F92-0656 & F92-0935

Regulated L.P. to Natural Gas

Conversion Kits

INSTALLATION INSTRUCTIONS

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.

!WARNING

This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer's instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a fire, explo- sion, or production of carbon monoxide may result, causing property damage, personal injury, or loss of life. The qualified service agency performing the work assumes the responsibility for the proper conversion of this appliance with this kit.

Regulator

 

Regulator

Plastic

Cover Screw

 

Cover

 

Regulator

 

 

Screw

Plastic Regulator

 

Adjustment

 

 

Adjustment

 

Regulator

Screw

Screw

Regulator

 

Regulator

Spring

 

Sleeve

 

Regulator

 

Spring

 

 

 

 

Sleeve

 

Figure 1. 36C and 36D

Figure 2. 36E, 36G and 36J

Single Stage

Models

Models

 

APPLICATION

These regulated L.P. Gas to regulated Natural Gas conver- sion kits allow the 36C, 36D, 36E, 36G, 36H and 36J Series gas valves to be used on natural gas applications. These conversion kits are for use on all single stage, fast and slow open models and 36G, 36H and 36J two stage models.

TO CONVERT FROM L.P. TO NATURAL GAS

1.Remove regulator cover screw.

2.Remove regulator adjustment screw (beneath the cover screw).

3.Remove L.P. regulator spring from regulator sleeve.

4.Insert the natural gas regulator spring (provided in the conversion kit) into the regulator sleeve.

5.Replace the regulator adjustment screw. Then adjust the outlet pressure to the appliance manufacturer's specified outlet pressure.

6.Replace the regulator cover screw.

7.Attach the WARNING label (provided in the kit) to the gas valve where it can be readily seen. Also attach the small round NAT. GAS label to the top of the regulator cover screw.

8.If present, pilot burner is to be used, the pilot orifice must be replaced.

Conversion back to L.P. Gas use may be made at a later date by retaining the L.P. spring (removed in step 3, above) and following the same procedures (except for burner pressure given in step 5).

Regulator

Cover Screw

Plastic Regulator

Adjustment Screw

Regulator Spring

If low outlet pressure greater than 5" W.C. is required, use an additional kit to convert low pressure.

If low outlet pressure greater

 

than 5" W.C. is required, use

 

an additional kit to

Regulator

convert low pressure.

Cover Screw

 

 

Plastic Regulator

 

Adjustment Screw

 

Regulator Spring

Figure 3. 36G and 36J

2-Stage models

Figure 4. 36H Single Stage

and 2-Stage models

! WARNING

 

VALVE CONVERTED FOR USE ON

Natural Gas

NATURAL GAS. IMPROPER OPERATION

COULD RESULT IN DEATH OR SERIOUS

INJURY.

Regulator

! MISE EN GARDE

Spring

SOUPAPE CONVERTIE POUR USAGE

NAT

SUR GAZ NATUREL.

UN FONCTIONNEMENT INAPPROPRIÉ

GAS

PEUT PROVOQUER LA MORT OU DES

Natural Gas

BLESSURES GRAVES.

WARNING Label

Label

Figure 5. Contents of kit

PART NO. 37-5380B

www.white-rodgers.com

Replaces 37-5380A 0640

Page 1
Image 1
Emerson F92-0935, F92-0656 installation instructions Remove regulator cover screw, Replace the regulator cover screw