Model Ei161RC Ionisation
Technical Specification
Sensor | Ionisation |
Sensitivity: | Complies with BS 5446 Part 1: |
| 2000 |
Source: | Americium 241 (33kBq) |
Button Test: | Simulates the effect of smoke and |
| checks electronics and horn |
Automatic | Circuitry is tested every 40 |
| seconds and unit beeps if fault is |
| detected |
Supply Voltage: | 230V AC, 50Hz |
Battery back up: | Rechargeable Lithium cells |
Continuous green LED | |
Alarm: | Electronic Piezoelectric horn |
Alarm Sound Output: | 85dB(A) (minimum) at 3m |
Alarm Status: | Red LED flashes every second on |
| unit sensing fire |
Normal Operating |
|
Temperature Range: | 0 to 40°C |
Humidity Range: | 15% to 95% Relative Humidity |
Interconnect: | Up to 12 of these units can be |
| interconnected: |
| - Ei161RC/164RC/166RC smoke or |
| heat alarms |
| - Ei261ENRC/261DENRC CO alarm |
| - Ei128RBU relay base |
| Use with optional control (see below) |
Optional Controls: | - Ei1529RC Control Switch |
| - MCP401RC Manual Call Point |
Fixing: | |
Plastic material: | UL94VO flame retardant |
Dimensions: | 145mm diameter x 40mm depth |
Weight: | 281g |
Guarantee: | 5 year (limited) |
Approvals: | Kitemarked to BS EN 14604:2005 |
| (License no. KM07862) and CE |
| certified |
Specifications are subject to change
System Wiring
Wiring for Interconnected Alarms with optional Remote System Control Switch & Manual Call Point
Ensure correct wiring of the alarms and switches as mixing Live and Neutral will blow / damage interconnected units.
Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.+353 61 471277 Fx.+353 61 471053
Email. eielectronics@eiltd.ie
Web: www.eielectronics.com
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice. | Ei161RC DataSht RevB |