Emerson 60HZ, 40-120KVA specifications Site Planning Data 40-120kVA, 60Hz, 480VAC, Ocpd VDC

Models: 480VAC 40-120KVA 60HZ

1 2
Download 2 pages 62.47 Kb
Page 2
Image 2

Liebert® NX3-Phase UPS: 40-120kVA, 60Hz, 480VAC - Site Planning Data

Site Planning Data - 40-120kVA, 60Hz, 480VAC

UPS Rating

Voltage

 

AC Input

 

 

Battery

AC Output

 

Mechanical Data

 

 

 

 

 

Current (A)

Rec.

Nom.

 

Max.

Current

Dimensions

Weight

Heat Dis.

Cooling Air

kVA

kW

Input

Output

Nom.

Max.

OCPD

VDC

 

Discharge

Nom.

OCPD

WxDxH, in. (mm)

lb. (kg)

BTU/hr (kWH)

CFM (m3/hr)

40

36

480

480

48

66.8

90

480

 

98

48

70

 

1290 (585)

11,612 (3.4)

620 (1050)

60

54

480

480

72

100.2

125

480

 

146

72

110

23.6 x 38.2 x 78.7

1290 (585)

15,204 (4.5)

620 (1050)

80

72

480

480

96

133.6

175

480

 

195

96

150

1290 (585)

20,273 (5.9)

620 (1050)

 

(600 x 970 x 2000)

100

90

480

480

120

167.1

225

480

 

244

120

175

1422 (645)

23,496 (6.9)

920 (1550)

 

 

120

108

480

480

144

200.5

250

480

 

293

144

225

 

1422 (645)

28,196 (8.3)

920 (1550)

See Notes for Table (below):

1

2,3,5,8,12

6

4

 

1,3,8,12

1,3,8,12

6

13

14

Notes for Table

1.Nominal (Nom) current is based on full rated output load at nominal input voltage.

2.Maximum (Max) current (140% of nominal) is short duration for battery recharge conditions and low input voltage.

3.UPS input and bypass cables must be run in separate conduit from output cables.

4.Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.

5.For Single Input units only.

For Dual Input units, see “Electrical Data Specification Sheet, 40-120kVA UPS Module, Single or Dual Input Liebert NX - U3819100.”

6.OCPD = Overcurrent Protection Device. Recommended AC input and AC output overcurrent protection represents 125% of nominal full load current (continuous) plus 100% of recharge current (non-continuous) per NEC 215.

7.Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground conductors are recommended. Neutral conductors to be sized for full capacity per NEC 310-15 (b)(4). References are per NEC 1999.

8.Wiring requirements:

AC Input: 3-phase, 3-wire, plus ground

AC Output: 3-phase, 3-wire, plus ground

9.All wiring is to be in accordance with national and local electric codes.

10.Minimum access clearance is 3 ft. (0.9m) front and 8 in. (203mm) above the UPS.

Notes for Table (continued)

11.Top or bottom cable entry through removable access plates. Punch plate to suit conduit size, then replace.

12.Control wiring and power wiring must be run in separate conduit.

13.Dimensions and weights in table do not include external battery cabinet.

Additional Notes

Input and output wiring and breakers for a Liebert NX with Softscale technol- ogy should be sized for the maximum scalable capacity. For example, a 40kVA Liebert NX that is scalable to 80kVA should be installed with wiring and breakers rated for an 80kVA configuration.

If site configuration includes a backup emergency generator, it is recom- mended that the engine generator set be properly sized and equipped for a UPS application. Generator options would typically include an isochronous governor (generator frequency regulation) and a UPS-compatible regulator (generator voltage regulation). Consult generator manufacturer for required generator options and sizing.

If site configuration includes an automatic transfer switch, refer to Liebert Power Line titled “Criteria for Application of Automatic Transfer Switches (ATS) With Uninterruptible Power Supply (UPS) Systems,” publication

91K-PLT-48-02. It is also recommended that the transfer switch be equipped with auxiliary contacts for UPS “on generator” current limit. Consult transfer switch manufacturer for required transfer switch options and sizing.

If site configuration requires an external isolated maintenance bypass circuit, it should be noted that utility AC input might not be in phase with the UPS AC output. Consult a Liebert sales representative or applications engineer.

© 2008 Liebert Corporation

All rights reserved throughout the world. Specifications subject to change without notice.

® Liebert is a registered trademark of Liebert Corporation.

All names referred to are trademarks or registered trademarks of their respective owners.

SL-25218_REV0_03-08

Technical Support / Service

United States

800-222-5877 (Outside U.S. 614-841-6755)

1050 Dearborn Drive

upstech@emersonnetworkpower.com

P.O. Box 29186

Web site: www.liebert.com

Columbus, OH 43229

2

Page 2
Image 2
Emerson 60HZ, 40-120KVA specifications Site Planning Data 40-120kVA, 60Hz, 480VAC, Ocpd VDC

480VAC, 40-120KVA, 60HZ specifications

The Emerson 40-120KVA UPS is a high-performing uninterruptible power supply designed to ensure the reliability and continuity of critical operations across various industries. This UPS operates at 480VAC and 60Hz, making it suitable for environments where high-power demands are common.

One of the standout features of this UPS system is its modular design, which allows for easy scalability. Organizations can expand their power capacity as their needs grow, making the Emerson 40-120KVA UPS a future-proof investment. The system operates with high efficiency, minimizing energy consumption and operational costs. This is vital for data centers and industrial applications where energy management is increasingly important.

The Emerson UPS incorporates advanced digital signal processing technology, delivering real-time monitoring and control. This enhances the overall performance and reliability of the system, providing seamless power protection against voltage fluctuations, surges, and interruptions. With a total harmonic distortion of less than 5%, the UPS ensures a clean and stable power output, preserving the integrity of sensitive electronic equipment.

Another noteworthy characteristic of the Emerson 40-120KVA is its redundancy features. The system supports N+1 redundancy, allowing for one extra module to ensure uninterrupted service in case of a failure. This design offers peace of mind for critical applications, ensuring that there is no single point of failure.

User-friendliness is also a significant aspect of the Emerson UPS. The intuitive graphical user interface simplifies monitoring and management, allowing operators to assess system performance and status at a glance. Additionally, remote monitoring capabilities enable real-time tracking of system health and performance from anywhere, providing flexibility and oversight for facility managers.

The Emerson 40-120KVA UPS also meets stringent safety and compliance standards, ensuring reliable operation in demanding environments. Its robust design is suitable for a variety of applications, including information technology, telecommunications, and industrial processes. Overall, the Emerson 40-120KVA UPS stands out as a reliable, efficient, and versatile solution for businesses aiming to safeguard their critical power supply against any disruption.