4.2Client Side Connections

FS-8700-52 Notifier AM6000

Driver Manual

4.2Client Side Connections

Section Title

 

 

Connections

 

 

Column Title

Function

Legal Values

Port

Specify which port the device is

P1-P8, R1-R2

 

connected to the FieldServer

 

Baud*

Specify baud rate

2400 (Only baud rate supported by

 

 

the Notifier port)

Parity*

Specify parity

Even

Data_Bits*

Specify data bits

7

 

 

 

Stop_Bits*

Specify stop bits

1

 

 

 

Protocol

Specify protocol used

AM6000

 

 

 

Handshaking*

Specify hardware handshaking

None

Poll Delay*

Time between internal polls

0-32000 seconds

 

 

default 1 second

Example

 

 

//Client Side Connections

Connections

Port, Baud, Parity, Protocol, Data_bits, Handshaking, Poll_Delay

P8, 2400, Even, AM6000, 7,

None,

0.100s

4.3Client Side Nodes

Section Title

 

 

Nodes

 

 

Column Title

Function

Legal Values

Node_Name

Provide name for node

Up to 32 alphanumeric characters

Node_ID

Modbus station address of physical

1-255

 

server node

 

Protocol

Specify protocol used

Modbus_RTU, Modbus/TCP, etc.

Port

Specify which port the device is

P1-P8, R1-R2

 

connected to the FieldServer

 

Example

 

 

//Client Side Nodes

Nodes

Node_Name, Protocol, Port

Panel1, AM6000, P8

FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042

Visit our website: www.fieldserver.com E-mail: support@fieldserver.com

Page 5

Page 7
Image 7
FieldServer Client Side Connections, Client Side Nodes, None, default 1 second, FS-8700-52 Notifier AM6000, Function