Product Data Document

420DS-6c / D301311X012

January 29, 2009 - Page 4

Bristol® ControlWave® Express

 

 

ControlWave Express Process I/O

ControlWave Express I/O module is designed to maximize usability while minimizing installation and maintenance.

The I/O module (bottom card) provides a mix of analog and digital inputs and outputs that are a perfect fit for small RTU applications.

2 DI/PI (on CPU)

1 RTD input on 14 MHz CPU

4 DI

2 DO

2 selectable DI or DO

2 selectable DI or HSC

Optional 3 AI or 3 AI and 1 AO

Features

Convenient pluggable local terminations

All configuration jumpers and switches accessible without disassembly of circuit boards

Termination points for external loop power supply

Specifications

All I/O

I/O access: 50 ms with 33 MHz CPU, 250 ms with 14 MHz CPU

1 second for 2 DI/PI inputs on CPU board

Surge protection: Meets C37.90-1978

30 Vdc transorb between signal and ground

Terminations are pluggable and accept a maximum wire size of 16 gauge

Power consumption is stated for each I/O module type measured at the input supply and does not include loop power

Pulse/Digital Inputs

Inputs located on base CPU board

Number of points: up to 2 non-interrupting inputs

Internally sourced, dry contact single ended inputs

Scan rate: Once per second

Input filter: 20 microSec

Voltage Range: Internally sourced dry contact input - 3.3 Vdc

On state: >1.6 V, Off state <1.3V

Input current : 200 µA for low power applications

Power consumption:

200 µA input, all inputs ON: 0.002 watt

Used as Pulse Input:

Frequency Range: 0-10 kHz

Debounce: None

Accumulator: 16 bit

RTD Input

Input available on 14 MHz Ultra Low Power

CPU only

Specifications are for the interface only, not includ- ing the RTD probe or wiring

RTD Conversion Accuracy: ± 0.1°C, or ± 0.1% of reading, whichever is greater

Remote Automation Solutions

Website: www.EmersonProcess.com/Remote

Page 4
Image 4
Emerson Process Management manual ControlWave Express Process I/O, All I/O, Pulse/Digital Inputs, RTD Input