PERFORMANCE DATA NO LOAD & NO DOOR OPENINGS
AT
Type A with Run/Start | 65°F (18°C) Ambient | 90°F (32°C) Ambient | |
Capacitor | |||
|
| ||
|
|
| |
Operating Time | N/A | 30 to 50% | |
|
|
| |
Temperature | 34º F to 45º F | 34º F to 45º F | |
|
|
| |
Low Side Pressure | 30 to 45 psig | 30 to 45 psig | |
208 to 310 kPa | 208 to 310 kPa | ||
| |||
|
|
| |
Low Side Pressure | |||
| |||
|
|
| |
High Side Pressure | 90 to 120 psig | 130 to 175 psig | |
(last 1/3 cycle) | 621 to 827 kPa | 896 to 1207 kPa | |
|
|
| |
Wattage (last 1/3 cycle) | 85 to 125 | 85 to 125 | |
|
|
| |
Amps (running) | .75 to 1.2 | .75 to 1.2 | |
|
|
| |
Base Voltage | 115 vac (127 vac max) |
| |
|
|
| |
| CONDENSER FAN MOTOR |
| |
|
|
| |
Watts | RPM | Amps | |
|
|
| |
3.1 | 1100 CW Opposite Shaft | 0.03 Running | |
|
|
| |
| EVAPORATOR FAN MOTOR |
| |
|
|
| |
1.7 each | 9000 | .02 each | |
|
|
|
service data sheet
241958200
REFRIGERATOR DRAWERS - R134a
important safety NOTE
The information provided herein is designed to assist qualified repair personnel only. Untrained persons should not attempt to make repairs due to the possibility of electrical shock. Disconnect power cord before servicing this appliance.
IMPORTANT
If any green grounding wires are removed during servicing, they must be returned to their original position and properly secured.
Caution
All electrical parts and wiring must be shielded from torch flame. DO NOT allow torch to touch insulation; it will char at 200°F and flash ignite (burn) at 500°F. Excessive heat will distort the plastic liner.
NOTE
Your Electrolux refrigerator drawers has been designed for
To ease unit installation and removal, it is recommended that the cabinet rough opening dimensions be increased by at least ¼ inch over the dimensions given for your unit.
IMPORTANT: PLEASE RETURN THIS SHEET TO IT’S ORIGINAL LOCATION.
WARNING
Double drawer Refrigerator Drawers are designed to be
All screws supplied with the
Unit Dimensions
Width | Height | Depth |
2313/16 inch | 263/4 inch |