THERMOSTATS
LINE VOLTAGE THERMOSTATS
1A11-2
1a11-2 LIGHT DUTY FAN COIL THERMOSTAT
For Direct Control of Line Voltage Valves and/or Blower Motors on Fan Coil Units Featuring Manual Changeover From Heat to Cool and a
FEATURES
•Mounts to a standard vertical outlet box or on a
•Wiring color coded for ease of installation.
•
•System Switch: Heat – OFF – Cool. “OFF” breaks both valve and fan circuits.
•Beige color.
SPECIFICATIONS
|
|
| FAN |
|
|
| HIGH | MED | LOW |
| |
CUSTOMER |
| TAN | BLUE | RED |
|
CONNECTIONS |
|
|
|
|
|
THERMOSTAT |
|
|
|
|
|
SCHEMATIC |
|
|
|
|
|
HIGH
FAN MED
SWITCH
LOW
RED
HEAT
SYSTEM
SWITCH OFF
COOL
BLUE
*L1 is Power In
VALVE | L1* | GND |
(SOL) | (HOT) | |
ORANGE | BLACK | GREEN |
HEAT
COOL
Dimensions . . . | . . . . . . . . . 41/2”H x 41/2” W x 21/4”D |
Agency | . . . . . . . . . . . . . . . . . U.L. listed and C.S.A. approved |
PARTS AND ACCESSORIES
• Thermostat guards – see pages
–Thermostat cycles both fan and valve
–Thermostat cycles fan only (if valve is not used tape orange lead)
–System “OFF” breaks both valve and fan circuits
–Thermostat cycles valve only with continuous fan (interchange valve and L1 leads)
Note: Above FAN and SYSTEM switches shown in
MED and HEAT positions respectively.
manual heat/cool changeover
|
|
|
|
|
| Contact Ratings |
|
| Pilot Duty | |
Model |
|
| Switch | Motor Ratings (inductive) Full Load | Motor Ratings (inductive) Locked Rotor | 120/240 | ||||
Number | Range | Differential | Action | 120 VAC | 240 VAC | 277 VAC | 120 VAC | 240 VAC | 277 VAC | 277 VAC |
36 to 90°F | 1.5°F | SPDT | 5.5A | 2.75A | 2.3A | 33.0A | 16.5A | 13.8A | 120A | |
| (2 to 32°C) |
|
|
|
|
|
|
|
|
|
30 |