FieldServer FS-8700-22 X30 Appendix A. Advanced Topics, Appendix A.2. Using RSNetWorx

Models: FS-8700-22 X30

1 12
Download 12 pages 5.78 Kb
Page 10
Image 10
Appendix A. Advanced Topics

FS-8700-22_X30_DeviceNet_Slave Manual

Page 10 of 12

Appendix A. Advanced Topics

Appendix A.1. DeviceNet X30 LED indicators

LED 1 – Reserved

LED 2 – Network Status

Color

 

Frequency

Description

-

 

Off

Not powered / Not online

Green

On

Link OK, online, connected

Green

Flashing

Online, not connected

Red

On

Critical link failure

Red

Flashing

Connection timeout

LED 3 – Module Status

 

 

 

 

 

Color

 

Frequency

Description

-

 

Off

Not powered

Green

On

Device operational

Green

Flashing

Data size bigger than configured

Red

On

Unrecoverable fault

Red

Flashing

Minor fault

LED 4 – Reserved

Appendix A.2. Using RSNetWorx

Please refer to the following document on the HMS website, www.anybus.com APPLICATION NOTE: Establishing I/O communication between AnyBus-S DeviceNet using RsNetWorx for DeviceNet

Appendix A.3. Using RSLogix 5000

Please refer to the following document on the HMS website, www.anybus.com APPLICATION NOTE: Reading/writing data from AnyBus-S DeviceNet using ControlLogix5000 MSG instruction