Emerson 65 Specifications, Surge Current Capacity, EMI/RFI Noise Rejection Values, Enclosure

Models: 65

1 2
Download 2 pages 36.94 Kb
Page 2
Image 2
Specifications

Specifications

Surge Current Capacity

 

Minimum Tested

Single Pulse Surge Current Capacity

Protection Mode

Impulses Per Mode

Model 100

Model 80

Model 65

Line-to-Neutral

> 3,500

> 100,000 A

> 80,000 A

> 65,000 A

 

 

 

 

 

Line-to-Ground

> 3,500

> 100,000 A

> 80,000 A

> 65,000 A

Neutral-to-Ground

> 3,500

> 100,000 A

> 80,000 A

> 65,000 A

 

 

 

 

 

Line-to-Line

> 3,500

> 100,000 A

> 80,000 A

> 65,000 A

Per Phase

> 7,000

> 200,000 A

> 160,000 A

> 130,000 A

 

 

 

 

 

Duty life cycle tested to survive 20kV, 10kA, IEEE C62.41 Category C3 surge current with less than 5% degradation of clamping voltage.

EMI/RFI Noise Rejection Values

Single Unit

Frequency

 

System Installation

34 dB

100 kHz

 

51 dB

 

 

 

 

51 dB

1 MHz

 

94 dB

54 dB

10 MHz

 

114 dB

 

 

 

 

48 dB

100 MHz

 

120 dB

All systems EMI-RFI noise or attenuation rejection values are in compliance with test

 

and evaluation procedures outlined in NEMA LS 1-1992, paragraphs 2.2.11 and 3.11.

 

UL 1449 RATINGS

 

Line to

Line to

Line

Neutral

System Voltage

Neutral

Ground

to Line

to Ground

120/208 or 120/240

400 V

400 V

800 V

400 V

 

 

 

 

 

208, 240, 277 or 277/480

800 V

800 V

1500 V

800 V

 

 

 

 

 

Enclosure

NEMA 1 rated.

Surface mount dimensions are 12” x 20” x 6”.

Flush mount unit is 12” x 21.5” x 6”.

Weight is 15 lbs.

How To Order Liebert Liebert PanelGuardExtension

Liebert Corporation

1050 Dearborn Drive

P.O. Box 29186

Columbus, Ohio 43229

800 877 9222 Phone (U.S. &

Canada Only)

614 888 0246 Phone (Outside U.S.)

614 841 6022 FAX

Via Leonardo Da Vinci 8

Zona Industriale Tognana

35028 Piove Di Sacco (PD)

Italy

39 049 9719 111 Phone

39 049 5841 257 FAX

Emerson Network Power Asia Pacific

7/F., Dah Sing Financial Centre

108 Gloucester Rd, Wanchai

Hong Kong

852 25722201 Phone

852 28029250 FAX

liebert.com

Technical Support

800 288 6169 Toll-Free

607 7214 88652484 Phone

607 722 8713 Fax

While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.

© 2008 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.

All names referred to are trademarks or registered trademarks of their respective owners.

® Liebert is a registered trademark of the Liebert Corporation.

SL-22065 (R06/08) Printed in USA

Emerson Network Power.

The global leader in enabling
Business-Critical Continuity.
Surge Current Capacity AC Power

Phase configuration

Code

1 Ph, 3W+G. 120/240 VAC

120S

3 Ph, 4W+G. 120/208 VAC

120Y

3 Ph, 4W+G. 277/480 VAC

277Y

Other phase configurations available.

 

Please consult factory.

 

kA per mode/per phase

Code

65 kA per mode, 130 kA per phase

65

80 kA per mode, 160 kA per phase

80

100 kA per mode, 200 kA per phase

100

Trim type

Code

Surface mount trim

S

Flush mount trim

F

Monitoring options

Code

Standard Status LEDs only

-00

LEDs, Audible Alarm, Counter

-01

LEDs, Audible Alarm

-02

LEDs, Counter

-03

 

 

How to construct a Liebert PanelGuard

 

Extension (LPGE) model #

Code

1. Liebert PanelGuard Extension

LPGE

2. Phase configuration

120S

3. kA per mode /per phase

65

4. Trim type: surface mount

S

5. Monitoring options

-01

Sample model #: LPGE120S65S-01

EMI/RFI Noise Rejection Values Connectivity

UL 1449 RATINGS DC Power

Enclosure Embedded Computing

NEMA 1 rated. Embedded Power

How To Order Liebert Liebert PanelGuard™ Extension Monitoring

Liebert Corporation Outside Plant

liebert.com Power Switching & Controls Emerson Network Power. Precision Cooling

The global leader in enabling Racks & Integrated Cabinets Business-Critical Continuity™. Services

 AC Power Surge Protection

Emerson Network Power.com

Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2008 Emerson Electric Co.

Page 2
Image 2
Emerson 65 Specifications, Surge Current Capacity, EMI/RFI Noise Rejection Values, UL 1449 RATINGS, Enclosure, AC Power