Standard Features Optional Features
Unit Status Indicators
The unit has an integral status circuit that monitors the operational status of all modes of protection, including Line to Neutral, Line to Ground, and Neutral to Ground. In the unlikely event that protection is reduced,
the green LED will go out and the red LED will be lit. LED indication shall be provided internal and external to the product.
Enclosure
The unit is housed in a heavy duty, steel, NEMA 12
Undervoltage Detection
System monitoring will indicate an undervoltage at 70% of nominal.
Phase and Power Loss Monitoring
System monitoring will indicate a loss of any phase or loss of power.
Noise Attentuation
The filter provides insertion loss up to 60 dB from 100 kHz to 100 MHz per 50 Ohm Insertion Loss Methodology from
Audible Alarm
The system is equipped with an audible alarm activated when summary alarm contacts are activated. An ON/OFF button is provided to silence the alarm, and an alarm
Agency Listing
The specified unit is UL 1449 (Second Edition) Listed, UL 1283 Listed, and CUL Listed. Control Concepts/Liebert is also company certified ISO 9001 for manufacturing, design, and service.
Warranty
A full
Form C Dry Contacts
Two sets of electronically isolated form C dry contacts are provided, (two normally open, two normally closed) for remote monitoring.
Integral Fused Disconnect
A 200k AIC integral disconnect switch located within the system enclosure with an external manual operator.
Transient Counter
The system can be equipped with a transient counter which totals transient surges that deviate from the sine wave envelop by more than 125 volts. The counter is located on the unit's front cover and features an 8 digit LCD, lithium batteries (with
Remote Monitor Panel
A self contained, UL Listed monitoring panel. Input power to the monitoring panel is equipped with a
The monitor has an audible alarm, red and green LEDs silence switch, and a test switch.
MIL Std. 220A.
Overcurrent Protection
All components are individually fused and unit is UL rated for 200k AIC for safe operation.
Life Cycle Testing
The system is life cycle tested to survive multiple 10kA, 20KV, IEEE C62.41 Category C3 transients with less than 5% degradation of clamping voltage. The minimum numbers of surges the unit shall be able to protect against are 8,000 per phase.
3