!WARNING
PERSONAL INJURY HAZARD
Becauseoftheweightandsizeoftherangehood canopy,twoormorepeopleareneededtomove and safely install the rangehood canopy.
Failure to properly lift rangehood could result in damage to the product or personal injury.
PLAN THE DUCTWORK
The Pellicano rangehood is designed to offer wide flexibility of installations. The rangehood can be ducted vertically or horizontally through a 6" round vent. The unit can also be installed in a recirculating configuration. FIGURES 1 and 2 show vertical and horizontalinstallationsforthisunit. FIGURE3shows recirculating installation. For direct rear venting, remove the 10 screws on the outside edge of the exhaust plate and flip motor to the rear exit.
The Pellicano requires 6" round ductwork. To en- sure that the blower performs to its highest possible capacity, ductwork should be as short and straight as possilbe.
WARNING! BEFORE MAKING ANY CUTS OR HOLES FOR INSTALLATION, DETERMINE WHICH VENTING METHOD WILL BE
CALCULATE THE DUCTRUN LENGTH
The ductrun should not exceed 35 equivalent feet if ducted with the required minimum of 6" round duct. Calculate the length of the ductwork by adding the equivalent feet in FIGURE 4 for each piece of duct in the system. An example is given in FIGURE 5.
45˚ Elbow |
| 3.0 feet | |
90˚ Elbow |
| 5.0 feet | |
90˚ Flat Elbow | 12.0 feet | ||
Wall Cap |
| 0.0 feet | |
FIGURE 4 |
|
|
|
|
|
| |
|
|
| |
9 Feet Straight Duct |
| 9.0 feet | |
2 - 90˚ Elbows | 10.0 feet | ||
Wall Cap |
| 0.0 feet | |
Total System |
| 19.0 feet |
|
FIGURE 5 |
|
|
|
|
|
|
|
For best results, use no more than three 90° elbows. Make sure that there is a minimum of 24" of straight duct between elbows if more than one is used. Do not install two elbows together. If you must elbow right away, do it as far away from the hood's exhaust opening as possible.
FIGURE 1 | FIGURE 2 |
ceiling | ceiling |
open space | enclosed soffit |
| |
upper | upper |
cabinet | cabinet |
rangehood | rangehood |
cooking surface | cooking surface |
side view | side view |
FIGURE 3A | FIGURE 3B |
FIGURE 3C | FIGURE 3D |
RECIRCULATING INSTALLATIONS
For recirculating installations, Charcoal Filters are necessary. Remove all grease filters and set aside. Attach one charcoal filter to each end of the blower. Each charcoal filter attaches to the black grid on the side of the blower. Rotate the filter clockwise to install and counterclockwise to remove (FIGURE 3C). Replace all grease filters. Some ductwork must be installed to exhaust the rangehood back into the kitchen, either at the top of the cabinet (FIGURE 3A) or at the face or side of the soffit (FIGURE 3B). A plastic vent grate (FIGURE 3D) supplied with the rangehood can be used to cover the duct opening. This duct work must not terminate into a
dead air space. | Version 10/05 - Page 5 |