Ducane (HVAC) FITS-ALL 80V warranty Model Number Guide, Physical & Electrical, Mpg A

Models: FITS-ALL 80V

1 4
Download 4 pages 29.44 Kb
Page 2
Image 2
Model Number Guide

Model Number Guide

MPG A V 050

B 3

MPG = Mult-Postion (Gas-Fired Warm Air Furnace)

Series

V = Variable Speed 2-Stage

Nominal Input (Btuh) x 1000

050 = 50,000 Btu/hr.

075 = 75,000 Btu/hr.

100 = 100,000 Btu/hr.

125 = 125,000 Btu/hr

Revision Level

Blank = First Series

Nominal Cooling Airflow Capacity

3 = Adjustable from 600, 800, 1000,

1200 cfm

4 = Adjustable from 1000, 1200, 1400,

1600 cfm

5 = Adjustable from 1400, 1600, 1800,

2000 cfm

Minor Revision Level

B = first minor revision

Physical & Electrical

 

 

 

 

 

Nom.

Flue

 

 

 

 

Model

 

Input

Output

AFUE

Cooling

Size

Volts/

FLA

Transformer

Weight

 

 

(Btuh)

(Btuh)

 

Cap.

(in.)

Hz/Phase

 

 

(lbs.)

 

 

 

 

 

(tons)

 

 

 

 

 

MPGAV050B3

High Fire

50,000

40,000

80

1.5-3.0

4

115/1/60

9.9

40VA, 115 VAC Primary, 24 VAC Secondary

105

Low Fire

40,000

32,000

 

 

 

 

 

 

 

 

MPGAV075B3

High Fire

75,000

60,000

80

1.5-3.0

4

115/1/60

9.9

40VA, 115 VAC Primary, 24 VAC Secondary

113

Low Fire

60,000

48,000

 

 

 

 

 

 

 

 

MPGAV100B4

High Fire

100,000

80,000

80

2.0-4.0

4

115/1/60

11.8

40VA, 115 VAC Primary, 24 VAC Secondary

141

Low Fire

80,000

64,000

 

 

 

 

 

 

 

 

MPGAV125B5

High Fire

125,000

100,000

80

2.0-5.0

5

115/1/60

15.0

40VA, 115 VAC Primary, 24 VAC Secondary

167

Low Fire

100,000

80,000

 

 

 

 

 

 

 

 