Specifications
Connection Type | Series connected |
Agency Listings | UL 1449, UL 1283, CSA |
Protection Modes | All modes standard (Line to Neutral, |
| Line to Ground, Neutral to Ground, |
| Line to Line); any combination optional |
EMI/RFI Filtering | Normal mode — 60 dB maximum from |
| 10 kHz to 500 MHz; Common mode |
| 50 dB maximum from 10 kHz to 500 MHz |
Response Time | less than .5 nanoseconds |
Load Regulation | 1% no load to full load |
Enclosure | NEMA 12 standard; options include |
| NEMA 3R, 4, 4X and caseless for |
| switchgear applications |
Line Frequency | 47 to 63 Hz |
Line Voltage | ±15% nominal |
Temperature | |
Operating Humidity | 0 to 95% noncondensing |
Altitude | 0 to 18,000 feet |
Audible Noise | Less than 45 dBa |
Operational Crest Factor | 3.0 |
Warranty |
|
|
|
|
|
|
|
|
| - Optional Features | ||
F - Diameter |
|
| 2.0” MAX | |||||
|
| - Standard Features | ||||||
|
|
|
|
|
| .50” MAX |
|
|
|
|
|
|
|
|
|
|
|
A
D
E |
|
|
|
|
|
| C |
|
|
|
|
|
| ||
|
|
|
B
How To Specify The Appropriate Model:
1)Go to Chart A, choose your Current Rating from column one and corresponding Configuration from column two.
2)Follow column two across to column three to determine your Model Number.
3)Refer to Chart B to determine the Voltage Code from the available choices. Substitute the Voltage Code for “XXX.” (Use the first three digits of the Voltage Code for split phase and three phase configurations).
4)Finally, to complete your model number, go to the last column or (Monitoring Options) and choose the suffix for Standard Features
Chart A - Active Tracking® Filter Systems
Current |
| Model Number | Surge Current Capability |
|
| Dimensions |
|
|
|
| Monitoring |
| ||
Rating | Configuration | (xxx=voltage code) | per phase |
|
|
| (inches) |
|
| Weight | Options |
| ||
|
|
|
| A | B | C |
| D | E | F | Lbs. | Standard Features Include: |
| |
30A | Single Phase | FXXXL30 | 100kA | 24.0 | 20.0 | 9.0 |
| 21.25 | 10.0 | .44 | 40 |
| •Audible Alarm, |
|
30A | Single Phase | FXXXN30 | 100kA | 24.0 | 20.0 | 9.0 |
| 21.25 | 10.0 | .44 | 35 |
| Transient Counter |
|
|
|
|
|
|
|
|
|
|
|
|
|
| • Door LEDs indicating |
|
30A | Split Phase | FXXXS30 | 100kA | 24.0 | 20.0 | 9.0 |
| 25.25 | 14.0 | .44 | 45 |
|
| |
|
| unit status |
| |||||||||||
30A | Three Phase Delta | FXXXD30 | 100kA | 24.0 | 20.0 | 9.0 |
| 25.25 | 14.0 | .44 | 50 |
|
| |
|
| • Individual Module |
| |||||||||||
30A | Three Phase Wye | FXXXY30 | 100kA | 24.0 | 20.0 | 9.0 |
| 25.25 | 14.0 | .44 | 60 |
| Status LEDs, and | |
60A | Single Phase | FXXXL60 | 100kA | 24.0 | 20.0 | 9.0 |
| 21.25 | 10.0 | .44 | 40 |
| Form C Dry Contacts |
|
|
|
|
|
|
|
|
|
|
|
|
|
| for Remote System |
|
60A | Single Phase | FXXXN60 | 100kA | 24.0 | 20.0 | 9.0 |
| 21.25 | 10.0 | .44 | 35 |
|
| |
|
| Integrity Monitoring |
| |||||||||||
60A | Split Phase | FXXXS60 | 100kA | 24.0 | 20.0 | 9.0 |
| 25.25 | 14.0 | .44 | 45 |
|
| |
|
| and Indication of |
| |||||||||||
60A | Three Phase Delta | FXXXD60 | 100kA | 24.0 | 20.0 | 9.0 |
| 25.25 | 14.0 | .44 | 50 |
| Under Voltage, Phase |
|
60A | Three Phase Wye | FXXXY60 | 100kA | 24.0 | 20.0 | 9.0 |
| 25.25 | 14.0 | .44 | 60 |
| and/or Power Loss. |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Optional Features Include: |
|
100A | Single Phase | FXXXL100 | 150kA | 30.0 | 24.0 | 9.0 |
| 31.25 | 18.0 | .44 | 65 |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| • Additional Seven- |
|
100A | Single Phase | FXXXN100 | 150kA | 30.0 | 24.0 | 9.0 |
| 31.25 | 18.0 | .44 | 60 |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| Digit Transient Counter |
|
100A | Split Phase | FXXXS100 | 150kA | 30.0 | 24.0 | 9.0 |
| 31.25 | 18.0 | .44 | 70 |
|
| |
|
| for Normal Mode | ||||||||||||
100A | Three Phase Delta | FXXXD100 | 150kA | 30.0 | 24.0 | 9.0 |
| 31.25 | 18.0 | .44 | 70 |
| ||
|
| • Additional Form C |
| |||||||||||
100A | Three Phase Wye | FXXXY100 | 150kA | 30.0 | 24.0 | 9.0 |
| 31.25 | 18.0 | .44 | 80 |
| Dry Contacts |
|
125A | Single Phase | FXXXL225 | 150kA | 30.0 | 24.0 | 9.0 |
| 31.25 | 18.0 | .44 | 65 |
| NOTES: For configurations not |
|
125A | Single Phase | FXXXN225 | 150kA | 30.0 | 24.0 | 9.0 |
| 31.25 | 18.0 | .44 | 60 |
|
| |
|
| mentioned, including caseless |
| |||||||||||
225A | Split Phase | FXXXS225 | 150kA | 30.0 | 24.0 | 9.0 |
| 31.25 | 18.0 | .44 | 70 |
|
| |
|
| units for switchgear applications | ||||||||||||
225A | Three Phase Delta | FXXXD225 | 150kA | 30.0 | 24.0 | 9.0 |
| 31.25 | 18.0 | .44 | 70 |
| and ungrounded delta units, |
|
225A | Three Phase Wye | FXXXY225 | 150kA | 30.0 | 24.0 | 9.0 |
| 31.25 | 18.0 | .44 | 80 |
| consult factory. For different levels | |
|
|
|
|
|
|
|
|
|
|
|
|
| of surge current capacity mode | |
400A | Three Phase Delta | FXXXD400 | 150kA | 48.0 | 36.0 | 12.0 |
| 49.25 | 30.0 | .44 | 275 | |||
| and/or phase, consult factory. |
| ||||||||||||
400A | Three Phase Wye | FXXXY400 | 150kA | 48.0 | 36.0 | 12.0 |
| 49.25 | 30.0 | .44 | 300 |
| ||
|
|
| ||||||||||||
800A | Three Phase Delta | FXXXD800 | choose 200 or 300 kA | 60.0 | 48.0 | 12.0 |
| - | - | - | 500 | CODE: |
| |
800A | Three Phase Wye | FXXXY800 | choose 200 or 300 kA | 60.0 | 48.0 | 12.0 |
| - | - | - | 530 | L - N = Line to Neutral |
| |
|
|
|
|
|
|
|
|
|
|
|
|
| L - G = Line to Ground |
|
1200A | Three Phase Delta | FXXXD1200 | choose 200 or 300 kA | 60.0 | 48.0 | 20.0 |
| - | - | - | 700 |
| ||
| N - G = Neutral to Ground |
| ||||||||||||
1200A | Three Phase Wye | FXXXY1200 | choose 200 or 300 kA | 60.0 | 48.0 | 20.0 |
| - | - | - | 750 |
| ||
| L - L = Line to Line |
| ||||||||||||
2000A | Three Phase Delta | FXXXD2000 | choose 200 or 300 kA | 60.0 | 48.0 | 20.0 |
| - | - | - | 875 | *Valid for 220/380 and |
| |
2000A | Three Phase Wye | FXXXY2000 | choose 200 or 300 kA | 60.0 | 48.0 | 20.0 |
| - | - | - | 950 |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| 240/415 per IEC. |
|
4000A | Three Phase Delta | FXXXD4000 | choose 200 or 300 kA | 60.0 | 48.0 | 20.0 |
| - | - | - | 1175 |
| ||
|
|
| ||||||||||||
4000A | Three Phase Wye | FXXXY4000 | choose 200 or 300 kA | 60.0 | 48.0 | 20.0 |
| - | - | - | 1300 |
|
|
Chart B - Nominal Voltage Codes
(substitute for “xxx” to complete model number)
Single Phase, 2 wire plus ground | 100, 110, 120, 230, 240, 277, 346, 400, 480, 600 |
Split Single Phase, 3 wire plus ground | 100/173, 110/190, 120/208 or 240, 230/400, 277/480, 346/600 |
Three Phase Delta, 3 wire plus ground | 208, 240, 380, 400, 480, 600 |
Three Phase Delta | 120/240 |
Three Phase Wye, 3 or 4 wire plus ground | 100/173, 110/190, 120/208, 230/400, *277/480, 346/600 |
Example Model Number:
3