Firex 4480, 484 Technical Specifications, Interconnect Quantities, Installation of Smoke Alarm

Models: 4480 484 480

1 2
Download 2 pages 42.89 Kb
Page 2
Image 2
Photoelectric

Photoelectric

Technical Specifications

Item

4480

484(C)

480(C)

 

 

 

 

 

Model

PAD

PG

PB

 

 

 

 

 

Product Weight

8 ounces

5.5 ounces

4.2 ounces

 

 

 

 

 

Operating Temperature

 

40˚–100˚F 4˚-38˚C

 

 

 

 

 

 

Electrical

120V AC, 60HZ, 50mA max,

120V AC, 60HZ, 50mA

9 Volt DC Battery Powered

Rating

9 Volt Battery Backup

 

 

 

 

 

 

 

Alarm Point

obs. 2.3 ± .95%/ft.

obs. 2.2 ± 1.2%/ft.

obs. 2.2 ± 1.2%/ft.

(Canadian)

 

(obs. 2.2 ± .75%/ft.)

(obs. 2.2 ± .75%/ft.)

 

 

 

 

 

Horn Output

 

85 decibels at 10 feet

 

 

 

 

 

 

 

Listing

 

UL 217 and ULC S531

 

 

 

 

 

 

 

Detection Type

 

Photoelectric Chamber

 

 

 

 

 

 

 

Humidity Rating

 

10%-93%

 

 

 

 

 

 

 

Interconnect Quantities

4480

Item

4480

4418

 

4518

 

5700*

(Model)

(PAD)

 

(AD)

 

(ADC)

(ADH)

 

 

 

 

 

 

 

 

Quantity

12

 

12

 

12

12

 

 

 

 

 

 

 

 

 

 

484

 

 

 

 

 

 

 

 

 

 

Item

484

 

406

 

 

41216

(Model)

(PG)

 

(G)

 

 

(GC)

 

 

 

 

 

 

 

Quantity

12

 

6

 

 

12

 

 

 

 

 

 

 

 

 

 

484(C)

 

 

 

 

 

 

 

 

 

 

Item

484(C)

 

406(C)

 

 

418(C)

(Model)

(PG)

 

(G)

 

 

(G)

 

 

 

 

 

 

 

Quantity

12

 

6

 

 

12

 

 

 

 

 

 

 

 

*Heat alarm item. Interconnectable up to 12 Firex AC/DC smoke alarms and 6 Firex heat alarms.

Installation of Smoke Alarm

This smoke alarm should be installed in accordance with NFPA’s Standard 72 (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269) and any local codes that apply. For the AC and AC/DC direct wire smoke alarms use #18 AWG minimum solid or stranded wire. When interconnecting, maximum wire length between any two is 1,500 feet for #18 AWG or 4,000 feet for #14 AWG (20 OHMS loop resistance). DO NOT connect to any other type or model of heat or smoke alarm. Connect smoke and heat alarms to a single AC branch circuit. If local codes do not permit, be sure the neutral wire is common to both phases.

Architectural Specifications

The 4480 shall be 1-3/8” high and 5” wide, powered by a 120V AC, 60Hz source with a 9 volt battery back-up. Nominal sensitivity shall be measured by U.L. at obs. 2.3 ± .95%/ft. A green continuous power on indicator shall be a built-in light emitting diode (LED) in the standby condition; a second red blinking LED shall indicate that a sufficient 9-volt battery back-up is present; when activated, the initiating alarm red LED shall flash while the interconnected alarms remain extinguished. A 70 day low battery signal shall be included.

The 484(C) shall be 1-3/16” high and 4-7/8”wide powered by a 120V AC, 60Hz source. Nominal sensitivity shall be measured by U.L. at obs. 2.2 ± 1.2%/ft. and by U.L.C. at obs. 2.2 ± .75%/ft. A power-on indicator shall be a built-in LED which blinks once per minute in the standby condition; when activated, the initiating alarm LED shall flash while the interconnected alarms remain extinguished.

The 4480 and the 484(C) shall be rated at no more than 0.5W in standby and have 100% solid state alarm circuits over an input range of 100-130V AC. The alarm shall mount to a single gang box, 4” octagon junction box, or a square-to- round drywall ring without screw removal. It shall have a Quick Connect molded harness and pigtail wiring.

The 480(C) shall be 1” high and 4” wide powered by a 9V DC battery source. Nominal sensitivity shall be measured by U.L. at obs. 2.2 ± 1.2%/ft. and by U.L.C. at obs. 2.2 ± .75%/ft. 100% solid state alarm circuits over an input range of 6.8-10V DC. A power-on indicator shall be a built-in LED which blinks once per minute in the standby condition and a 30 day low battery signal shall be included.

All Firex photoelectric smoke alarms shall be a Styleline designTM and have a photoelectric sensor. Operating temperature range shall be between 40° and 100°F (4°-38°C) and relative humidity range between 10%-93%. The test switch shall electronically activate the chamber to simulate smoke and check for proper operation. The electric horn shall have a level of 85 decibels at

10 feet and all units have a separate mounting bracket. Items 4480, 484, 480 shall meet the requirements of U.L. 217 and items 484(C) and 480(C) shall meet the requirements of U.L.C. S531.

Shipping Specifications

 

 

4480

484, 484(C)

480, 480(C)

 

Ind. Ctn. Dim.

5-1/8” x 5-1/8” x 1-1/2”

5-1/8” x 5-1/8” x 1-1/2”

4-1/8” x 4-1/8” x 1-1/2”

 

 

13cm x 13cm x 3.8cm

13cm x 13cm x 3.8cm

10.5cm x 10.5cm x 3.8cm

 

Master Ctn. Qty.

12

12

12

 

Master Ctn. Dim.

10-3/4” x 10-1/2” x 5-3/4”

10-3/4” x 10-1/2” x 5-3/4”

9-3/8” x 8-3/4” x 4-7/8”

 

 

27.3cm x 26.7cm x 14.6cm

27.3cm x 26.7cm x 14.6cm

23.8cm x 22.2cm x 12.4cm

 

Master Ctn. Wt.

6.4 lbs / 2.9kg

4.5 lbs / 2kg

3.5 lbs / 1.6kg

 

Pallet Quantity

864

864

2160

 

Pallet Dim.

40”L x 48”W x 40.5”D

40”L x 48”W x 40.5”D

48”L x 40”W x 48.3”D

 

 

102cm x 122cm x 103cm

102cm x 122cm x 103cm

122cm x 102cm x 103cm

 

 

 

 

 

Controls Americas

 

191 E. North Avenue

 

Carol Stream Illinois 60188 USA

For Technical Service

Customer Service Telephone +1 800 951 5526

Telephone +1 800 445 8299

Customer Service Facsimile +1 630 260 7299

Facsimile +1 630 260 7243

iccacustomerservice@invensys.com

technicalservice@invensys.com

www.icca.invensys.com

 

©2005 Invensys Controls Americas - #150-1358E

 