Product Data Document
July 19, 2007 - Page
Bristol® ControlWave® LP
Fixed I/O Subsystem
ControlWave LP Discrete Input Module
•Number of Points: 16 Fixed
•Input Voltage Range: 12V or 24V
•Input Filtering: 1 millisecond or 30 milliseconds
•Input Configuration: Contact Closure, internally or externally sourced on a point by point basis.
Jumper Configurable
•Input Current: 2.5 mA +/- 10%
•‘1’ State Voltage: 90 % of input voltage range
•‘0’ State Voltage: 10 % of input voltage range
•Interrupt Generation: On change of state transition on a point by point basis
•Bus Access: Sixteen bit wide
•Electrical isolation: 1500 VDC
•Electrical isolation: 1500 VDC
•Surge suppression: 500Vdc MOV to chassis 38 VDC MOV across input and to Field Common Meets ANSI/IEEE
•Terminations: Pluggable, maximum wire size is 16 gauge
•Status indication: 16 LED’s (one per point)
ControlWave LP Discrete Output Module
ControlWave LP Analog Input Module
•Number of Points: 8
•Input Configuration: Isolated Voltage Input:
•Isolated Current Input:
•Powered Current Loop:
•Accuracy: 0.1 % of span @ 25 deg. C 0.2 % of span
•Isolated Voltage/Current: 38 VDC referenced to isolated common
•Powered Current Loop: 0 V referenced to isolated common When a field supply common is connectesd to the AI system the isolated common is connected to the field supply common
•Input Filtering: 300 milliseconds to 99.75% of signal input.
•Channel Settling Time: 300 microseconds
•Conversion Time: 200 microseconds
•On Board References: 1V, 5V - optional
•Surge Suppression: 500Vdc MOV isolated common to chassis 38 VDC MOV across input signals and
•Terminations: Pluggable, maximum wire size is 16 gauge
•Number of Points: 8
•Output Type: Open Drain
•Max Operating Voltage: 38 VDC
•Max. Operating Freq: 20 Hz
•Sink Current: 100 mA Maximum
•Electrical Isolation: 1500 VDC
•Surge Suppression: 500Vdc MOV isolated common to chassis 38 VDC MOV across input signals and
•Terminations: Pluggable, maximum wire size is 16 gauge
•Bus Access: 16 Bits Wide
ControlWave LP High Speed Counter Module
•Number of points: 4
•Input Voltage Range: 12V or 24V
•Input Filtering: 10 KHz max.
•Input Filtering: 20 microseconds
•Input Configuration: Set/Reset inputs, contact closure, externally sourced on point by point basis with jumper configurtion.
•Input Current: 2.5 mA +/- 10%
•Bus Access: 16 Bits Wide
Remote Automation Solutions
Website: www.EmersonProcess.com/Remote