T36EP, (V)T36EN installation manual Horizontal Termination Configurations, Ground Floor Installation