Type 99 Pressure Reducing Regulators
Introduction
Scope of the Manual
This manual describes and provides instructions and parts lists for Type 99 pressure reducing regulators complete with standard P590 Series integral filter. However, complete instructions and parts listing for the Type 1301F pilot supply regulator, and other Fisher® equipment, such as monitoring pilots will be found in separate instruction manuals.
Description
The Type 99 gas regulators provide a broad capacity for controlled pressure ranges and capacities
in a wide variety of distribution, industrial, and commercial applications.
A Type 99 regulator has a Type 61L (low pressure), Type 61H (high pressure), or a Type 61HP (extra high pressure) pilot integrally mounted to the actuator casing as shown in Figure 1. The Type 99 regulator can handle up to 1000 psig (69,0 bar) inlet pressures (the 1000 psig (69,0 bar) regulator requires a
Type 1301F pilot supply regulator and a Type H110 pop relief valve). The pilot supply regulator reduces inlet pressure to a usable 200 psig (13,8 bar) for the extra high pressure pilot. This regulator comes standard with
Specifications
!Warning
Since a
W2676
Figure 1. Type 99 Regulator with Type 61H (high pressure) Pilot
the maximum inlet pressure shown on the nameplate of either unit. When inlet pressure exceeds the pilot limitation, a pilot supply reducing regulator and/or relief valve will be required.
Specifications and ratings for various Type 99 constructions are listed in the Specifications section on page 2. Some specifications for a given regulator as it originally comes from the factory are stamped on nameplates located on the pilot and actuator spring cases. A tag (key 159, Parts List) additionally may be installed on the pilot to indicate a regulator with