Specifications

8.0

SPECIFICATIONS

 

Transfer Time (to and from maintenance bypass)

< 6 milliseconds

Operating Ambient Temperature

32°F to 104°F (0°C to +40°C)

Storage Ambient Temperature

-4°F to 140°F (-20°C to +60°C)

Dimensions with brackets W x D x H: in. (mm)

19.0 x 5.24 x 5.24 (482.6 x 133 x 133)

Humidity

0 to 95% non-condensing

Agency/Standards

UL1778, c-UL, ISTA Procedure 1A

Electrical Rating

See Model Label on 3U POD

This 3U POD is intended for use with a UPS meeting all the following requirements:

UPS input cord is compatible with the rating and type of receptacle on the 3U POD labeled “CON-

NECT UPS LINE CORD HERE.”

UPS output receptacle is compatible with the 3U POD input power connector labeled “UPS.”

Available utility is compatible with the 3U POD input connection and an appropriately sized branch circuit breaker has been provided.

Table 2

Breaker specifications

 

 

 

Model

Input Current

Recommended

Recommended Wire

Maximum Wire

Terminal

VA - Volt

Rating

(Maximum) External

(including ground wire)

Accepted by

Tightening

Rating

at 208V

Overcurrent Protection

(75ºC copper wire)

Terminal Block

Torque

MP2-220N

16A

20A

12 AWG

10 AWG

20 in-lb

8.1Product Warranty Registration

To register for warranty protection:

Visit the Quick Links section of our Web site at: http://www.liebert.com

Click on Product Warranty Registration and fill in the form.

If you have any questions, please contact us at:

US: 800-222-5877

Outside the US: 614-841-6755

upstech@liebert.com

11

Page 15
Image 15
Emerson 3U MP2-220N user manual Product Warranty Registration, Specifications