Emerson SL-19534 Dual Unit Control Board, Jumper settings for servicing InteleCool2 unit

Models: SL-19534

1 8
Download 8 pages 8.37 Kb
Page 6
Image 6
Figure 1 Dual Unit Control Board

Control Startup

Figure 1 Dual Unit Control Board

1

2

P5

P5

P4

Reverse

Normal

to LED

 

Panel

3

4

 

 

R

 

DRAWING IS

1/2

Unit

Y

2

NOT TO SCALE

 

 

 

W

 

 

R

 

 

1/2

Unit

 

Y

1

 

W

 

 

 

TB1

1

2

Slow

P3

Fast

 

3

4

P1

1

2

3P1 to

4Thermostat

5

6

7

8/4Day

4/2Day

2/1Day

Lead1

Lead2

S e

P2 r

v i c e

! WARNING

InteleCool and InteleCool2 units contain potentially lethal voltage. Shut off power before performing any service work.

During service, the P2 jumper should be placed on the pins that identify the unit NOT being serviced. Refer to Table 2 for required jumper pin connections. The P2 setting will override the lead unit setting until the jumper is returned to the proper number-of-days location.

Table 2

Jumper settings for servicing InteleCool2 unit

 

 

 

To service desired unit

Jumper Settings P2

Jumper Setting P4

 

 

 

 

 

Unit 1

Lead 2

Pins 3 & 4 (normal)

 

 

 

 

 

Unit 2

Lead 1

Pins 3 & 4 (normal)

 

 

 

 

4

Page 6
Image 6
Emerson SL-19534 Dual Unit Control Board, Jumper settings for servicing InteleCool2 unit, Drawing Is, Not To Scale