FieldServer FS-8700-39 EST3 Description, Provided By the Supplier of 3rd Party Equipment Hardware

Models: FS-8700-39

1 21
Download 21 pages 23.97 Kb
Page 3
Image 3

FS-8700-39 EST3 Driver Manual

Page 3 of 21

 

 

1.EST3 Description

The EST3 External Communications Protocol (ECP) driver allows the FieldServer to transfer data to and from EST devices over RS-232 or RS-485 (with converter) serial ports using the EST3 ECP protocol. In the EST application the FieldServer always emulates a Client.

The FieldServer makes use of the following ECP Services:

Read Operations:

Report Service

Delta Service Write Operations:

Command Service

All read points are continually updated using the Report Service; response times are enhanced using Delta Service broadcasts by the EST3 panel.

The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer.

2.Driver Scope of Supply

2.1.Supplied By FieldServer Technologies for this Driver

FIELDSERVER

 

DESCRIPTION

 

TECHNOLOGIES PART #

 

 

 

 

 

FS-8915-10

7’ Patch Cable

FS-8917-03

RJ45 to DB9M Connector adapter

FS-8917-10

DB9F to terminal Adapter

FS-8700-39

EST3 ECP Driver Manual

2.2.Provided By the Supplier of 3rd Party Equipment

2.2.1.Hardware

PART #

DESCRIPTION

VERSION

 

EST3 Gateway

 

 

 

 

2.2.2.Required 3rd Party Configuration

The EST3 panel has to be set into the “Gateway Mode” using the EST3 Configuration tool (3- SDU)

Possible Protocols

 

ECP Type II

Supported

ECP Type II with Text

Not Supported

ECP Type III

Supported

ECP Type III with Text

Not Supported

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Page 3
Image 3
FieldServer FS-8700-39 EST3 Description, Provided By the Supplier of 3rd Party Equipment Hardware, ECP Type III with Text