3
Specifications
Connection Type Series connected
Agency Listings UL 1449, UL 1283, CSA
Protection Modes All modes standard (Line to Neutral,
Line to Ground, Neutral to Ground,
Line to Line); any combination optional
EMI/RFI Filtering Normal mode — 60 dB maximum from
10 kHz to 500 MHz; Common mode
50 dB maximum from 10 kHz to 500 MHz
Response Time less than .5 nanoseconds
Load Regulation 1% no load to full load
Enclosure NEMA 12 standard; options include
NEMA 3R, 4, 4X and caseless for
switchgear applications
Current Model Number Surge Current Capability Dimensions
Rating Configuration (xxx=voltage code) per phase (L-N or L-L+L-G) (inches) Weight
ABCDEFLbs.
30A Single Phase L-L FXXXL30 100kA 24.0 20.0 9.0 21.25 10.0 .44 40
30A Single Phase L-N FXXXN30 100kA 24.0 20.0 9.0 21.25 10.0 .44 35
30A Split Phase FXXXS30 100kA 24.0 20.0 9.0 25.25 14.0 .44 45
30A Three Phase Delta FXXXD30 100kA 24.0 20.0 9.0 25.25 14.0 .44 50
30A Three Phase Wye FXXXY30 100kA 24.0 20.0 9.0 25.25 14.0 .44 60
60A Single Phase L-L FXXXL60 100kA 24.0 20.0 9.0 21.25 10.0 .44 40
60A Single Phase L-N FXXXN60 100kA 24.0 20.0 9.0 21.25 10.0 .44 35
60A Split Phase FXXXS60 100kA 24.0 20.0 9.0 25.25 14.0 .44 45
60A Three Phase Delta FXXXD60 100kA 24.0 20.0 9.0 25.25 14.0 .44 50
60A Three Phase Wye FXXXY60 100kA 24.0 20.0 9.0 25.25 14.0 .44 60
100A Single Phase L-L FXXXL100 150kA 30.0 24.0 9.0 31.25 18.0 .44 65
100A Single Phase L-N FXXXN100 150kA 30.0 24.0 9.0 31.25 18.0 .44 60
100A Split Phase FXXXS100 150kA 30.0 24.0 9.0 31.25 18.0 .44 70
100A Three Phase Delta FXXXD100 150kA 30.0 24.0 9.0 31.25 18.0 .44 70
100A Three Phase Wye FXXX Y100 150kA 30.0 24.0 9.0 31.25 18.0 .44 80
125A Single Phase L-L FXXXL225 150kA 30.0 24.0 9.0 31.25 18.0 .44 65
125A Single Phase L-N FXXXN225 150kA 30.0 24.0 9.0 31.25 18.0 .44 60
225A Split Phase FXXXS225 150kA 30.0 24.0 9.0 31.25 18.0 .44 70
225A Three Phase Delta FXXXD225 150kA 30.0 24.0 9.0 31.25 18.0 .44 70
225A Three Phase Wye FXXXY225 150kA 30.0 24.0 9.0 31.25 18.0 .44 80
400A Three Phase Delta FXXXD400 150kA 48.0 36.0 12.0 49.25 30.0 .44 275
400A Three Phase Wye FXXX Y400 150kA 48.0 36.0 12.0 49.25 30.0 .44 300
800A Three Phase Delta FXXXD800 choose 200 or 300 kA 60.0 48.0 12.0 - - - 500
800A Three Phase WyeFXXXY800 choose 200 or 300 kA 60.0 48.0 12.0 - - - 530
1200A Three Phase Delta FXXXD1200 choose 200 or 300 kA 60.0 48.0 20.0 - - - 700
1200A Three Phase Wye FXXXY1200 choose 200 or 300 kA 60.0 48.0 20.0 - - - 750
2000A Three Phase Delta FXXXD2000 choose 200 or 300 kA 60.0 48.0 20.0 - - - 875
2000A Three Phase Wye FXXXY2000 choose 200 or 300 kA 60.0 48.0 20.0 - - - 950
4000A Three Phase Delta FXXXD4000 choose 200 or 300 kA 60.0 48.0 20.0 - - - 1175
4000A Three Phase Wye FXXXY4000 choose 200 or 300 kA 60.0 48.0 20.0 - - - 1300

How To Specify The Appropriate Model:

1) Go to Chart A, choose your Current Rating from column one and corresponding Configuration from column two.
2) Follow column two across to column three to determine your Model Number.
3) Refer to Chart Bto determine the Voltage Code from the available choices. Substitute the Voltage Code for “XXX.”
(Use the first three digits of the Voltage Code for split phase and three phase configurations).
4) Finally, to complete your model number, go to the last column or (Monitoring Options) and choose the suffix for Standard Features (-06) or
Optional Features (-03).

Chart A - Active Tracking®Filter Systems

Chart B - Nominal Voltage Codes

(substitute for “xxx” to complete model number)
Single Phase, 2 wire plus ground 100, 110, 120, 230, 240, 277, 346, 400, 480, 600
Split Single Phase, 3 wire plus ground 100/173, 110/190, 120/208 or 240, 230/400, 277/480, 346/600
Three Phase Delta, 3 wire plus ground 208, 240, 380, 400, 480, 600
Three Phase Delta Hi-Leg, 4 wire plus ground 120/240
Three Phase Wye, 3 or 4 wire plus ground 100/173, 110/190, 120/208, 230/400, *277/480, 346/600
A
D
F
E
B
- Diameter
C
- Optional Features
2.0” MAX
- Standard Features
.50” MAX
Line Frequency 47 to 63 Hz
Line Voltage ±15% nominal
Temperature -40 to +60°C
Operating Humidity 0 to 95% noncondensing
Altitude 0 to 18,000 feet
Audible Noise Less than 45 dBa
Operational Crest Factor 3.0
Warranty 10-Years Parts and
5-Years On-Site Labor
Monitoring
Options
Standard Features Include:
•Audible Alarm,
Transient Counter
•Door LEDs indicating
unit status
Individual Module
Status LEDs, and -06
Form C Dry Contacts
for Remote System
Integrity Monitoring
and Indication of
Under Voltage, Phase
and/or Power Loss.
Optional Features Include:
•Additional Seven-
Digit Transient Counter
for Normal Mode -03
•Additional Form C
Dry Contacts
NOTES: For configurations not
mentioned, including caseless
units for switchgear applications
and ungrounded delta units,
consult factory. For different levels
of surge current capacity mode
and/or phase, consult factory.
CODE:
L - N = Line to Neutral
L - G = Line to Ground
N - G = Neutral to Ground
L - L = Line to Line
*Valid for 220/380 and
240/415 per IEC.
Example Model Number:
F120Y30-03