WCP Dimensions and Specifications
NOTE: Due to EMI’s ongoing development programs, design and specifications may change without notice.
DISCHARGE AIR SPEED AND FLOW | ||||
| (230V High Speed Fan) | |||
Model | CFM | Coil | FPM | Throw/Ft. |
|
|
|
|
|
9/12 | 310 | Dry | 960 | 16 |
15/18 | 600 | Dry | 1412 | 26 |
24/30 | 750 | Dry | 1400 | 25 |
36 | 750 | Dry | 1400 | 25 |
WCP PHYSICAL DIMENSIONS
Model | Width “A” | Height “B” | Depth “C” | Width “D” | Width “E” | Width “F” | Width “G” | Width “H” | Width “I” | Shipping |
|
|
|
|
|
|
|
|
|
| Wt. |
09/12 | 36½” | 14½” | 10¾” | 32” | 9” | 24½” | 8” | 18” | 16” | 85 |
15/18 | 47½” | 14½” | 10¾” | 32” | 10” | 34½” | 8” | 18” | 27” | 115 |
24/30 | 57½” | 14½” | 10¾” | 42” | 10” | 44½” | 8” | 27” | 28” | 115 |
36 | 57½” | 17” | 11¼” | 42” | 10” | 44½” | 10½” | 25” | 28½” | 115 |
WCP ELECTRICAL SPECIFICATIONS
| Volts/HZ/ |
| Fan | Total | Min. | Min. | Max | |
Model # |
|
|
| Ampacity | ||||
Phase | FLA |
| HP | Amps | Volt | Fuse (1) | ||
|
|
|
|
|
|
| (1) |
|
09A, 12A | 115/60/1 | 0.64 |
| 0.03 | 0.64 | 104 | 0.8 | 15 |
09D, 12D | 208/230/60/1 | 0.34 |
| 0.02 | 0.34 | 197 | 0.43 | 15 |
15A, 18A | 115/60/1 | 1.2 |
| 0.083 | 1.2 | 104 | 1.5 | 15 |
15D, 18D | 208/230/60/1 | 0.56 |
| 0.07 | 0.56 | 197 | 0.7 | 15 |
24A, 30A | 115/60/1 | 1.2 |
| 0.083 | 1.2 | 104 | 1.5 | 15 |
24D, 30D | 208/230/60/1 | 0.56 |
| 0.07 | 0.56 | 197 | 0.7 | 15 |
(1) If electric heaters are installed, use Min Amp and Max Fuse from Heater Options Chart.
WCP ELECTRIC HEAT OPTIONS
Model | Voltage | KW | Heater | Total | Min. Cir. | Max |
|
|
| Amps | Amps | Amps | Fuse |
9/12 | 230 | 3 | 13.1 | 13.5 | 16.8 | 20 |
15/18 | 230 | 3 | 13.1 | 13.6 | 17 | 20 |
24/30 | 230 | 5 | 21.7 | 22.3 | 27.9 | 30 |
36 | 230 | 5 | 21.7 | 22.3 | 27.9 | 30 |
WCP OBSERVED SOUND VALUES
(230V High Speed Fan)
Model | DbA |
9/12 | 48 |
15/18 | 51 |
24/30 | 54 |
3654
CONNECTIONS
WCP
Chilled Line | Drain Size | |
Size | ||
|
1/2” I.D. | 1/2” I.D. |
5/8” I.D. | 1/2” I.D. |
5/8” I.D. | 1/2” I.D. |
3/4” I.D. | 1/2” I.D. |
Enviromaster International LLC
5780 Success Drive, Rome, NY 13440
www.enviromaster.com
WCP Chilled Water Air Handler | Made in Rome, New York, USA |