Specifications

Connection Type

Series connected

Agency Listings

UL 1449, UL 1283, CSA

Protection Modes

All modes standard (Line to Neutral,

 

Line to Ground, Neutral to Ground,

 

Line to Line); any combination optional

EMI/RFI Filtering

Normal mode — 60 dB maximum from

 

10 kHz to 500 MHz; Common mode

 

50 dB maximum from 10 kHz to 500 MHz

Response Time

less than .5 nanoseconds

Load Regulation

1% no load to full load

Enclosure

NEMA 12 standard; options include

 

NEMA 3R, 4, 4X and caseless for

 

switchgear applications

Line Frequency

47 to 63 Hz

Line Voltage

±15% nominal

Temperature

-40 to +60°C

Operating Humidity

0 to 95% noncondensing

Altitude

0 to 18,000 feet

Audible Noise

Less than 45 dBa

Operational Crest Factor

3.0

Warranty

10-Years Parts and

 

5-Years On-Site Labor

 

 

 

 

 

 

- Optional Features

F - Diameter

 

 

2.0” MAX

 

 

- Standard Features

 

 

 

 

 

 

.50” MAX

 

 

 

 

 

 

 

 

 

 

 

A

D

E

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

B

How To Specify The Appropriate Model:

1)Go to Chart A, choose your Current Rating from column one and corresponding Configuration from column two.

2)Follow column two across to column three to determine your Model Number.

3)Refer to Chart B to determine the Voltage Code from the available choices. Substitute the Voltage Code for “XXX.” (Use the first three digits of the Voltage Code for split phase and three phase configurations).

4)Finally, to complete your model number, go to the last column or (Monitoring Options) and choose the suffix for Standard Features (-06) or Optional Features (-03).

Chart A - Active Tracking® Filter Systems

Current

 

Model Number

Surge Current Capability

 

 

Dimensions

 

 

 

 

Monitoring

 

Rating

Configuration

(xxx=voltage code)

per phase (L-N or L-L+L-G)

 

 

 

(inches)

 

 

Weight

Options

 

 

 

 

 

A

B

C

 

D

E

F

Lbs.

Standard Features Include:

 

30A

Single Phase L-L

FXXXL30

100kA

24.0

20.0

9.0

 

21.25

10.0

.44

40

 

•Audible Alarm,

 

30A

Single Phase L-N

FXXXN30

100kA

24.0

20.0

9.0

 

21.25

10.0

.44

35

 

Transient Counter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Door LEDs indicating

 

30A

Split Phase

FXXXS30

100kA

24.0

20.0

9.0

 

25.25

14.0

.44

45

 

 

 

 

unit status

 

30A

Three Phase Delta

FXXXD30

100kA

24.0

20.0

9.0

 

25.25

14.0

.44

50

 

 

 

 

• Individual Module

 

30A

Three Phase Wye

FXXXY30

100kA

24.0

20.0

9.0

 

25.25

14.0

.44

60

 

Status LEDs, and

-06

60A

Single Phase L-L

FXXXL60

100kA

24.0

20.0

9.0

 

21.25

10.0

.44

40

 

Form C Dry Contacts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for Remote System

 

60A

Single Phase L-N

FXXXN60

100kA

24.0

20.0

9.0

 

21.25

10.0

.44

35

 

 

 

 

Integrity Monitoring

 

60A

Split Phase

FXXXS60

100kA

24.0

20.0

9.0

 

25.25

14.0

.44

45

 

 

 

 

and Indication of

 

60A

Three Phase Delta

FXXXD60

100kA

24.0

20.0

9.0

 

25.25

14.0

.44

50

 

Under Voltage, Phase

 

60A

Three Phase Wye

FXXXY60

100kA

24.0

20.0

9.0

 

25.25

14.0

.44

60

 

and/or Power Loss.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Optional Features Include:

 

100A

Single Phase L-L

FXXXL100

150kA

30.0

24.0

9.0

 

31.25

18.0

.44

65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Additional Seven-

 

100A

Single Phase L-N

FXXXN100

150kA

30.0

24.0

9.0

 

31.25

18.0

.44

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digit Transient Counter

 

100A

Split Phase

FXXXS100

150kA

30.0

24.0

9.0

 

31.25

18.0

.44

70

 

 

 

 

for Normal Mode

-03

100A

Three Phase Delta

FXXXD100

150kA

30.0

24.0

9.0

 

31.25

18.0

.44

70

 

 

 

• Additional Form C

 

100A

Three Phase Wye

FXXXY100

150kA

30.0

24.0

9.0

 

31.25

18.0

.44

80

 

Dry Contacts

 

125A

Single Phase L-L

FXXXL225

150kA

30.0

24.0

9.0

 

31.25

18.0

.44

65

 

NOTES: For configurations not

 

125A

Single Phase L-N

FXXXN225

150kA

30.0

24.0

9.0

 

31.25

18.0

.44

60

 

 

 

 

mentioned, including caseless

 

225A

Split Phase

FXXXS225

150kA

30.0

24.0

9.0

 

31.25

18.0

.44

70

 

 

 

 

units for switchgear applications

225A

Three Phase Delta

FXXXD225

150kA

30.0

24.0

9.0

 

31.25

18.0

.44

70

 

and ungrounded delta units,

 

225A

Three Phase Wye

FXXXY225

150kA

30.0

24.0

9.0

 

31.25

18.0

.44

80

 

consult factory. For different levels

 

 

 

 

 

 

 

 

 

 

 

 

 

of surge current capacity mode

400A

Three Phase Delta

FXXXD400

150kA

48.0

36.0

12.0

 

49.25

30.0

.44

275

 

and/or phase, consult factory.

 

400A

Three Phase Wye

FXXXY400

150kA

48.0

36.0

12.0

 

49.25

30.0

.44

300

 

 

 

 

800A

Three Phase Delta

FXXXD800

choose 200 or 300 kA

60.0

48.0

12.0

 

-

-

-

500

CODE:

 

800A

Three Phase Wye

FXXXY800

choose 200 or 300 kA

60.0

48.0

12.0

 

-

-

-

530

L - N = Line to Neutral

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L - G = Line to Ground

 

1200A

Three Phase Delta

FXXXD1200

choose 200 or 300 kA

60.0

48.0

20.0

 

-

-

-

700

 

 

N - G = Neutral to Ground

 

1200A

Three Phase Wye

FXXXY1200

choose 200 or 300 kA

60.0

48.0

20.0

 

-

-

-

750

 

 

L - L = Line to Line

 

2000A

Three Phase Delta

FXXXD2000

choose 200 or 300 kA

60.0

48.0

20.0

 

-

-

-

875

*Valid for 220/380 and

 

2000A

Three Phase Wye

FXXXY2000

choose 200 or 300 kA

60.0

48.0

20.0

 

-

-

-

950

 

 

 

 

 

 

 

 

 

 

 

 

 

 

240/415 per IEC.

 

4000A

Three Phase Delta

FXXXD4000

choose 200 or 300 kA

60.0

48.0

20.0

 

-

-

-

1175

 

 

 

 

4000A

Three Phase Wye

FXXXY4000

choose 200 or 300 kA

60.0

48.0

20.0

 

-

-

-

1300

 

 

Chart B - Nominal Voltage Codes

(substitute for “xxx” to complete model number)

Single Phase, 2 wire plus ground

100, 110, 120, 230, 240, 277, 346, 400, 480, 600

Split Single Phase, 3 wire plus ground

100/173, 110/190, 120/208 or 240, 230/400, 277/480, 346/600

Three Phase Delta, 3 wire plus ground

208, 240, 380, 400, 480, 600

Three Phase Delta Hi-Leg, 4 wire plus ground

120/240

Three Phase Wye, 3 or 4 wire plus ground

100/173, 110/190, 120/208, 230/400, *277/480, 346/600

Example Model Number:

F120Y30-03

3

Page 3
Image 3
Emerson Active Tracking Warranty Years Parts Years On-Site Labor, Current, Dimensions Monitoring, Options, Audible Alarm