Firex 5700 Side View, Mounting Bracket Architectural Specifications, Technical Specifications

Models: 5700

1 2
Download 2 pages 16.6 Kb
Page 2
Image 2
Side View

Item 5700

Side View

5"

 

2.125"

Mounting Bracket

Architectural Specifications

The heat alarm shall be a StyleLine design™ (2-1/8" high, 5" diameter), powered by 120V AC, 60Hz source with a 9-volt battery back-up. The alarm shall have a fixed temperature sensor set to alarm at nominal 135°F (57°C). The alarm shall be rated at no greater than .05W in standby. Operating temperature range shall be between -10°F and 158°F; 10%-93% relative humidity; 100% solid state circuits over an input range of 100-130V AC. A green continuous power on indicator shall be a built-in light emitting diode (LED) in the standby condition; a second red blinking LED shall indicate that a sufficient 9-volt battery back-up is present; when activated; the initiating alarm red LED shall flash while the interconnected alarms remain extinguished. The test switch shall activate the alarm function by electronically simulating

a temperature greater than 135°. The alarm shall mount to a single gang box, 4" octagon junction box, or a square to round drywall ring without screw removal. It shall have a Quick Connect molded harness, pigtail wiring and separate mounting bracket. It shall meet the requirements of U.L. Standard 539 and 217.

Technical Specifications

Item

5700

Model

ADH

Product Weight

8.6 ounces

Operating Temperature

-10°F to 158°F (-23°C to 70°C)

Interconnect Qty

Up to 18 Firex devices maximum: 12 smoke alarm

 

items 5000, 4618 and 46182 (model FADC), 4518

 

(model ADC) and 4480 (model PAD). Up to 6 heat, car-

 

bon monoxide or smoke and carbon monoxide combi-

 

nation alarms maximum; Firex carbon monoxide alarm

 

item 6045 (model COQ8), Firex smoke and carbon

 

monoxide combination alarm item 7000 (model

 

FADCQ) or Firex heat alarm item 5700 (model ADH).

Electrical Rating

120V AC, 60HZ, 50mA max, 9 Volt Battery Back-up

Alarm Point

135°F (57°C) fixed temperature

 

triggers alarm

Horn Output

85 decibels at 10 feet

Listing

U.L. 539 and 217

U.L. Recommended

 

Coverage

2500 square feet

U.L. Recommended

 

Spacing

50 feet

Maximum Distance

 

from Wall

25 feet

Installation of Heat Alarm

This heat alarm should be installed in accordance with the NFPA’s Standard 72 (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269) and any local codes that apply.

Use #18 AWG minimum solid or stranded wire. When interconnecting, maximum wire length between any two is 1,500 feet for #18 AWG or 4,000 feet for #14 AWG (20 OHMS loop resistance).

DO NOT connect to any other type or model of heat or smoke alarm. Connect heat alarms to a single AC branch circuit. If local codes do not permit, be sure the neutral wire is common to both phases.

Climate Controls Americas

 

 

191 E. North Avenue

 

3505 Laird Road Unit #14

Carol Stream Illinois 60188 USA

Mississauga Ontario L5L 5Y7 Canada

Cust. Service Telephone

+1 800 951 5526

Cust. Service Telephone

+1 800 668 6958

Cust. Service Facsimile

+1 630 260 7299

Cust. Service Facsimile

+1 905 828 1265

For Technical Service

 

 

 

Telephone +1 800 445 8299

Visit us on the web at

 

Facsimile +1 630 260 7299

www.icca.invensys.com

mctechservices@invensys.com

 

 

©2003 Invensys Climate Controls Americas

Shipping Specifications

Individual Carton Dimensions

5-1/4" x 2-11/16" x 5-1/4"

Master Carton Quantity

10

Master Carton Dimensions

15-3/4" x 11-1/4" x 6"

Master Carton Weight

7.62 lbs.

150-1344E