VENTING INSTALLATION INSTRUCTIONS
Installation Planning (Cont.)
VENTING INSTALLATION INSTRUCTIONS
Continued
9.Slide wall firestop against interior wall surface and attach with screws provided. See Figure 13 for horizontal termination details.
10.Place fireplace into position and shim with noncombustible ma- terial if needed. Nail or screw side flanges to framing to secure unit in place. IMPORTANT: Make sure fireplace is level before securing. If fireplace is not level it will not work properly.
Minimum Pipe | Siding Standoff | |
Overlap 11/4" | ||
| ||
| Screws | |
Direct Vent |
| |
Pipe |
| |
Wall |
| |
Firestop |
| |
Maintain 1" |
| |
Minimum Air | High Wind | |
Space Around | ||
Outer Pipe When | Termination | |
Penetrating a Wall |
| |
| Apply Mastic to | |
10 3/4" x 10 3/4" | Outside Edge of | |
Framed | Standoff | |
| ||
Opening |
| |
| Exterior Wall | |
| with Vinyl Siding |
Figure 13 - Typical Horizontal Termination Cap Mounting with Additional Siding Standoff Installed
Horizontal Termination Configurations
Figures 14 through 18 show different configurations and alternatives for venting with horizontal termination. Each figure includes a chart with critical minimum and maximum dimensions which MUST be met. IMPORTANT: Remember that a horizontal run of venting must have a 1/4" rise for every 12" of run toward the termination.
WARNING: Never run vent downward as this may cause excessive temperatures which could cause a fire. Operation of improperly installed and main- tained venting system could result in serious injury, property damage or loss of life.
GROUND FLOOR INSTALLATION
Recommended Applications:
•Installation using cabinet surrounds
•Through the wall using round or square termination (up to 12" horizontal pipe)
•NOT FOR CORNER INSTALLATION
45° Elbow
Horizontal High
Wind Square
Termination
Adjustable
Pipe 12" Max.
Wall
Firestop
| Square Termination | |
| Vertical (V) | Horizontal (H) |
V36 Series | 32 3/4" | 17" max. |
V42 Series | 36 3/4" | 17" max. |
45° Elbow
Wall |
| Exterior Portion of Wall | |||
Firestop |
| Firestop (Round | |||
|
|
|
|
| Termination Only) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Horizontal
Round
Termination
Round Termination
(Kit 01491 Shown)
Figure 14 - Horizontal Termination Configuration for Square or Round Termination