SG SeriesTM UPS PLUS®

 

 

 

2kVA & 3kVA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model Number

 

SG2K-1T

 

SG2K-2T

 

 

SG3K-1T

 

SG3K-2T

 

SG2K-2TXI

 

 

SG3K-2TX

 

 

Nominal VA

 

 

2000

 

 

3000

 

2000

 

 

3000

 

 

 

Electrical Input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal AC Voltage

 

120V

 

230V

 

 

120V

 

230V

 

 

 

230V

 

 

 

AC Voltage Range

 

87 – 140V

 

170 – 275V

 

 

87 – 140V

 

170 – 275V

 

 

170 – 275V

 

 

 

Current – Amps

 

14.2

 

7.4

 

 

21.4

 

11.2

 

7.5

 

 

 

11.3

 

 

 

Frequency

 

 

 

 

 

 

50/60 Hz ± 5%

(Auto – Tracking)

 

 

 

 

 

 

 

 

 

 

Power Factor Correction

 

 

 

 

 

 

 

> 0.95

 

 

 

 

 

 

 

 

 

 

 

Efficiency (Typical)

 

 

 

 

> 86%

 

 

 

 

 

 

> 85%

 

 

 

 

Electrical Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Watts

 

 

1400

 

 

 

2100

 

1400

 

 

 

2100

 

 

 

AC Voltage

 

100V

 

200V

 

 

100V

 

200V

120V

 

208V

 

 

120V

 

208V

 

 

(Switchable)

 

110V

 

220V

 

 

110V

 

220V

(700W

 

220V

 

 

(1400W

 

220V

 

 

 

 

115V

 

230V

 

 

115V

 

230V

each

 

230V

 

 

Max.)

 

230V

 

 

 

 

 

 

 

 

5-20R)

 

 

 

 

 

 

 

 

 

120V

 

240V

 

 

120V

 

240V

 

240V

 

 

 

 

240V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency

 

 

 

 

 

 

50/60 Hz

(Auto Tracking )

 

 

 

 

 

 

 

 

 

 

Frequency Stability

 

 

 

 

 

 

± 0.3% (Battery Mode)

 

 

 

 

 

 

 

 

 

 

Voltage Regulation

 

 

 

 

 

± 2%

 

 

 

± 5%

 

 

 

± 3%

 

 

 

Step Load Change

 

 

 

 

 

 

± 7% for 100% load v ariation

 

 

 

 

 

 

 

 

 

 

Harmonic Distortion

 

 

 

 

 

 

< 3% Linear Load, < 5% Non -Linear Load

 

 

 

 

 

 

 

 

Overload

 

 

 

 

 

 

105% load for 50 Seconds

 

 

 

 

 

 

 

 

 

 

Crest Ratio

 

 

 

 

 

 

 

3:1

 

 

 

 

 

 

 

 

 

 

 

Battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC Voltage

 

 

72V

 

 

 

 

 

 

96V

 

 

 

 

 

 

 

 

Type

 

 

 

 

 

 

12V, 7AH Sealed Lead Acid Maintenance -Free

 

 

 

 

 

 

 

 

Back Up Time

@ Full Load

7 Minutes

 

 

5.5 Minutes

7 Minutes

 

 

5.5 Minutes

 

 

 

@ 1/2 Load

20 Minutes

 

 

15 Minutes

20 Minutes

 

 

15 Minutes

 

 

Recharge Time

 

 

 

 

 

 

8 Hours to 90%

 

 

 

 

 

 

 

 

 

 

Battery times are approximate.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transfer Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Line Fails/Recovers

 

 

 

 

 

 

 

 

Zero

 

 

 

 

 

 

 

 

 

 

UPS to Bypass or Reverse

 

 

 

 

 

 

< 4ms

 

 

 

 

 

 

 

 

 

 

After Overload

 

 

 

 

 

 

Auto Transfer to UPS

 

 

 

 

 

 

 

 

 

 

Electrical Connections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

 

6’ Cord with

 

6’ Cord with

 

 

6’ Cord with

 

6’ Cord with

6’ Cord with 6 -20P, L6-20P

 

 

 

 

5-20P

 

6-20P, L6-20P

 

L5-30P

 

6-20P, L6-20P

 

 

or Schuko

 

 

 

 

 

 

 

or Schuko

 

 

 

 

or Schuko

 

 

 

 

 

 

 

 

 

 

Output

 

(6) 5-15R or

 

(6) IEC 320

 

 

(6) 5-15R or

 

(6) IEC 320

(2) 5-20R & (1) L6 -20R

 

 

 

 

 

(3) 5-15R &

 

or (1) L6-20R

 

 

(3) 5-15R &

 

or (1) L6-20R

 

 

 

 

 

 

 

 

 

 

 

 

(2) 5-20R

 

 

 

 

(2) 5-20R

 

 

 

 

 

 

 

 

 

 

 

 

Contact the factory for other input/output options.

Environmental

Operating Temperature

0º C - 40º C (32º F to 104º F)

Humidity

10% to 95% Non – Condensing

Altitude

7,000 Feet

Cooling

Low Velocity Forced Air Fans

Audible Noise @ 1 Meter

<50dBA

Controls and Indicators

LED

Line, Inverter, Battery Reserve, Load, Bypass, Alarm, Crest, Battery

& Load Capacity Level

Audible Alarms

DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency,

High Temp. , Over Load, Fault Alarm

Communications

RS-232 Serial Port (Bundled UPSilon 2000 Software)

Mechanical

Dimensions H x W x D inches (mm)

13.8 x 7.6 x 18.9

(350 x 193 x 480)

13.8 x 7.6 x 30 .0

(350 x 193 x 720)

Weight

lb. (kg)

68.4 (31)

81.4 (37)

150.0

(68)

Agency Listing

 

-1T Models: UL 1778, CUL, FCC

Class A

UL 1778, CUL,

FCC Class A

 

 

-2T Models: UL 1778, CUL , FCC Class A ; CE available with Schuko plug only

 

 

Available Options

Option A

60 Hz to 50 Hz Frequency Conversion

Option B

50 Hz to 60 Hz Frequency Conversion

Option C

SNMP/HTTP Network Card (Internal)

Option D

Standard Contact Closure Interface Card

Maintenance Bypass

Make-Before-Break External Wrap Around

External Battery Packs

Extended Run Time Battery Packs (minutes to hours)

Fast Battery Charger

Fast Charger internal to the Extended Battery Pack Cabinet (Required for battery times 2 hours or more.)

24