Wall-Mounted Dewpoint Sensor
Product Information Sheet 210-2002
Set the Low End Point field to 0.
Set the HighEnd Point field to 5.0.
Set the Low Eng. Units field to 0.
Set the High Eng. Units field to 80.
Set the Low End Limit field to -0.5.
Set the HighEnd Limit field to 6.5.
REFLECS
1. Log in to the controller.
2. From the Main Menu, select 4 -Sensor
Control.
3. From the Sensor Control screen, select 2 -
Setup.
4. From the Select Sensor screen, choose the
sensor you wish to set up:
5. Once you select a sensor, the Sensor Setup
screen opens. Enter a name for the sensor in
the Name field (for example, DEWPOINT)
and set the Type field to Linear by using the
scroll keys or pressing the red button + the
(L) button.
6. Press 0 to go back to the Sensor Control
screen. Select 3 -Setpoints and then choose
the sensor to set Gain and Offset.
Analog Input Screen - Set Sensor Properties
REFLECS Login Screen
REFLECS Main Menu Screen
Sensor Control Screen
Select Item Screen
Sensor Control Screen
49