11

11 Device Information

Device information for air-to-water heat pumps for heating purposes

1Type and order code

2Design

2.1Degree of protection according to EN 60 529 for compact devices and heating components

2.2Installation Location

3 Performance data

3.1Operating temperature limits:

 

Heating water flow/return flow 1

 

°C / °C

 

Air

 

°C

3.2

Temperature spread of heating water at A2 / W35

K

 

Heat output / COP

at A-7 / W35 2

kW / ---

 

 

at A-7 / W50 2

kW / ---

 

 

at A2 / W35 2

kW / ---

 

 

at A7 / W35 2

kW / ---

 

 

at A10 / W35 2

kW / ---

3.3

Sound power level

 

dB(A)

3.4Heating water flow with an internal pressure differential of m³/h / Pa

3.5

Air flow rate

 

m³/h / Pa

3.6

Refrigerant; total filling weight

 

type / kg

4

Dimensions, connections and weight

 

4.1

Device dimensions

 

H x W x L cm

4.2

Device connections to heating system

Inch

4.3

Weight of the transportable unit(s) incl. packing

kg

5

Electrical Connection

 

 

5.1

Nominal voltage; fuse protection

 

V / A

5.2

Nominal power consumption 2

A2 W35

kW

5.3

Starting current with soft starter

 

A

5.4

Nominal current A2 W35 / cosϕ

 

A / ---

6Complies with the European safety regulations

7Additional model features

7.1Defrosting

Type of defrosting Defrosting tray included

7.2Heating water in device protected against icing 4

7.3Performance levels

7.4Controller internal/external

LA 9PS

IP24

Outdoors

Up to 65 / above 18

-20 to +35

5.5

5.6/ 2.6

5.0/ 2.2

7.1/ 3.2

8.5/ 3.6

9.6/ 4.0 62

1.2/ 9000 2000

R290 / 1.0

132 x 77 x 66 G 1'' external 168

400 / 16

2.2

28

4.0 / 0.8

3

Automatic

Reverse cycle

Yes (heated)

Yes

1

External

LA 12PS

IP24

Outdoors

Up to 65 / above 18

-20 to +35

6.3

7.2/ 2.6

6.4/ 2.0

9.4/ 3.2

11.1 / 3.8

12.1 / 4.0

65

1.4/ 9000 2000

R290 / 1.4

113 x 80 x 159

G 1'' external

235

400 / 16

3.0

30

4.9 / 0.8

3

Automatic

Reverse cycle

Yes (heated)

Yes

1

External

LA 18PS

IP24

Outdoors

Up to 65 / above 18

-20 to +35

8.2

10.6/ 2.4

10.3/ 2.0

14.1/ 3.0

15.8/ 3.3

18.3/ 3.7 74

1.6/ 9000 4000

R290 / 2.0

113 x 80 x 199

G 1'' external

254

400 / 20

4.7

30

8.7 / 0.8

3

Automatic

Reverse cycle

Yes (heated)

Yes

1

External

English

1.See operating limits diagram

2.This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, other parameters, such as, in particular, the defrosting capacity, the bivalence point and regulation, should also be taken into consideration. The specified values, e.g. A2 / W55, have the following meaning: 2 °C external air temperature and 55 °C heating water flow temperature.

3.See CE declaration of conformity

4.The heat circulating pump and the heat pump controller must always be ready for operation.

E-9

Page 10
Image 10