DRY CONTACT & OPTO COUPLER INTERFACE BOARD OPTIONS
Typical Falcon Dry Contact Relay Board
JP1 | J1 |
JP2 | J2 |
JP3 | J3 |
|
|
|
| PIN & JUMPER ASSIGNMENT FOR THE FALCON | ||||||||
|
|
|
|
|
| UA88374 RELAY OPTION BOARD | ||||||
|
|
|
|
|
|
|
|
| (no | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| PIN |
|
|
|
|
|
| DESCRIPTION |
|
|
| |
| 1 |
|
|
| Low Battery ( When UPS reaches low battery, contact activates) |
|
|
| ||||
|
|
|
|
| (J1, |
|
|
| ||||
| 2 |
|
|
| JP2 shorted = Low Battery common & all other shorted JP commons |
|
|
| ||||
|
|
|
|
| JP2 open = common for low battery only |
|
|
| ||||
| 3 |
|
|
| Utility Loss N.O. ( At loss of utility voltage, contact activates) |
|
|
| ||||
| 4 |
|
|
| Utility Loss N.C. ( At loss of utility voltage, contact activates) |
|
|
| ||||
| 5 |
|
|
| JP1 shorted = Utility Loss common & all other shorted JP commons |
|
|
| ||||
|
|
|
|
| JP1 open = Utility Loss common only |
|
|
| ||||
| 6 |
|
|
| Remote Shutdown common |
|
|
| ||||
| 7 |
|
|
| Remote Shutdown |
|
|
| ||||
|
|
|
|
| (J2, |
|
|
| ||||
|
|
|
|
|
|
|
| |||||
|
|
|
|
| and seven, | while the UPS is on battery, will turn the UPS off. |
|
|
| |||
|
|
|
|
|
|
|
| |||||
|
|
|
|
| seven, while | the UPS is on battery, will turn the UPS off. |
|
|
| |||
| 8 |
|
|
| Alarm (Upon a UPS fault or failure the contact activates) |
|
|
| ||||
|
|
|
|
| (J3, |
|
|
| ||||
| 9 |
|
|
| JP3 shorted = Alarm common & all other shorted JP commons |
|
|
| ||||
|
|
|
|
| JP3 open = Alarm common only |
|
|
| ||||
|
|
|
|
| PIN & JUMPER ASSIGNMENT FOR THE FALCON | |||||||
|
|
|
|
|
|
| UA88376 RELAY OPTION BOARD | |||||
|
|
|
|
|
|
|
|
| (with | |||
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |||||
| PIN |
|
|
|
|
|
|
| DESCRIPTION |
|
| |
| 1 |
| Low Battery ( When UPS reaches low battery, contact activates) |
|
| |||||||
|
|
| (J1, |
| ||||||||
| 2 |
| JP2 shorted = Low Battery common & all other shorted JP commons |
|
| |||||||
|
|
| JP2 open = common for low battery only |
| ||||||||
| 3 |
| Utility Loss N.O. ( At loss of utility voltage, contact activates) |
|
| |||||||
| 4 |
| Utility Loss N.C. ( At loss of utility voltage, contact activates) |
|
| |||||||
| 5 |
| JP1 shorted = Utility Loss common & all other shorted JP commons |
|
| |||||||
|
|
| JP1 open = Utility Loss common only |
| ||||||||
| 6 |
| Remote Shutdown common |
|
| |||||||
| 7 |
| Remote Shutdown |
|
| |||||||
|
|
| (J2, |
| ||||||||
|
|
|
| |||||||||
|
|
| and seven, | while the UPS is on battery, will turn the UPS off. |
| |||||||
|
|
|
| |||||||||
|
|
| seven, while | the UPS is on battery, will turn the UPS off. |
| |||||||
| 8 |
| On Bypass or Alarm (Upon the UPS going to bypass or a UPS failure |
|
| |||||||
|
|
| the contact activates) |
| ||||||||
|
|
| (J3, |
| ||||||||
| 9 |
| JP3 shorted = On bypass, Alarm common & all other shorted JP |
|
| |||||||
|
|
| commons |
| ||||||||
|
|
| JP3 open = On bypass, Alarm common only |
|
|
16