Specifications
8.0 | SPECIFICATIONS |
|
Transfer Time (to and from maintenance bypass) | < 6 milliseconds | |
Operating Ambient Temperature | 32°F to 104°F (0°C to +40°C) | |
Storage Ambient Temperature | ||
Dimensions with brackets W x D x H: in. (mm) | 19.0 x 5.24 x 5.24 (482.6 x 133 x 133) | |
Humidity | 0 to 95% | |
Agency/Standards | UL1778, | |
Electrical Rating | See Model Label on 3U POD |
This 3U POD is intended for use with a UPS meeting all the following requirements:
•UPS input cord is compatible with the rating and type of receptacle on the 3U POD labeled “CON-
NECT UPS LINE CORD HERE.”
•UPS output receptacle is compatible with the 3U POD input power connector labeled “UPS.”
•Available utility is compatible with the 3U POD input connection and an appropriately sized branch circuit breaker has been provided.
Table 2 | Breaker specifications |
|
|
| |
Model | Input Current | Recommended | Recommended Wire | Maximum Wire | Terminal |
VA - Volt | Rating | (Maximum) External | (including ground wire) | Accepted by | Tightening |
Rating | at 208V | Overcurrent Protection | (75ºC copper wire) | Terminal Block | Torque |
16A | 20A | 12 AWG | 10 AWG | 20 |