WCP Dimensions and Specifications

WCP Dimensions and Specifications

NOTE: Due to EMI’s ongoing development programs, design and specifications may change without notice.

DISCHARGE AIR SPEED AND FLOW

 

(230V High Speed Fan)

Model

CFM

Coil

FPM

Throw/Ft.

 

 

 

 

 

9/12

310

Dry

960

16

15/18

600

Dry

1412

26

24/30

750

Dry

1400

25

36

750

Dry

1400

25

WCP PHYSICAL DIMENSIONS

Model

Width “A”

Height “B”

Depth “C”

Width “D”

Width “E”

Width “F”

Width “G”

Width “H”

Width “I”

Shipping

 

 

 

 

 

 

 

 

 

 

Wt.

09/12

36½”

14½”

10¾”

32”

9”

24½”

8”

18”

16”

85

15/18

47½”

14½”

10¾”

32”

10”

34½”

8”

18”

27”

115

24/30

57½”

14½”

10¾”

42”

10”

44½”

8”

27”

28”

115

36

57½”

17”

11¼”

42”

10”

44½”

10½”

25”

28½”

115

WCP ELECTRICAL SPECIFICATIONS

 

Volts/HZ/

 

Fan

Total

Min.

Min.

Max

Model #

 

 

 

Ampacity

Phase

FLA

 

HP

Amps

Volt

Fuse (1)

 

 

 

 

 

 

 

(1)

 

09A, 12A

115/60/1

0.64

 

0.03

0.64

104

0.8

15

09D, 12D

208/230/60/1

0.34

 

0.02

0.34

197

0.43

15

15A, 18A

115/60/1

1.2

 

0.083

1.2

104

1.5

15

15D, 18D

208/230/60/1

0.56

 

0.07

0.56

197

0.7

15

24A, 30A

115/60/1

1.2

 

0.083

1.2

104

1.5

15

24D, 30D

208/230/60/1

0.56

 

0.07

0.56

197

0.7

15

(1) If electric heaters are installed, use Min Amp and Max Fuse from Heater Options Chart.

WCP ELECTRIC HEAT OPTIONS

Model

Voltage

KW

Heater

Total

Min. Cir.

Max

 

 

 

Amps

Amps

Amps

Fuse

9/12

230

3

13.1

13.5

16.8

20

15/18

230

3

13.1

13.6

17

20

24/30

230

5

21.7

22.3

27.9

30

36

230

5

21.7

22.3

27.9

30

WCP OBSERVED SOUND VALUES

(230V High Speed Fan)

Model

DbA

9/12

48

15/18

51

24/30

54

3654

CONNECTIONS

WCP

Chilled Line

Drain Size

Size

 

1/2” I.D.

1/2” I.D.

5/8” I.D.

1/2” I.D.

5/8” I.D.

1/2” I.D.

3/4” I.D.

1/2” I.D.

Enviromaster International LLC

5780 Success Drive, Rome, NY 13440

www.enviromaster.com

WCP Chilled Water Air Handler

Made in Rome, New York, USA

Page 2