| SG SeriesTM UPS PLUS® | & | 2kVA - 3kVA | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| Model Number |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| |||
| Nominal VA |
|
| 2000 |
|
|
| 3000 |
|
|
| Electrical Input |
|
|
|
|
|
|
|
|
|
| Nominal AC Voltage |
|
|
|
| 120Vac |
|
|
| |
| AC Voltage Range |
|
|
| 80 – 138V |
|
|
| ||
| Current – Amps |
| 14.2 |
|
|
| 21.4 |
|
| |
| Frequency |
|
|
| 50/60 Hz ± 5% | (Auto – Tracking) |
|
|
| |
| Power Factor Correction |
|
|
| > 0.95 |
|
|
| ||
| Efficiency (Typical) |
|
|
|
| > 83% |
|
|
| |
| Electrical Output |
|
|
|
|
|
|
|
|
|
| Watts |
| 1400 |
|
|
| 2100 |
|
| |
| Galvanic Isolation |
|
| with derived neutral |
|
| ||||
|
|
|
|
|
|
|
| |||
| AC Voltages |
|
|
|
| |||||
|
|
|
|
|
| |||||
| Frequency |
|
|
| 50/60 Hz (Auto Tracking) |
|
|
| ||
| Frequency Stability |
|
|
| ± 0.3% (Battery Mode) |
|
|
| ||
| Voltage Regulation |
|
|
|
| ± 2% |
|
|
| |
| Step Load Change |
|
|
| ± 7% for 100% load variation |
|
|
| ||
| Harmonic Distortion |
|
| < 3% Linear Load, < 5% |
|
| ||||
| Overload |
|
|
| 105% load for 50 Seconds |
|
|
| ||
| Crest Ratio |
|
|
|
| 3:1 |
|
|
| |
| Battery |
|
|
|
|
|
|
|
|
|
| DC Voltage |
|
| 72Vdc |
|
|
| 96V |
|
|
| Type |
|
| 12V, 7AH Sealed Lead | Acid |
|
| |||
| Back Up Time | @ Full Load |
| 7 Minutes |
|
|
| 5.5 Minutes |
|
|
|
| @ 1/2 Load |
| 20 Minutes |
|
|
| 15 Minutes |
| |
| Recharge Time |
|
|
| 8 Hours | to 90% |
|
|
| |
| Battery times are approximate. |
|
|
|
|
|
|
|
| |
| Transfer Time |
|
|
|
|
|
|
|
|
|
| Line Fails/Recovers |
|
|
|
| Zero |
|
|
| |
| UPS to Bypass or Reverse |
|
|
| < 4ms |
|
|
| ||
| After Overload |
|
|
| Auto Transfer to UPS |
|
|
| ||
| Electrical Connections |
|
|
|
|
|
|
|
| |
| Input |
|
| Fixed & Strain Relieved 6’ Cord with |
| Fixed & Strain Relieved 6’ Cord with |
|
| ||
|
|
|
|
|
|
|
|
| ||
| Output |
|
| (3) |
|
| ||||
|
|
|
|
|
|
|
| |||
| External battery |
|
| (1) Anderson style battery connector | with cover plate on the UPS rear panel |
| ||||
|
|
|
|
|
|
|
|
|
|
|
Contact the factory for other input/output options.
Environmental
Operating Temperature | 0º C - 40º C (32º F to 104º F) |
Humidity | 10% to 95% Non – Condensing |
Altitude | 7,000 Feet |
Cooling | Low Velocity Forced Air Fans |
Audible Noise @ 1 Meter | <50dBA |
Controls and Indicators
LED | Line, Inverter, Battery Reserve, Load, Bypass, Alarm, Crest, Battery & Load Capacity Level |
Audible Alarms | DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temp., Over Load, Fault Alarm |
Communications |
Mechanical
Dimensions H x W x D inches (mm) |
| 15.1 x 7.6 x 30.0 (384 x 193 x 720) | ||
Weight | lb. (kg) | 138.7 (63) |
| 150 (68) |
Agency Listing |
|
| UL 1778 & CUL Listed, FCC Class A |
24