Ei Electronics EI 103C Nuisance Alarms, a Important Safeguards, Looking after your Heat Alarm

Models: EI 103C

1 3
Download 3 pages 26.74 Kb
Page 2
Image 2
(b) Connecting the battery.

1.Pull Cover open at Tab (2). Do not remove Cover from base.

2.Place the Base on ceiling or wall exactly where you want to mount the unit. With a pencil, mark the location of the Screw Holes (6)

3.Taking care to avoid any electrical wiring in the ceiling, drill a hole through the centers of the marked locations. Push the plas- tic Screw Anchors provided into the drilled holes. Screw in firmly.

(b) Connecting the battery.

With a pencil, write the date of Battery installation on the inside of the Cover to remind you when to replace the battery (4).

Lift Battery from Battery holder, and snap Battery Connectors to Battery. They fit together only one way (Figure 4).

Figure 4

Figure 5

9 Volt

wiring inside the unit must be kept clear of the test button con- tacts, and must not impede the air flow. Drafts from wiring open- ings, conduit, or mounting boxes/holes, may blow smoke away from the sensing chamber, making it insensitive. It is essential that all such openings be closed by silicone sealant or similar.

Figure 6

COVER (NOT REMOVEABLE)

WIRING HOLE

INTERCONNECT WIRES

TERMINAL 1

TERMINAL 2

TEST BUTTON

CONTACTS

Figure 7

Figure 8

If the alarm fails to sound, follow this checklist.

1.Check Battery Connectors to be sure they are firmly snapped to the Battery.

2.Replace the Battery. (Check the date marked on the Cover when you last replaced the Battery).

3.Refer to “Cleaning Your Heat Alarm” 6 (d).

(c) Replacing the Battery.

7. Nuisance Alarms

If, when the alarm goes off, there is no sign of smoke, heat or noise to indicate that there is a fire, you should get your family into a safe place, before you start investigating.

Check the house carefully in case there is a small fire smould-ering somewhere.

Check whether there is some source of heat, fumes or smoke, for example steam from a kettle triggering a Heat Alarm or cook- ing fumes being drawn past a Smoke Alarm by an extractor. The Heat Alarm or Smoke Alarm initiating the alarm can be identified as it will have a rapidly flashing red light. If there are frequent nui- sance/false alarms it may be necessary to re-locate the offend- ing device away from the cause of the alarm.

8. (a) Important Safeguards

When using household protective devices, basic safety precau- tions should always be followed, including those listed below:

￿

Please read all instructions.

￿

Rehearse emergency escape plans so everyone at home

 

knows what to do in case the alarm sounds.

Battery

Battery

Connectors

NOTE: You may hear a loud chirp when attaching the Battery Connectors to the Battery. Test the installed Heat Alarm - see section 6(a) below.

Some models will be fitted with a battery missing indicator warn- ing flag which pops up when the battery is removed. This pre- vents the cover from closing when there is no battery in the unit. When the battery is being installed or changed, this flag must be held down while gently pushing the Battery into the Battery Holder. (see figure 5).

5.Interconnecting your Heat Alarms and Smoke Alarms.

A maximum of 12 interconnect EI 103, EI 100C and EI 105C Heat/Smoke Alarms may be wired together so that when one unit senses fire all other units sound a warning. This helps en- sure the alarms will be heard.

Warning: Do not interconnect to any other Heat / Smoke Alarms

A maximum of 820 feet (250 metres) of wire can be used, (maxi- mum resistance between detectors 50 ohm). The units are inter- connected by wiring all the terminals marked 1 together, and all the terminals marked 2 together, as shown in Figure 6. An open- ing should be made in the label covering the wiring hole in the base, and the wires routed into the unit as shown. Note that the

6

After wiring together the Interconnect Alarms, test the first unit by pressing the button. All the detectors should alarm within 10 seconds and the red light only on the unit being tested, will flash about once a second. Check all the other units similarly.

These Alarms should be interconnected only within the confines of a single family living unit. If they are connected between differ- ent units there may be excessive nuisance alarms. Everybody may not be aware that they are being tested or that it is a nui- sance alarm caused by cooking etc.

6.Looking after your Heat Alarm

(a)Testing your Heat Alarm

It is recommended that you test your Heat Alarm once a week to be sure the unit is working. Press and hold the Test Button until the alarm sounds (it may take up to 10 seconds) see figure 7. It will also help you and your family to become familiar with the sound of the Alarm.

(b) Testing with Heat

When you press the Test Button it simulates the effect of Heat during a real fire. So, there is no need to test the Alarm with Heat.

WARNING: Do not test with flame.

This can be a fire hazard in itself.

If you want to check your Alarm with heat we recommend using a hair dryer with a power rating of at least 1000 watts. Direct the hot air as shown in figure 8 on to the heat sensor and the alarm should sound within 30 seconds.

7

A fresh battery should last about one year. When battery power is low and replacement is necessary, the Alarm will “beep” about once per minute for at least 30 days. The battery must then be replaced. Replace battery if the alarm does not sound when the Test Button is pressed. For maximum reliability, replace battery at least once a year.

If the Power Indicator light ceases flashing every 40 seconds re- place the battery. Be sure to replace the battery as soon as pos- sible to ensure proper operation and to avoid a leaking battery. Leakage could cause damage to the Alarm, furniture, and car- peting.

For replacement batteries, refer to the label inside the Heat Alarm Cover.

WARNING: Use of any other battery may be detrimental to the operation of the Heat Alarm.

(d) Cleaning your Heat Alarm

Heat Alarms are not as susceptible to dust and contamination as Smoke Alarms but it is prudent to clean them periodically. Use the narrow nozzle attachment of your vacuum cleaner to re- move dust, insects and cobwebs from the sides and cover slots where the heat enters. To clean the cover, wipe with a damp cloth. Dry cover thoroughly with cloth.

WARNING: Do not paint your Heat Alarm.

Other than the cleaning described above, no other customer servicing of this product is required. Repairs, when needed, must be performed by the manufacturer.

8

￿ For replacement batteries, refer to label inside Heat Alarm.

￿ NOTE: Constant exposure to high or freezing temperatures

or high humidity may reduce the life of the batteries.

￿ Do not disconnect battery to stop alarm sounding. (Fanning

vigorously with a newspaper or similar will remove heat from

the Heat Alarm and stop it sounding.)

￿ Do not attempt to recharge or burn batteries, as they may

explode. Wrap in paper and discard normally.

￿ When removing battery, handle carefully to avoid possible

eye damage or skin irritation if battery has leaked or cor-

roded.

￿ To maintain sensitivity to heat, do not paint or cover Heat

Alarm in any manner; do not permit any accumulation of

cobwebs, dust or grease.

￿ If unit has been damaged in any way or does not function

properly,do not attempt a repair. Return Heat Alarm (see -

Getting your Heat Alarm Serviced page 11.)

￿ This appliance is only intended for premises having a resi-

dential type environment.

￿ This is not a portable product. It must be mounted following

the instructions in this leaflet.

￿ Heat Alarms are not a substitute for insurance. The supplier

or manufacturer is not your insurer.

(b) Limitations of Heat Alarms

Heat Alarms combined with Smoke Alarms can significantly help to reduce the risk of fire fatalities.

However independent authorities have stated that these sys- tems may be ineffective in some fire situations. There are a number of reasons for this:

9

P/N B11803

PAGE 6,7,8&9

REV 0

Page 2
Image 2
Ei Electronics EI 103C manual Nuisance Alarms, a Important Safeguards, Interconnecting your Heat Alarms and Smoke Alarms