Emerson 450XL manual 452XL 454XL 456XL 458XL 4512XL 4516XL

Models: 450XL

1 8
Download 8 pages 36 Kb
Page 8
Image 8

OTH003-EN-0512

General Dimensions

 

452XL

454XL

456XL

458XL

4512XL

4516XL

 

 

 

 

 

 

 

Number of Cylinders

2

4

6

8

12

16

 

 

 

 

 

 

 

Maximum RPM

1200

1200

1200

1200

1200

1200

 

 

 

 

 

 

 

Bore & Stroke (mm)

114 x 114

114 x 114

114 x 114

114 x 114

114 x 114

114 x 114

 

 

 

 

 

 

 

CFM @ Maximum RPM (m3/h)

169

336

507

676

1014

1352

Refrigeration Capacity at -12°C/+35°C, R-717 (kW)

84

172

257

341

514

686

 

 

 

 

 

 

 

Suction Connection (inch)

2 1/2

3

4

4

5

6

 

 

 

 

 

 

 

Discharge Connection (inch)

2

2 1/2

3

3

2 x 3

2 x 3

 

 

 

 

 

 

 

Unit Weight Less Motor (kg)

862

1225

1406

1542

2404

2630

 

 

 

 

 

 

 

Oil Charge (l)

19

27

27

27

53

53

 

 

 

 

 

 

 

Standard Steps of Unloading (%)

0

50

33/66

24/50

33/66

25/50

 

 

 

 

 

 

 

Option 1 Steps of Unloading (%)

50

25/50/75

-

25/50/75

-

25/50/75

 

 

 

 

 

 

 

Option 2 Steps of Unloading (%)

100

50/100

33/66/100

25/50/75/100

33/66/100

25/50/75/100

 

 

 

 

 

 

 

Maximum Discharge Temperature (°C)

149

149

149

149

149

149

 

 

 

 

 

 

 

Crankcase Oil Temperature Range (°C)

43-54

43-54

43-54

43-54

43-54

43-54

 

 

 

 

 

 

 

Vilter reserves the right to make changes in design and specifications without notice.

For more details, see www.emersonclimate.eu

Emerson Climate Technologies GmbH - European Headquarters - Pascalstrasse 65 - 52076 Aachen, Germany

Tel. +49 (0) 2408 929 0 - Fax: +49 (0) 2408 929 570 - Internet: www.emersonclimate.eu

The Emerson Climate Technologies logo is a trademark and service mark of Emerson Electric Co. Emerson Climate Technologies Inc. is a subsidiary of Emerson Electric Co.

Copeland is a registered trademark and Copeland Scroll is a trademark of Emerson Climate Technologies Inc.. All other trademarks are property of their respective owners.

Information contained in this brochure is subject to change without notification.