Emerson Process Management manual Fixed I/O Subsystem, ControlWave LP Analog Input Module

Models: ControlWave LP

1 11
Download 11 pages 30.84 Kb
Page 3
Image 3
Fixed I/O Subsystem

Product Data Document

420DS-4c

July 19, 2007 - Page

Bristol® ControlWave® LP

Fixed I/O Subsystem

ControlWave LP Discrete Input Module

Number of Points: 16 Fixed

Input Voltage Range: 12V or 24V

Input Filtering: 1 millisecond or 30 milliseconds

Input Configuration: Contact Closure, internally or externally sourced on a point by point basis.

Jumper Configurable

Input Current: 2.5 mA +/- 10%

‘1’ State Voltage: 90 % of input voltage range

‘0’ State Voltage: 10 % of input voltage range

Interrupt Generation: On change of state transition on a point by point basis

Bus Access: Sixteen bit wide

Electrical isolation: 1500 VDC

Electrical isolation: 1500 VDC

Surge suppression: 500Vdc MOV to chassis 38 VDC MOV across input and to Field Common Meets ANSI/IEEE C37.90-1978

Terminations: Pluggable, maximum wire size is 16 gauge

Status indication: 16 LED’s (one per point)

ControlWave LP Discrete Output Module

ControlWave LP Analog Input Module

Number of Points: 8

Input Configuration: Isolated Voltage Input: 1-5V

Isolated Current Input: 4-20 mA

Powered Current Loop: 4-20 mA

Accuracy: 0.1 % of span @ 25 deg. C 0.2 % of span –20 deg.C to + 70 deg. C 0.3 % of span –40 deg.C to + 70 deg. C

Isolated Voltage/Current: 38 VDC referenced to isolated common

Powered Current Loop: 0 V referenced to isolated common When a field supply common is connectesd to the AI system the isolated common is connected to the field supply common

Input Filtering: 300 milliseconds to 99.75% of signal input.

Channel Settling Time: 300 microseconds

Conversion Time: 200 microseconds

On Board References: 1V, 5V - optional

Surge Suppression: 500Vdc MOV isolated common to chassis 38 VDC MOV across input signals and (-) input to chassis Meets ANSI/ IEEE C37.90-1978

Terminations: Pluggable, maximum wire size is 16 gauge

Number of Points: 8

Output Type: Open Drain

Max Operating Voltage: 38 VDC

Max. Operating Freq: 20 Hz

Sink Current: 100 mA Maximum

Electrical Isolation: 1500 VDC

Surge Suppression: 500Vdc MOV isolated common to chassis 38 VDC MOV across input signals and (-) input to chassis Meets ANSI/ IEEE C37.90-1978

Terminations: Pluggable, maximum wire size is 16 gauge

Bus Access: 16 Bits Wide

ControlWave LP High Speed Counter Module

Number of points: 4

Input Voltage Range: 12V or 24V

Input Filtering: 10 KHz max.

Input Filtering: 20 microseconds

Input Configuration: Set/Reset inputs, contact closure, externally sourced on point by point basis with jumper configurtion.

Input Current: 2.5 mA +/- 10%

Bus Access: 16 Bits Wide

Remote Automation Solutions

Website: www.EmersonProcess.com/Remote

Page 3
Image 3
Emerson Process Management manual Fixed I/O Subsystem, ControlWave LP Discrete Input Module, Bristol ControlWave LP