SG SeriesTM UPS PLUS®

-1TX

& -1TXI

2kVA - 3kVA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model Number

 

 

SG2K-1TX

 

 

 

SG3K-1TX

 

 

 

 

 

SG2K-1TXI

 

 

 

SG3K-1TXI

 

 

Nominal VA

 

 

2000

 

 

 

3000

 

 

 

Electrical Input

 

 

 

 

 

 

 

 

 

 

Nominal AC Voltage

 

 

 

 

120Vac

 

 

 

 

AC Voltage Range

 

 

 

80 – 138V

 

 

 

 

Current – Amps

 

14.2

 

 

 

21.4

 

 

 

Frequency

 

 

 

50/60 Hz ± 5%

(Auto – Tracking)

 

 

 

 

Power Factor Correction

 

 

 

> 0.95

 

 

 

 

Efficiency (Typical)

 

 

 

 

> 83%

 

 

 

 

Electrical Output

 

 

 

 

 

 

 

 

 

 

Watts

 

1400

 

 

 

2100

 

 

 

Galvanic Isolation

 

 

-1TX = 120Vac output

with derived neutral

 

 

 

 

 

 

 

-1TXI = 120/240Vac Split-Phase

 

 

 

 

AC Voltages

 

 

-1TX = 100, 110, 115 or 120Vac (Switch Selectable)

 

 

 

 

 

 

 

-1TXI = 120/240Vac Split-Phase Only

 

 

Frequency

 

 

 

50/60 Hz (Auto Tracking)

 

 

 

 

Frequency Stability

 

 

 

± 0.3% (Battery Mode)

 

 

 

 

Voltage Regulation

 

 

 

 

± 2%

 

 

 

 

Step Load Change

 

 

 

± 7% for 100% load variation

 

 

 

 

Harmonic Distortion

 

 

< 3% Linear Load, < 5% Non-Linear Load

 

 

 

Overload

 

 

 

105% load for 50 Seconds

 

 

 

 

Crest Ratio

 

 

 

 

3:1

 

 

 

 

Battery

 

 

 

 

 

 

 

 

 

 

DC Voltage

 

 

72Vdc

 

 

 

96V

 

 

 

Type

 

 

12V, 7AH Sealed Lead

Acid Maintenance-Free

 

 

 

Back Up Time

@ Full Load

 

7 Minutes

 

 

 

5.5 Minutes

 

 

 

 

@ 1/2 Load

 

20 Minutes

 

 

 

15 Minutes

 

 

Recharge Time

 

 

 

8 Hours

to 90%

 

 

 

 

Battery times are approximate.

 

 

 

 

 

 

 

 

 

Transfer Time

 

 

 

 

 

 

 

 

 

 

Line Fails/Recovers

 

 

 

 

Zero

 

 

 

 

UPS to Bypass or Reverse

 

 

 

< 4ms

 

 

 

 

After Overload

 

 

 

Auto Transfer to UPS

 

 

 

 

Electrical Connections

 

 

 

 

 

 

 

 

 

Input

 

 

Fixed & Strain Relieved 6’ Cord with 5-20P

 

Fixed & Strain Relieved 6’ Cord with L5-30P

 

 

 

 

 

 

 

 

 

 

 

 

Output

 

 

(3) 5-15R & (2) 5-20R

 

L5-30R & (1) Duplex 5-20R

 

 

 

 

 

 

 

 

 

 

External battery

 

 

(1) Anderson style battery connector

with cover plate on the UPS rear panel

 

 

 

 

 

 

 

 

 

 

 

 

Contact the factory for other input/output options.

Environmental

Operating Temperature

0º C - 40º C (32º F to 104º F)

Humidity

10% to 95% Non – Condensing

Altitude

7,000 Feet

Cooling

Low Velocity Forced Air Fans

Audible Noise @ 1 Meter

<50dBA

Controls and Indicators

LED

Line, Inverter, Battery Reserve, Load, Bypass, Alarm, Crest, Battery & Load Capacity Level

Audible Alarms

DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temp., Over Load, Fault Alarm

Communications

RS-232 Serial Port

Mechanical

Dimensions H x W x D inches (mm)

 

15.1 x 7.6 x 30.0 (384 x 193 x 720)

Weight

lb. (kg)

138.7 (63)

 

150 (68)

Agency Listing

 

 

UL 1778 & CUL Listed, FCC Class A

24

Page 26
Image 26
Falcon SG800-1T, SG800-2T specifications 2kVA 3kVA